Declaratory Statement DS 2012-81
ISSUE:
DS 2012-81. Petitioner seeks a
Declaratory Statement regarding the applicability of the 2010 Florida Building
Code to enclosures/buildings proposed as protection products for electrical
generating sets. The specific situations
are outlined below.
Background
Florida
Statutes
553.844 Windstorm loss mitigation; requirements for roofs
and opening protection.—
(4) Notwithstanding the provisions of this section,
exposed mechanical equipment or appliances fastened to a roof or installed on
the ground in compliance with the code using rated stands, platforms, curbs,
slabs, or other means are deemed to comply with the wind resistance
requirements of the 2007 Florida Building Code, as amended. Further support or
enclosure of such mechanical equipment or appliances is not required by a state
or local official having authority to enforce the Florida Building Code. This subsection expires on the effective date
of the 2013 Florida Building Code.
Florida Statutes
553.73 Florida Building Code.—
(6) The initial
adoption of, and any subsequent update or amendment to, the Florida Building
Code by the commission is deemed adopted for use statewide without adoptions by
local government. For a building permit for which an application is submitted
prior to the effective date of the Florida Building Code, the state minimum
building code in effect in the permitting jurisdiction on the date of the
application governs the permitted work for the life of the permit and any extension
granted to the permit.
SECTION 419
HOSPITALS
419.4.2.6 Heating,
ventilation and air-conditioning (HVAC) standards.
419.4.2.6.1.2 Their
fastening systems are designed to meet the wind load requirements of the
Florida Building Code, Building and they and all associated equipment are
protected as required by TAS 201, 202, and 203 in accordance with the
requirements of Sections 1626.2 through 1626.4 of this code from damage by
horizontal impact by a separate and independent structure that allows access to
all parts of the equipment at all times or
419.4.2.6.1.3 They
are completely protected by the equipment shrouding that meets the requirements
of TAS 201, 202, and 203 in accordance with the requirements of Sections 1626.2
through 1626.4 of this code.
419.4.2.9.6 The
emergency generator(s) shall be air or self-contained liquid cooled and it and
other essential electrical equipment shall be installed in a protected area(s)
designed and constructed to meet the structural requirements of the code and
debris impact requirements of Sections 1626.2 through 1626.4.
SECTION 420 NURSING HOMES
420.4.2.6 Heating,
ventilation and air conditioning (HVAC) standards.
420.4.2.6.1.2
Their fastening systems are designed to meet the wind load requirements of the
Florida Building Code, Building and they and all associated equipment are
protected as required by TAS 201, 202, and 203 in accordance with the
requirements of Sections 1626.2 thru 1626.4 of this code from damage by
horizontal impact by a separate and independent structure that allows access to
all parts of the equipment at all times; or
420.4.2.6.1.3 They
are completely protected by the equipment shrouding that meets the requirements
of TAS 201, 202, and 203 in accordance with the requirements of Sections 1626.2
through 1626.4 of this code.
420.4.2.9.6 The emergency generator(s) shall be air- or
self-contained liquid cooled and it and other essential electrical equipment
shall be installed in a protected area(s) designed and constructed to meet the
structural requirements of this code and debris impact requirements as
specified by Sections 1626.2 through 1626.4.
SECTION 423 STATE REQUIREMENTS FOR EDUCATIONAL FACILITIES
423.25 Public
shelter design criteria.
423.25.4.1 Missile
impact criteria.
The building
enclosure, including walls, roofs, glazed openings, louvers and doors, shall
not be perforated or penetrated by a flying object. For walls and roofs, the
missile criteria are as provided in ASTM E 1886 and ASTM E 1996, or SBC/SSTD
12.
423.25.5
Electrical and standby emergency power system.
The EHPA shall be
provided with a standby emergency electrical power system, per Chapter 27, NFPA
70 Articles 700 and 701, which shall have the capability of being connected to
a backup generator or other optional power source. Where economically feasible,
an equivalent photovoltaic system may be provided. The EHPA’s emergency systems
includes, but are not limited to: (1) an emergency lighting system, (2)
illuminated exit signs, (3) fire protection system(s), alarm (campus wide) and
sprinkler, and (4) minimum ventilation for health/safety purposes. The fire
alarm panel shall be located in the EHPA manager’s office. A remote annunciator
panel shall be located in or adjacent to the school administrator’s office.
When generators are installed, the facility housing the generator, permanent or
portable shall be an enclosed area designed to protect the generators from wind
and missile impact. Air intakes and exhausts shall be designed and installed to
meet the wind load and missile impact criteria. Generators hardened by the
manufacturer to withstand the area’s design wind and missile impact criteria
shall be exempt from the enclosed area criteria requirement.
SECTION 1626 HIGH-VELOCITY HURRICANE ZONES— IMPACT TESTS FOR
WIND-BORNE DEBRIS
1626.1 All parts
or systems of a building or structure envelope such as, but not limited to,
exterior walls, roof, outside doors, skylights, glazing and glass block shall
meet impact test criteria or be protected with an external protection device
that meets the impact test criteria. Test procedures to determine resistance to
wind-borne debris of wall cladding, outside doors, skylights, glazing, glass
block, shutters and any other external protection devices shall be performed in
accordance with this section.
Exception: The
following structures or portion of structures shall not be required to meet the
provisions of this Section:
a. Roof assemblies for screen rooms,
porches, canopies, etc.; attached to a building that do not breach the exterior
wall or building envelope and have no enclosed sides other than screen.
b. Soffits, soffit vents and ridge vents.
Size and location of such vents shall be detailed by the designer and shall not
compromise the integrity of the diaphragm boundary.
c. Vents in a garage with four or fewer
cars. Size and location of such vents shall be detailed by the designer and
shall not exceed the minimum required area by more than 25 percent.
d. Exterior wall or roof openings for
wall- or roof-mounted HVAC equipment.
e. Openings for roof-mounted personnel
access roof hatches.
f. Storage sheds
that are not designed for human habitation and that have a floor area of 720
square feet (67 m2) or less are not required to comply with the mandatory
windborne debris impact standards of this code.
g. Louvers as long as they properly
considered ASCE 7 in the design of the building.
h. Buildings and structures for marinas,
cabanas, swimming pools and greenhouses.
i. Exterior balconies or porches under
existing roofs or decks enclosed with screen or removable vinyl and acrylic
panels complying with Section 1622.1 or Section 1622.2 shall not be required to
be protected and openings in the wall separating the unit from the balcony or
porch shall not be required to be protected unless required by other provisions
of this code.
1626.4
Construction assemblies deemed to comply with Section 1626.
1. Exterior
concrete masonry walls of minimum nominal 8-inch (203 mm) thickness,
constructed in accordance with Chapter 21 (High-Velocity Hurricane Zones) of
this code.
2. Exterior
frame walls or gable ends constructed in accordance with Chapter 22 and Chapter
23 (High-Velocity Hurricane Zones) of this code, sheathed with a minimum
19/32-inch (15 mm) CD exposure 1 plywood and clad with
wire lath and stucco installed in accordance with Chapter 25 of this code.
3. Exterior
frame walls and roofs constructed in accordance with Chapter 22 (High-Velocity
Hurricane Zones) of this code sheathed with a minimum 24-gage rib deck type
material and clad with an approved wall finish.
4. Exterior
reinforced concrete elements constructed of solid normal weight concrete (no
voids), designed in accordance with Chapter 19 (High-Velocity Hurricane Zones)
of this code and having a minimum 2-in. (51 mm) thickness.
5. Roof systems
constructed in accordance with Chapter 22 or Chapter 23 (High-Velocity
Hurricane Zones) of this code, sheathed with a minimum 19/32-inch (15 mm) CD
exposure 1 plywood or minimum nominal 1-inch (25 mm) wood decking and surfaced
with an approved roof system installed in accordance with Chapter 15 of this
code.
All connectors
shall be specified by the building designer of record for all loads except
impact.
SECTION 312
UTILITY AND
MISCELLANEOUS GROUP U
312.1 General.
Buildings and
structures of an accessory character and miscellaneous structures not
classified in any specific occupancy shall be constructed, equipped and
maintained to conform to the requirements of this code commensurate with the
fire and life hazard incidental to their occupancy. Group U shall include, but
not be limited to, the following:
Agricultural
buildings
Aircraft hangars,
accessory to a one- or two-family residence (See Section 412.5)
Barns
Carports
Fences more than 6
feet (1829 mm) high
Grain silos,
accessory to a residential occupancy
Greenhouses
Livestock shelters
Private garages
Retaining walls
Sheds
Stables
Tanks
Towers
Staff Recommendation:
1.
A Client intends to install an
electrical generator set in an enclosure to provide emergency backup power to a
hospital in the event of a loss of utility power. There will be no other debris impact
protection aside from the generator enclosure.
According to FBC 419.4.2.9.6
“The emergency generator(s) shall be air or self-contained liquid cooled
and it and other essential electrical equipment shall be installed in a
protected area(s) designed and constructed to meet the structural requirements
of the code and debris impact requirements of Sections 1626.2 through 1626.4”.
a.
Is the generator enclosure required
to be tested and approved per Section 1626 of the 2010 Florida Building Code
and bear either appropriate Florida Product Approval numbers or Miami-Dade Notice
of Acceptance approval?
Answer: As per Section 419.4.2.9.6 of the
2010 FBC, Building “the Code”, the generator enclosure in question must be
constructed to meet the structural requirements of the Code and the debris
impact requirements of Sections 1626.2 through 1626.4 as applicable. Further, in order to demonstrate compliance
with the debris impact requirements of the Code, the generator enclosure or its
components must be either tested to TAS 201, 202, and 203 in accordance with
the requirements of Sections 1626.2 and 1626.3 as applicable or
designed/constructed to meet the deemed to comply
standards of Section 1626.4 as applicable. Product approval of the enclosure in
question as meeting the debris impact requirements of the Code is subject to the
review and discretion of the authority having jurisdiction.
2.
A Client intends to install an
electrical generator set in an enclosure to provide emergency backup power to a
Nursing Home in the event of a loss of utility power. There will be no other debris impact
protection aside from the generator enclosure.
According to FBC 420.4.2.9.6
“The emergency generator(s) shall be air or self-contained liquid cooled
and it and other essential electrical equipment shall be installed in a
protected area(s) designed and constructed to meet the structural requirements
of the code and debris impact requirements of Sections 1626.2 through 1626.4”.
a.
Is the generator enclosure required
to be tested and approved per Section 1626 of the 2010 Florida Building Code
and bear either appropriate Florida Product Approval numbers or Miami-Dade
Notice of Acceptance approval?
Answer: As per Section 420.4.2.9.6 of the
2010 FBC, Building “the Code”, the generator enclosure in question must be
constructed to meet the structural requirements of the Code and the debris
impact requirements of Sections 1626.2 through 1626.4 as applicable. Further, in order to demonstrate compliance
with the debris impact requirements of the Code, the generator enclosure or its
components must be either tested to TAS 201, 202, and 203 in accordance with
the requirements of Sections 1626.2 and 1626.3 as applicable or
designed/constructed to meet the deemed to comply
standards of Section 1626.4 as applicable. Product approval of the enclosure in
question as meeting the debris impact requirements of the Code is subject to
the review and discretion of the authority having jurisdiction.
3.
A Client intends to install an
electrical generator set in an enclosure to provide emergency backup power to
an Enhanced Hurricane Protection Area (EHPA) as part of an Educational Facility
Public Shelter in the event of a loss of utility power. There will be no other debris impact
protection aside from the generator enclosure.
According to FBC 423.25.5
“When generators are installed, the facility housing the generator,
permanent or portable, shall be an enclosed area designed to protect the
generators from wind and missile impact. Air intakes and exhausts shall be
designed and installed to meet the wind load and missile impact criteria.
Generators hardened by the manufacturer to withstand the area’s design wind and
missile impact criteria shall be exempt from the enclosed area criteria
requirement.”
a.
Is the generator enclosure required
to be tested and approved per Section 1626 of the 2010 Florida Building Code
and bear either appropriate Florida Product Approval numbers or Miami-Dade
Notice of Acceptance approval?
Answer: According to Section 423.25.5 of the 2010
Florida Building Code, Building (the Code); the generator enclosure or its
components is required to be designed to protect the generator from wind and
missile impact and thus the generator enclosure or its components must be
tested and approved as meeting the impact requirements of Section 423.25.4.1 of
the Code.
4.
A Client intends to install an
electrical generator set in an enclosure to a commercial facility located in a
High Velocity Hurricane Zone (HVHZ) to provide emergency backup power in the
event of a loss of utility power. The
generator Set and enclosure will be installed on the roof of the facility. There will be no other debris impact
protection aside from the generator enclosure.
According to FBC 1601.1
“The provisions of this chapter shall govern the structural design of
buildings, structures and portions thereof regulated by this code.
Exception: Buildings and structures located within the high-velocity
hurricane zone shall comply with the provisions of Sections 1615 through 1626,
and, as applicable in flood hazard areas, Section 1612.”
a.
Is the generator enclosure required
to be tested and approved per Section 1626 of the 2010 Florida Building Code
and bear either appropriate Florida Product Approval numbers or Miami-Dade
Notice of Acceptance approval?
Answer:
Option #1: No. The enclosure in question
is storage shed and according to Section 1626.1, Exception f, of the Code, the
enclosure in question is not required to meet the impact criteria of Section
1626 of the Code.
Option #2: Yes. The
enclosure in question is a building which must be constructed to meet the
structural requirements of the Code and the debris impact requirements of
Sections 1626.2 through 1626.4 as applicable.
Further, in order to demonstrate compliance with the debris impact
requirements of the Code, the generator enclosure or its components must be
either tested to TAS 201, 202, and 203 in accordance with the requirements of
Sections 1626.2 and 1626.3 as applicable or designed/constructed to meet the
deemed to comply standards of Section 1626.4 as
applicable. Product approval of the enclosure in question as meeting the debris
impact requirements of the Code is subject to the review and discretion of the
authority having jurisdiction.
5.
A Client intends to install an
electrical generator set in an enclosure to a commercial facility located in a
High Velocity Hurricane Zone (HVHZ) to provide emergency backup power in the
event of a loss of utility power. The
generator Set and enclosure will be installed on the ground floor of the
facility. There will be no other debris
impact protection aside from the generator enclosure.
According to FBC 1601.1
“The provisions of this chapter shall govern the structural design of
buildings, structures and portions thereof regulated by this code.
Exception: Buildings and structures located within the high-velocity
hurricane zone shall comply with the provisions of Sections 1615 through 1626,
and, as applicable in flood hazard areas, Section 1612.”
a.
Is the generator enclosure required
to be tested and approved per Section 1626 of the 2010 Florida Building Code
and bear either appropriate Florida Product Approval numbers or Miami-Dade
Notice of Acceptance approval?
Answer:
Option #1: No. The enclosure in
question is storage shed and according to Section 1626.1, Exception f, of the
Code, the enclosure in question is not required to meet the impact criteria of
Section 1626 of the Code.
Option #2: Yes. The
enclosure in question is a building which must be constructed to meet the
structural requirements of the Code and the debris impact requirements of
Sections 1626.2 through 1626.4 as applicable.
Further, in order to demonstrate compliance with the debris impact
requirements of the Code, the generator enclosure or its components must be either
tested to TAS 201, 202, and 203 in accordance with the requirements of Sections
1626.2 and 1626.3 as applicable or designed/constructed to meet the deemed to comply standards of Section 1626.4 as applicable. Product
approval of the enclosure in question as meeting the debris impact requirements
of the Code is subject to the review and discretion of the authority having
jurisdiction.