Staff Analysis for Declaratory Statement Request DS 2015-154

Issue: Petitioner seeks a Declaratory Statement on an interpretation of Section C403.2.6 energy recovery ventilation systems. Chapter 4 of the 5th Edition (2014) Florida Building Code, Energy Conservation, Section C403.2.6. Specifically, requesting clarification of Exception C403.2.6 (7) and a determination on a type of product as it relates to this exception.

 

Background:

The Petitioner, David A. John, Stan Weaver & Company, seeks a determination on a type of product as it relates to Exception 7 of Section C403.2.6 of the Florida Building Code 2014, Energy Conservation. Stan Weaver & Company is a manufacturer’s representative of air distribution products for central Florida. One of the manufacturers they represent is Heat Pipe Technology (HPT) who manufactures heat pipes that are used in air handler units as an energy savings device.

 

The petitioner feels that having a heat pipe included as an exception in C403.2.6 Energy recovery ventilation systems is a major point of emphasis with Florida engineers and owners. It allows engineers to design HVAC systems, include a heat pipe, and not have to provide an additional energy recovery system. The petitioner feels it will save the building owner the expense of two heat recovery systems. Below are the relevant circumstances.

 

A selection and payback analysis for a current design under consideration

·             100% OA unit with constant 20,000 CFM

·             52 F off the cooling coil

·             no more than 65 F supplied after reheat

·             supplemental reheat is via hot water

 

Assumptions:

·             Chiller has efficiency of 20 EER (or 0.600 kW/ton)

·             utility rate is $0.10/kWh

·             hot water costs $1/therm (therm = 100,000 Btus)

·             AHU fan is 70% efficient and motor is 90% efficient

·             Temperatures and hours based on Tampa bin data for one year

·             AHU operates 24/7/365

 

At the first/uppermost bin (where OA is between 90 F and 95 F)…

 

Cooling Savings = Tons removed X Chiller’s kW/ton X Tampa’s cooling hours X Utility Rate

= 22 tons x 0.600 kW/ton x 157 Hours x $0.10/kWh = $209

Heating Savings = Free Reheat X Utility Rate Free Reheat = 265,746 BTUH = 2.66 Therms/hour = 2.66 Therms/hour X $1/Therm X 157 Hours = $417

Fan Penalty = (Airflow X Total Static Pressure X Utility Rate X Hours) / (Constant X Fan & Motor Efficiencies)

= (20,000 CFM X 0.37 X $0.10/kWh X 157 hours) / (8,522 X 0.7 X 0.9) = $22

NET Savings (for 90F-95F bin) = $209 + $417 - $22 = $604

 

Then calculate for each bin and sum to get NET Annual Savings = $16,965*

* See attached Bin Analysis for breakdown.

 

If this standard 2-row DHP is budgeted for $25,000 and annual savings are $16,965

Payback is less than a year and a half

 

 

Question: If an air handling unit is provided with a wrap-around heat pipe (for

dehumidification), is it acceptable to not provide an Energy Recovery Ventilation System per paragraph C403.2.6.7?

 

Petitioner respectfully believes the answer to the question outlined above is yes, if a wrap-around heat pipe coil is used, it is acceptable to not provide an Energy Recovery Ventilation System per paragraph C403.2. A wrap-around heat pipe is commonly viewed as a dehumidification device that employs energy recovery in series with the cooling coil.

 

-----

 

Reference Material

 

 

Florida Building Code 5th Edition (2014), Energy Conservation

Chapter 4

C403.2.6 Energy recovery ventilation systems. Where the supply airflow rate of a fan system exceeds the values specified in Table C403.2.6, the system shall include an energy recovery system. The energy recovery system shall have the capability to provide a change in the enthalpy of the outdoor air supply of not less than 50 percent of the difference between the outdoor air and return air enthalpies, at design conditions. Where an air economizer is required, the energy recovery system shall include a bypass or controls which permit operation of the economizer as required by Section C403.4

Exception: An energy recovery ventilation system shall not be required in any of the following conditions:

1. Where energy recovery systems are prohibited by the Florida Building Code, Mechanical.

2. Laboratory fume hood systems that include at least one of the following features:

2.1. Variable-air-volume hood exhaust and room supply systems capable of reducing exhaust and makeup air volume to 50 percent or less of design values.

2.2. Direct makeup (auxiliary) air supply equal to at least 75 percent of the exhaust rate, heated no warmer than 2°F (1.1°C) above room set point, cooled to no cooler than 3°F (1.7°C) below room set point, no humidification added, and no simultaneous heating and cooling used for dehumidification control.

3. Systems serving spaces that are heated to less than 60°F (15.5°C) and are not cooled.

4. Where more than 60 percent of the outdoor heating energy is provided from site-recovered or site solar energy.

5. Heating energy recovery in Climate Zones 1 and 2.

6. Cooling energy recovery in Climate Zones 3C, 4C, 5B, 5C, 6B, 7 and 8.

7. Systems requiring dehumidification that employ energy recovery in series with the cooling coil.

8. Where the largest source of air exhausted at a single location at the building exterior is less than 75 percent of the design outdoor air flow rate.

9. Systems expected to operate less than 20 hours per week at the outdoor air percentage covered by Table C403.2.6.

 

 

TABLE C403.2.6 ENERGY RECOVERY REQUIREMENT

CLIMATE ZONE

PERCENT (%) OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE

≥ 30% and < 40%

≥ 40% and < 50%

≥ 50% and < 60%

≥ 60% and < 70%

≥ 70% and < 80%

≥ 80%

DESIGN SUPPLY FAN AIRFLOW RATE (cfm)

3B, 3C, 4B, 4C, 5B

NR

NR

NR

NR

≥ 5000

≥ 5000

1B, 2B, 5C

NR

NR

≥ 26000

≥ 12000

≥ 5000

≥ 4000

6B

≥ 11000

≥ 5500

≥ 4500

≥ 3500

≥ 2500

≥ 1500

1A, 2A, 3A, 4A, 5A, 6A

≥ 5500

≥ 4500

≥ 3500

≥ 2000

≥ 1000

> 0

7, 8

≥ 2500

≥ 1000

> 0

> 0

> 0

> 0

 

NR = not required

 

 

ASHRAE 90.1-2010 User’s Manual.

Energy Recovery (6.5.6)

Exhaust Air Energy Recovery (6.5.6.1)

 

The requirements for exhaust air energy recovery have been significantly increased in stringency in the 2010 Standard. The standard requires exhaust air energy recovery on individual fan systems that meet or exceed the criteria in Table 6-E (Table 6.5.6.1 of the Standard). The requirements are based on climate zone, percent outside air at design condition and the design supply flow airflow rate.

 

Equipment used to meet this requirement includes plate heat exchangers (plastic and metal), heat pipes, run-around coils and enthalpy wheels, but which must also meet the recovery effectiveness discussed below.

 

The standard defines exhaust air energy recovery as the process of exchanging heat (sensible and/or latent) between the exhaust and outdoor airstreams. This reduces energy usage in the following manner:

 

-          During periods of heating, the exhaust air can preheat the cool outdoor air through sensible (dry) exchange.

-          During periods of cooling, the exhaust air can precool the hot outdoor air through sensible (dry) exchange.

-          During periods of cooling, dry exhaust air can be used to dehumidify moist outdoor are through latent exchange.

-          During periods of heating, exhaust air can be used to humidify dry outdoor air through latent exchange.

 

 

Exceptions to 6.5.6.1

There are a number of exceptions to the requirement for exhaust air energy recovery systems:

 

I)       Systems requiring dehumidification that employ energy recover in series with the cooling coil. This exception recognizes the energy savings inherent in series energy dehumidification systems.

 

 

INTERPRETATION IC 90.1-2004-3 OF ANSI/ASHRAE/IESNA STANDARD 90.1-2004

Energy Standard for Buildings Except Low-Rise Residential Buildings

©2006

 

Interpretation: Exception (i) to Section 6.5.6.1 allows the use of dehumidification devices for ventilation air streams, provided that the system requires dehumidification, and provided that the system uses energy recovery in series with the cooling coil.

A system which uses a desiccant-assisted cooling coil is also allowed under exception (i), provided that all of the energy it uses for desiccant reactivation is recovered from within that same system.

 

Question: Is this interpretation correct?

 

Answer:

Yes, your interpretation is correct and the desiccant wheel with regeneration obtained from site recovered heat which in your design is from the refrigeration condenser will meet the requirements of exception 6.5.6.1 (i). It should also be noted that there are other means for recovering heat like the heat pipe system shown in your diagram as well as condenser heat rejection coils placed downstream from a conventional evaporator coil.

 

 

 

 

 

 

 

 

 

Staff Analysis

 

Question:      If an air handling unit is provided with a wrap-around heat pipe (for

dehumidification), is it acceptable to not provide an Energy Recovery Ventilation System per paragraph C403.2.6.7?

 

Answer:

 

Option #1/Petitioner:

 

Petitioner respectfully believes the answer to the question outlined above is yes, if a wrap-around heat pipe coil is used, it is acceptable to not provide an Energy Recovery Ventilation System per paragraph C403.2. A wrap-around heat pipe is commonly viewed as a dehumidification device that employs energy recovery in series with the cooling coil.

 

Option #2/Staff:

 

No, the wrap-around heat pipe in question is not configured to provide heat exchange (sensible and/or latent) between the exhaust and outdoor airstreams and therefore, it does not fall within the technical scope of Section C403.2.6, Exception 7 of the 5th Edition (2014) FBC, Energy Conservation.