ROOFING
TECHNICAL ADVISORY
Meeting
Minutes
December 2, 2015
1:30 P.M.
TAC
MEMBERS |
TAC MEMBERS Present: CHAIRMAN;
BRIAN SWOPE, BOB BOYER, WARNER CHANG FOR REMINGTON BROWN, JIMMY BUCKNER,
BILLY CONE, CHUCK GOLDSMITH, LORRAINE ROSS, KAREN WARSECK, MARK ZEHNAL |
Ø Objective: To
consider, discuss, and provide recommendation for consideration by the Commission
regarding DS 2015-109 and DS 2015-135 by Robin Davies of Braken
Engineering |
MEETING
Minutes |
|
OBJECTIVE |
REVIEW OF OBJECTIVES WILL INCLUDE THE
FOLLOWING: Description of issue, discussion by Commission,
public comment, Commission action. |
1) |
Welcome
and Opening Remarks |
2) |
Roll
Call |
3) |
Reviewed
and Approved the Meeting Agenda |
4) |
Reviewed
and approved Minutes of
October 06, 2015 Roofing TAC Meeting |
5) |
TAC considered, discussed, and provided
recommendation for consideration by the Commission regarding DS
2015-109 by Robin Davies of Braken Engineering After
some lengthy discussion, the TAC voted 6-3 in agreement with the staff’s
answer. TAC ACTIONS: Question: Does
the repair of roof coverings performed in accordance with Chapter 6 of the
5th Edition (2014) Florida Building Code, Existing Building need to comply
with the requirements of Section 708 Reroofing? Answer: No, as per Section 606.2.1 of the 5th Edition
(2014) FBC, Existing Building “the Code), the project in question is
permitted to be restored to its predamage condition
without meeting the requirements of Section 708.1.1 of the Code. Building materials to be used in the
restoration of the project in question must be in accordance with Section
602.2 of Code. |
6) |
TAC considered, discussed, and provided
recommendation for consideration by the Commission regarding DS 2015-135 by
Robin Davies of Braken Engineering After
some lengthy discussion, the TAC voted 6-3 in agreement with the staff’s
answer. TAC ACTIONS: Question: Does
the repair of roof coverings performed in accordance with Chapter 6 of the
5th Edition (2014) Florida Building Code, Existing Building need to comply
with the requirements of Section 708 Reroofing? Answer: No,
as per Section 606.2.1 of the 5th Edition (2014) FBC, Existing Building “the
Code), the project in question is permitted to be restored to its predamage condition without meeting the requirements of
Section 708.1.1 of the Code. Building
materials to be used in the restoration of the project in question must be in
accordance with Section 602.2 of Code. |
7) |
General Public Comment- No Public Comment |
8) |
General
Member Comment- No Member comment |
9) |
Adjournment. |
STAFF CONTACTS: Robert Benbow, Robert.benbow@myfloridalicense.com, (850) 717-1828;
Mo Madani, mo.madani@myfloridalicense.com, (850) 717-1825.