FLORIDA
BUILDING COMMISSION
STRUCTURAL
TAC
CONCURRENT
WITH
SPECIAL OCCUPANCY TAC
Minutes
WEBINAR / TELECONFERENCE
Thursday, January 24, 2013,
10:00am – 11:35am
MEETING OBJECTIVES |
||
Ø To review and provide
recommendations on Declaratory Statements and other business on behalf of the
Commission. |
||
MEMBERS |
||
ØMembers present: James Schock – Chair, CW Macomber, Steve Strawn,
Craig Parrino, Bill Dumbaugh
alternate for Daniel Lavrich, Do Kim, Jack
Glenn, Jaime Gascon, Warner Chang, Harry
“Rusty” Carroll |
||
10:00
AM |
A) |
Called to Order a quorum was
achieved with 10 members present. The
meeting was held concurrently with the Special Occupancy TAC. The Special Occupancy TAC achieved a quorum
too. The Agenda and minutes were
both approved as submitted. |
|
B) |
Reviewed and provide the
following recommendations on Declaratory Statements and other business on
behalf of the Commission. 1.
DS 2012-081 – By Joseph Scofield of Advanced Manufacturing & Power Systems
Inc. 1. A Client intends to install an electrical
generator set in an enclosure to provide emergency backup power to a hospital
in the event of a loss of utility power. There will be no other
debris impact protection aside from the generator enclosure. According to FBC 419.4.2.9.6 “The
emergency generator(s) shall be air or self-contained liquid cooled and it
and other essential electrical equipment shall be installed in a protected
area(s) designed and constructed to meet the structural requirements of the
code and debris impact requirements of Sections 1626.2 through 1626.4”. a. Is the generator enclosure required to be
tested and approved per Section 1626 of the 2010 Florida Building Code and
bear either appropriate Florida Product Approval numbers or Miami-Dade Notice
of Acceptance approval? Answer: As per Section
419.4.2.9.6 of the 2010 FBC, Building “the Code”, the generator enclosure in
question must be constructed to meet the structural requirements of the Code
and the debris impact requirements of Sections 1626.2 through 1626.4 as
applicable. Further, in order to demonstrate compliance with the
debris impact requirements of the Code, the generator enclosure or its
components must be either tested to TAS 201, 202, and 203 in accordance with
the requirements of Sections 1626.2 and 1626.3 as applicable or
designed/constructed to meet the deemed to comply standards
of Section 1626.4 as applicable. Product approval of the enclosure in question
as meeting the debris impact requirements of the Code is subject to the
review and discretion of the authority having jurisdiction. 2. A Client intends to install an electrical
generator set in an enclosure to provide emergency backup power to a Nursing
Home in the event of a loss of utility power. There will be no
other debris impact protection aside from the generator enclosure. According to FBC 420.4.2.9.6 “The
emergency generator(s) shall be air or self-contained liquid cooled and it
and other essential electrical equipment shall be installed in a protected
area(s) designed and constructed to meet the structural requirements of the
code and debris impact requirements of Sections 1626.2 through 1626.4”. a. Is the generator enclosure required to be
tested and approved per Section 1626 of the 2010 Florida Building Code and
bear either appropriate Florida Product Approval numbers or Miami-Dade Notice
of Acceptance approval? Answer: As per Section
420.4.2.9.6 of the 2010 FBC, Building “the Code”, the generator enclosure in
question must be constructed to meet the structural requirements of the Code
and the debris impact requirements of Sections 1626.2 through 1626.4 as
applicable. Further, in order to demonstrate compliance with the
debris impact requirements of the Code, the generator enclosure or its
components must be either tested to TAS 201, 202, and 203 in accordance with
the requirements of Sections 1626.2 and 1626.3 as applicable or
designed/constructed to meet the deemed to comply standards
of Section 1626.4 as applicable. Product approval of the enclosure in
question as meeting the debris impact requirements of the Code is subject to
the review and discretion of the authority having jurisdiction. 3. A Client intends to install an electrical
generator set in an enclosure to provide emergency backup power to an
Enhanced Hurricane Protection Area (EHPA) as part of an Educational Facility
Public Shelter in the event of a loss of utility power. There will
be no other debris impact protection aside from the generator
enclosure. According to FBC 423.25.5 “When
generators are installed, the facility housing the generator, permanent or
portable, shall be an enclosed area designed to protect the generators from
wind and missile impact. Air intakes and exhausts shall be designed and
installed to meet the wind load and missile impact criteria. Generators
hardened by the manufacturer to withstand the area’s design wind and missile
impact criteria shall be exempt from the enclosed area criteria requirement.” a. Is the generator enclosure required to be
tested and approved per Section 1626 of the 2010 Florida Building Code and
bear either appropriate Florida Product Approval numbers or Miami-Dade Notice
of Acceptance approval? Answer: According to Section 423.25.5 of the
2010 Florida Building Code, Building (the Code); the generator enclosure or
its components is required to be designed to protect the generator from wind
and missile impact and thus the generator enclosure or its components must be
tested and approved as meeting the impact requirements of Section 423.25.4.1
of the Code. 4. A Client intends to install an electrical
generator set in an enclosure to a commercial facility located in a High
Velocity Hurricane Zone (HVHZ) to provide emergency backup power in the event
of a loss of utility power. The generator Set and enclosure will
be installed on the roof of the facility. There will be no other
debris impact protection aside from the generator enclosure. According to FBC 1601.1 “The provisions
of this chapter shall govern the structural design of buildings, structures
and portions thereof regulated by this code. a. Is the generator enclosure required to be
tested and approved per Section 1626 of the 2010 Florida Building Code and
bear either appropriate Florida Product Approval numbers or Miami-Dade Notice
of Acceptance approval? Answer: Yes.
The enclosure in question is part of a building which must be constructed to
meet the structural requirements of the Code and the debris impact
requirements of Sections 1626.2 through 1626.4 as applicable. Further,
in order to demonstrate compliance with the debris impact requirements of the
Code, the generator enclosure or its components must be either tested to TAS
201, 202, and 203 in accordance with the requirements of Sections 1626.2 and
1626.3 as applicable or designed/constructed to meet the deemed to comply standards of Section 1626.4 as applicable.
Product approval of the enclosure in question as meeting the debris impact
requirements of the Code is subject to the review and discretion of the
authority having jurisdiction. 5. A Client intends to install an electrical
generator set in an enclosure to a commercial facility located in a High
Velocity Hurricane Zone (HVHZ) to provide emergency backup power in the event
of a loss of utility power. The generator Set and enclosure will
be installed on the ground floor of the facility. There will be no
other debris impact protection aside from the generator enclosure. According to FBC 1601.1 “The provisions
of this chapter shall govern the structural design of buildings, structures
and portions thereof regulated by this code. a. Is the generator enclosure required to be
tested and approved per Section 1626 of the 2010 Florida Building Code and
bear either appropriate Florida Product Approval numbers or Miami-Dade Notice
of Acceptance approval? Answer: Yes.
The enclosure in question is a building which must be constructed to meet the
structural requirements of the Code and the debris impact requirements of
Sections 1626.2 through 1626.4 as applicable. Further, in order to
demonstrate compliance with the debris impact requirements of the Code, the
generator enclosure or its components must be either tested to TAS 201, 202,
and 203 in accordance with the requirements of Sections 1626.2 and 1626.3 as
applicable or designed/constructed to meet the deemed to comply standards of Section 1626.4 as applicable.
Product approval of the enclosure in question as meeting the debris impact
requirements of the Code is subject to the review and discretion of the
authority having jurisdiction.
Question 1: Does the
term “protection of openings” mean the same as the term “opening protection”,
as found in the text of the referenced section, and specific to “protection
from windborne debris”? Answer: Yes, the term “protection of openings” is analogous to the term
“opening protection” as referenced in Section 1609.1.2 of the 2010 Florida
Building Code, Building and specific to “protection from windborne debris.” Question 2: Is the
non-glazed door required to comply with Section 1609.1.2? Answer: No, Section 1609.1.2 is specific to glazed products. Question 3: If the
non-glazed door is not required to comply with Section 1609.1.2, but it
complies with the wind load requirements of the code, would the door also
comply with the code as “opening protection”? Answer: A non-glazed door is not required to be
protected in accordance with Section 1609.1.2 in a
non-HVHZ zone Question 4: Would the
state-approved, glazed garage door rated for non-HVHZ impact resistance be
acceptable for the job (which is outside the HVHZ) without an NOA? Answer: Yes, if used as per the limits of use of the Product
Approval.
RE: Project #1) In the scope of the work plan review for
permitting the process of stabilizing an interior concrete slab, on grade,
for a 2000 sq. ft. existing dwelling unit that was built in 2001, the
application consists of injecting pressurized structural polyurethane resin
through the slab, on grade, by using core drilled holes in which the
polyurethane resin expands to lift/stabilize the concrete slab. This process
has no control of the path of flow for the polyurethane resin in which direct
contact with the slab on grade concrete is possible. Question –
Does injecting this pressurized structural polyurethane resin for
soil stabilization thru the slab on grade for existing dwellings, with
possible direct contact with the concrete slab on grade, constitute a
violation of 2010 FBC-R Section 318.5? Answer: No. The application of Section R318.5 of the
FBC, Residential is limited in scope to new construction. RE: Project
#2) In the
scope of the work plan review for permitting the process of stabilizing an
exterior foundation/footer for a 1450 sq. ft. existing dwelling unit that was
built in 1985, the application consists of injecting structural polyurethane
resin in the ground outside of the existing dwelling unit to provide
structural support for the foundation /footer. This process has no
control of the path of flow for the polyurethane resin in which direct
contact with the foundation/footer is possible. Question - Does injecting this structural polyurethane
resin into the ground outside the existing dwelling unit with possible direct
contact with the foundation/footer constitute a violation of 2010FBC-R
318.5? Answer: No. The provisions of Section R318.5 of the FBC,
Residential do not apply to the projects in question. 4.
DS 2012-097 – By Robert W. Moody,
Jr. of Uretek Holdings, Inc. Question No. 1 Is the installation of
a rigid structural geotechnical polymer into the ground as a method of soil stabilization
for an existing building prohibited by the 2010 Florida Building Code, Residential, Chapter
3, Code Section R318.5? Answer: No. The provisions of Section R318.5 of
the FBC, Residential do not apply to the projects in question. Question No. 2 Are soil stabilization
techniques as discussed herein regulated by 2010 Florida Building Code – Residential and/or Existing Building? Answer: The applications of the soil stabilization techniques in
question fall within the technical scope of the 2010 Florida Building Code,
Existing Building and not the Florida Building Code, Residential. |
|
D) |
No Public Comment |
|
E) |
Adjourned at 11:35 am |
STAFF CONTACTS: Joe Bigelow, joe.bigelow@dbpr.state.fl.us, (850) 922-0359; Mo Madani, Manager
Note: This document is available to any person requiring materials in
alternate format upon request. Contact the Department of Business and
Professional Regulation, 2555 Shumard Oak Boulevard,
Tallahassee, Florida 32399-2100 or call 850-487-1824.