ENERGY TECHNICAL ADVISORY COMMITTEE (TAC)
DS 2016-033 by Alfonso Fernandez-Fraga, P.E. of Initial Engineering P.A.
Question: Does
the Florida Building Code- Energy Conservation 2014, Section C405.7.1 require
conformance with the requirements of ASHRAE 90.1, 8.4.2, Automatic Receptacle
Control?
Answer: Yes, as per Section
C405.7.1 of the 5th Edition (2014) Florida Building Code, Energy
Conservation, power distribution systems of the buildings in questions are
subject to the requirements of ASHRAE 90.1 – 2010 including the “Mandatory
Provisions” of Section 8.4 of the said standard.
PLUMBING TECHNICAL ADVISORY COMMITTEE (TAC)
DS
2016-032 by David Gilson, Building Development Inspector IV, of City of Tarpon
Springs Florida
Question
#1: Is an isolation valve required to be installed on a new gas piping
system for each intended appliance prior to final inspection and service start
up?
Answer: Yes,
as per section G2420.5 of the 5th Edition (2014) FBC, Residential, a
shutoff valve/isolation valve would be required for the level of work in
question (I.e., clothes dryer).
Question #2: Is identification (labeling) required for a
future stub out when multiple pressures
exist on the same piping system, and the stub out for the future
appliance is 2lbs. or more?
Answer:
Yes, per FBC residential G2412.7 piping meter
identification a system with more than one working pressure effectively equates
to more than one meter.
.