LEGAL REPORT
FIRE TECHNICAL ADVISORY COMMITTEE (TAC)
DS 2019-014 by
Allen Finfrock of Finfrock DMC
TAC ACTION:
Question: Does the code classify an access panel as a "smoke and
draft control door" which would require it to be rated per UL 1784?
Answer: The answer to question is “Yes.” As per section
716.5.3.1, Smoke and draft control, the access panel in question must meet the
requirements for a smoke and draft control door assembly tested in accordance
with UL 1784.
PRODUCT APPROVAL PROGRAM OVERSIGHT
COMMITTEE (PA POC)
DS 2019-021 by Jason
Malouf of Window and Door Design Center
TAC ACTION:
Since the Petitioner’s
questions pertain to the past conduct of other individuals, their petition
should be declined, since a declaratory statement is not the appropriate
mechanism through which to address their concerns.
ELECTRICAL TECHNICAL ADVISORY COMMITTEE
(TAC)
DS 2019-022 by
Robert Messing of Excel Electrical Group, LLC
TAC ACTION:
Petitioner’s question
pertains to a local amendment, rather than a provision of the statewide Florida
Building Code. The Building Commission is thus without authority to issue a
declaratory statement on the issue, and the petition should be declined.