DEC
REQUEST DS-2012-044 STAFF ANALYSIS
ISSUE: DS-2012-044.
Petitioner seeks a Declaratory Statement on ventilation requirements for Level
2 Alterations of the 2010 Florida Building Code, Existing Building
Petitioner in DS-2012-044 seeks
clarification of the following questions:
Question 1: Is it the intent of the 2010Florida
Building Code – Existing Building, Section 709.1 to require all Level 2
Alterations to conform with the current Code requirements with respect to
ventilation?
Situation:
Alfonso Fernandez-Fraga, P.E.
representing Initial Engineers, P.A., seeks clarification of code regarding
ventilation requirements for Level 2 Alterations as indicated in the 2010 Florida Building Code – Existing Building
According to the
Petitioner, the project in question is a future project that will fall within
the technical scope of Level 2 renovation of the 2010 FBC, Existing
Building. The proposed project is office
occupancy where most of the interior partitions will be rearranged. Therefore,
there is no occupancy change, but the renovation is clearly much more than
repair. The building is, of course,
existing, and was built in the mid-1980.
At the time it was constructed, the industry standard ventilation rates
that were used were on the order of 7.5 CFM per person. Today’s codes are more
complicated in the methodology used to arrive at required ventilation rates,
but for most part, today’s required ventilation rates are significantly greater
than 7.5 CFM per person.
The Petitioner has indicated that he believes two
(2) unintended consequences exist that are a result of the current Code
verbiage of Section 709.1:
In summary, the Petitioner is
indicating that the requirements of Existing
Building Section 709.1 may lead to incidental work required that may
substantially impact the original scope of work, and may extend beyond the defined
work area of the project.
Applicable
Codes:
Background:
Florida
Building Code – Existing Building Section 709.1 Reconfigured or converted
spaces. All
reconfigured spaces intended for occupancy and all spaces converted to
habitable or occupiable space in any work area shall be provided with
natural or mechanical ventilation or exhaust in accordance with the Florida
Building Code, Mechanical
Florida
Building Code – Existing Building Section 101.5 Compliance methods.
The repair, alteration,
change of occupancy, addition or relocation of all existing
buildings shall
comply with one of the methods
listed in Sections 101.5.1 through 101.5.3 as selected by the applicant.
Application of a method shall be the sole basis for assessing the compliance of
work performed under a single
permit unless otherwise approved by the code official. Sections 101.5.1
through 101.5.3 shall not be applied in combination with each other.
Exception:
Subject
to the approval of the code official, alterations complying with
the laws in existence at the time the building or the affected portion
of the building was built shall be considered in compliance with the
provisions of this code unless the building is undergoing more than a
limited structural alteration as defined in Section 807.4.3. New
structural members added as part of the alteration shall comply
with the Florida Building Code, Building. Alterations of existing
buildings in flood hazard areas shall comply with Section 601.3.
Staff Recommendations: Based on the above
facts and circumstances as provided in the petition, staff provides the
following recommendations as answers to proponent’s questions:
Question 1:
To the question” Is it the intent
of the 2010 Florida Building Code – Existing Building, Section 709.1 to require
all Level 2 Alterations to conform with the current Code requirements with
respect to ventilation? ”, the answer is yes. According to section 709.1 of the
FBC, Existing Building, all reconfigured spaces of the project in question that
are intended for occupancy must be provided with natural or mechanical
ventilation or exhaust in accordance with the 2010 Florida Building Code,
Mechanical.