Comments on the 2013 Update to the
Florida Building Code to considered by the
Energy TAC
Meeting
Date: August 6, 2013
Tracking ID |
Florida
Building Code, Energy Conservation Proposed
Changes |
Comments |
TAC Action |
|
EN 1 |
Section 553.912, Florida Statutes 553.912 Air conditioners.— All air conditioners
that are sold or installed in the state must Section R101.4.7 is changed by HB 269 (passed
by the 2013 Florida Legislature) to read as follows: R101.4.7 Building
systems and components. Thermal efficiency standards are set for the following building
systems and components where new products are installed or replaced in existing
buildings, and for which a permit must be obtained. New products shall meet
the minimum efficiencies allowed by this code for the following systems
and components:
Heating, ventilating or air conditioning systems;
Service water or pool heating systems;
Lighting systems. Replacement Fenestration.
R101.4.7.1 Existing equipment efficiencies. Existing
cooling and heating equipment in residential applications need not meet the
minimum equipment efficiencies |
Glitch – (e) Changes to or inconsistencies with federal or
state law. HB 269. |
|
|
EN2 |
Section R103.1.1
is changed by HB 269 (passed by the 2013 Florida Legislature) to read
as shown: R103.1.1 Compliance
certification. R103.1.1.1
Code compliance demonstration.
R103.1.1.1.1
Residential.
No license or registration is required to prepare the code compliance form
for single-family residential dwellings, duplexes and townhouses. R103.1.1.1.2
Commercial and multiple-family residential. Completion of procedures
demonstrating compliance with this code for multiple-family residential building
shall be in accordance with the provisions of Section 481.229, Florida
Statutes, or Section 471.003, Florida Statutes. Exception:
Where HVAC
systems are nominal 15 tons per system or
smaller, R103.1.1.2
Code compliance certification. The
building’s owner, the owner’s architect, or other authorized agent legally
designated by the owner shall certify that the building is in compliance with
the code, as per Section 553.907, Florida Statutes, prior to receiving
the permit to begin construction or renovation. |
Glitch – (e) Changes to or inconsistencies with federal or
state law. HB 269. |
|
|
EN3 |
Section
R403.2.2 is changed by HB 269 (passed by the 2013 Florida Legislature) to
read as shown: R403.2.2 Sealing (Mandatory).
All ducts, air
handlers, and filter boxes and building cavities that form the primary air
containment passageways for air distribution systems shall be considered
ducts or plenum chambers, shall be constructed and sealed in accordance with
Section C403.2.7.2 of the Commercial Provisions of this code and shall be
shown to meet duct tightness criteria below. Duct
tightness shall be verified by testing to Section 803 of the RESNET Standards
by either
an 1.
Postconstruction test: Total leakage shall be less than or equal to 4 cfm
(113.3 L/min) per 100 square feet (9.29 m2) of conditioned floor
area when tested at a pressure differential of 0.1 inches w.g. (25 Pa) across
the entire system, including the manufacturer’s air handler enclosure. All
register boots shall be taped or otherwise sealed during the test. 2.
Rough-in test: Total leakage shall be less than or equal to 4 cfm (113.3
L/min) per 100 square feet (9.29 m2) of conditioned floor area
when tested at a pressure differential of 0.1 inches w.g. (25 Pa) across the
system, including the manufacturer’s air handler enclosure. All registers
shall be taped or otherwise sealed during the test. If the air handler is not
installed at the time of the test, total leakage shall be less than or equal
to 3 cfm (85 L/min) per 100 square feet (9.29 m2) of conditioned
floor area. Exceptions: 1.
The total leakage test is not required for ducts and air handlers located
entirely within the building thermal envelope. 2.
Duct testing is not mandatory for buildings complying by Section 405 of this
code |
|
|
|
EN4 |
Florida Statutes 553.907 Compliance.—Each local enforcement agency shall report to
the department any information concerning compliance certifications and
amendments at such intervals as the department designates by rule adopted in
accordance with chapter 120. SECTION
R110 REPORTING
|
General comment – Cost to the state – 30K to archive and analyze the
data. There has been no demand or use
for the data that would justify continuation of this provision. Reporting
requirements for commercial compliance has been removed from the code. Glitch – Conflicts within the updated code. |
|
|
EN5 |
Section C103.1.1 is changed by HB 269 (passed by the 2013
Florida Legislature) to read as follows: C103.1.1
Compliance certification. C103.1.1.1 Code compliance demonstration. C103.1.1.1.1 Residential. See Florida Building
Code, Energy Conservation: Residential Provisions. C103.1.1.1.2 Commercial and multiple-family residential. Completion of
procedures demonstrating compliance with this code for multiple-family
residential building shall be in accordance with the provisions of Section
481.229, Florida Statutes, or Section 471.003, Florida Statutes. Exception: Where HVAC systems are ≤ 15 tons per system, air
conditioning or mechanical contractors licensed in accordance with Chapter
489, Florida Statutes, or Design professionals responsible under Florida law for the
design of lighting, electrical, mechanical, and plumbing systems and the
building shell, shall certify compliance of those building systems with the
code by signing and providing their professional registration number on the
energy code form provided as part of the plans and specifications to the
building department. C103.1.1.2 Code compliance certification. The building’s
owner, the owner’s architect, or other authorized agent legally designated by
the owner shall certify that the building is in compliance with the code, as
per Section 553.907, Florida Statutes, prior to receiving the permit
to begin construction or renovation. |
Glitch – (e) Changes to or inconsistencies with federal or
state law. HB 269. |
|
|
EN6 |
APPENDIX A (both
Commercial and Residential code provisions) is changed by SB 1514 and HB 209 (passed by the 2013 Florida Legislature) to
read (in part) as shown: BREVARD COUNTY 151000
II
EASTERN FLORIDA STATE LAKE COUNTY 451000 III
LAKE SUMTER STATE |
Glitch – (e) Changes to or inconsistencies with federal or
state law. HB 1514 and HB 209. |
|