Comments on the 2013 Update to the
Florida Building Code to considered by the
Fire TAC
Meeting
Date: August 1, 2013
Tracking ID |
Florida
Building Code, Residential Proposed
Changes |
Comments |
TAC Action |
||||||||||||||||||||||||||||||||||
F1 |
Section 553.73(10), Florida Statutes 553.73
Florida Building codes— (17) A provision Revise R101.2
to read as follows: R101.2 Scope. The provisions
of the International Residential Code for One- and Two-family Dwellings shall
apply to the construction, alteration, movement, enlargement, replacement,
repair, equipment, use and occupancy, location, removal and demolition of
detached one- and two-family dwellings and townhouses not more than three
stories above grade plane in height with
a separate means of egress and their accessory structures. Exceptions: 1. Live/work
units complying with the requirements of Section 419 of the International
Building Code shall be permitted to be built as one- and two-family dwellings
or townhouses. Fire suppression required by Section 419.5 of the International
Building Code when constructed under the International Residential Code
for One- and Two-family Dwellings shall conform to 2.
Owner-occupied lodging houses with five or fewer guestrooms shall be
permitted to be constructed in accordance with the International
Residential Code for One- and Two-family Dwellings when equipped with a
fire sprinkler system in accordance with Section
|
Glitch – (e) Changes to or inconsistencies with federal or
state law. HB 269. |
|
||||||||||||||||||||||||||||||||||
F2 |
Revise R302 to
read as follows: SECTION R302
FIRE-RESISTANT CONSTRUCTION R302.1
Exterior walls. Construction,
projections, openings and penetrations of exterior walls of dwellings
and accessory buildings shall comply with Table R302.1(1
Exceptions: 1. Walls,
projections, openings or penetrations in walls perpendicular to the line used
to determine the fire separation distance. 2. Walls of dwellings
and accessory structures located on the same lot. 3. Detached
tool sheds and storage sheds, playhouses and similar structures 4. Detached
garages accessory to a dwelling located within 2 feet (610 mm) of a lot
line are permitted to have roof eave projections not exceeding 4 inches
(102 mm). 5. Foundation
vents installed in compliance with this code are permitted. |
Glitch – (e) Changes to or inconsistencies with federal or
state law. HB 269. |
|
||||||||||||||||||||||||||||||||||
F3 |
Delete Table
R302.1(2) TABLE
R302.1(2) EXTERIOR
WALLS—DWELLINGS WITH FIRE SPRINKLERS |
Glitch – (e) Changes to or inconsistencies with federal or
state law. HB 269. |
|
||||||||||||||||||||||||||||||||||
|
|
||||||||||||||||||||||||||||||||||||
F4 |
Delete Section
P2904 in its entirety SECTION P2904 DWELLING UNIT
FIRE SPRINKLER SYSTEMS (See
Attachment) |
Glitch – (e) Changes to or inconsistencies with federal or
state law. HB 269. |
|
||||||||||||||||||||||||||||||||||
F5 |
Additional
Residential Fire Sprinkler language revisions to be considered for
modification (See Note): Revise R302.3
to read as follows: R302.3 Two-family dwellings. Dwelling units in
two-family dwellings shall be separated from each other by wall and/or floor assemblies having not less than a 1-hour fire-resistance rating when tested in accordance with ASTM E 119 or UL 263. Fire-resistance-rated floor/ceiling and wall assemblies shall extend to and be tight against the exterior wall, and
wall assemblies shall extend from the foundation to the underside of the roof sheathing. Exceptions:
Revise R309.5
to read as follows: R309.5 Fire sprinklers.
Revise R501.3 to
read as follows: R501.3 Fire protection of floors. Floor assemblies, not required elsewhere in this code to be fire-resistance rated, shall be provided with a 1/2-inch
(12.7 mm) gypsum wallboard membrane, 5/8-inch (16 mm) wood structural panel
membrane, or equivalent on the underside of the floor framing member. Exceptions: 1.
2. – 4. (No Change) Revise P2803.6.1 to read as follows: P2803.6.1 Requirements for discharge pipe. The discharge piping serving a pressure-relief valve, temperature relief valve or combination valve shall: 1. – 12. (No Change) 13.
|
Glitch – (e) Changes to or inconsistencies with federal or
state law. HB 269. Note:
Items should be modified as indicated if TAC recommends approval for
modifications listed in F1-F4 |
|
Revise P2803.6.1 to read as follows:
TABLE
P2902.3
APPLICATION
FOR BACKFLOW PREVENTERS
DEVICE
|
DEGREE
OF HAZARDa |
APPLICATIONb
|
APPLICABLE
|
Air gap |
High
or low hazard |
Backsiphonage or backpressure |
ASME A112.1.2 |
Air gap fittings for use with
plumbing fixtures, appliances and appurtenances |
High
or low hazard |
Backsiphonage or backpressure |
ASME A112.1.3 |
Antisiphon-type fill valves for
gravity water closet flush tanks |
High
hazard |
Backsiphonage only |
ASSE 1002, CSA B125.3 |
Backflow preventer with
intermediate atmospheric vents |
Low
hazard |
Backpressure or backsiphonage |
ASSE 1012, CSA B64.3 |
Double check backflow prevention
assembly and double check fire protection backflow prevention assembly |
Low
hazard |
Backpressure or backsiphonage |
ASSE 1015, AWWA C510, |
|
|
|
|
Dual-check-valve-type backflow
preventer |
Low
hazard |
Backpressure or backsiphonage |
ASSE 1024, CSA B64.6 |
Hose-connection backflow preventer
|
High
or low hazard |
Low head backpressure, rated
working pressure backpressure or backsiphonage Sizes 1/2″
- 1″ |
ASSE 1052, CSA B64.2.1.1 |
Hose-connection vacuum breaker |
High
or low hazard |
Low head backpressure or
backsiphonage Sizes 1/2″, 3/4″,
1″ |
ASSE 1011, CSA B64.2, CSA B64.2.1 |
Laboratory faucet backflow
preventer |
High
or low hazard |
Low head backpressure and
backsiphonage |
ASSE 1035, CSA B64.7 |
Pipe-applied atmospheric-type
vacuum breaker |
High
or low hazard |
Backsiphonage only Sizes 1/4″
- 4″ |
ASSE 1001, CSA B64.1.1 |
Pressure vacuum breaker assembly |
High
or low hazard |
Backsiphonage only Sizes 1/2″
- 2″ |
ASSE 1020, CSA B64.1.2 |
|
|
|
|
Reduced pressure principle
backflow prevention assembly and reduced pressure principle fire protection
backflow prevention assembly |
High
or low hazard |
Backpressure or backsiphonage |
ASSE 1013, AWWA C511, |
Spill-resistant pressure vacuum
breaker |
High
or low hazard |
Backsiphonage only Sizes 1/4″
- 2″ |
ASSE 1056, CSA B64.1.3 |
Vacuum breaker wall hydrants,
frost-resistant, automatic-draining type |
High
or low hazard |
Low head backpressure or
backsiphonage Sizes 3/4″ - 1″ |
ASSE 1019, CSA B64.2.2 |
For SI: 1 inch = 25.4 mm. |
a. Low hazard—See Pollution (Section R202).
High hazard—See Contamination (Section R202). |
b. See Backpressure (Section R202).
See Backpressure, Low Head (Section R202).
See Backsiphonage (Section
R202). |