Florida Building Commission

Fire Technical Advisory Committee

Meeting Minutes

August 6, 2014

Meeting Location:  Teleconference Meeting from Tallahassee, Florida

 

TAC/POC Members and Objectives

TAC Members Present Via Teleconference: Hamid Bahadori, Chair;   Brad Schiffer;  Tony Apfelbeck;; Robert Hamburger; Charlie Frank; Peter T. Schwab; Joe Belcher;

TAC Members not Present: James R. Schock; Jeffery Gross; Joe Holland

Staff Present: Mo Madani,  Robert lorenzo, Marlita Peters, Robert Benbow, Norman Bellamy, Joe Bigelow, Zubeyde Benici; April Hammonds, Jim Richmond, Chip Sellers, Nick Duval

Facilitator: Robert Benbow

Guests: Dwight Wilkes, Eric Neilenger; Mike Ennis

Objectives: To consider and discuss the DS 2014-083 by Eric Neilinger of Fire Alarm Systems and Security Inc.

 

Meeting Minutes

Objective

Discussion of objectives included the following: 

1)

 

10:00 AM Welcome and Opening, Roll Call.  A quorum was not originally present. Robert Hamburger joined the teleconference and a quorum was reached.

 

2) and 3)

Agenda and Meeting minutes. The Agenda for today’s meeting and the meeting minutes for the June 27, 2014 Fire TAC meeting were approved unanimously by the committee members.

4)

To consider, discuss, and provide recommendation for consideration by the commission regarding DS 2014-083 by Eric Neilinger of Fire Alarm Systems and Security Inc. The Declaratory Statement was introduced by the chair. The declaratory statement was presented by the petitioner.

TAC Actions:

Question 1: Does a UL listed integrated Fire alarm and smoke control system meet the intent of 909.12?

 Answer:  Answer is not possible.  The Commission has no authority to determine whether a listed system meets the intent of the Code. In fact, determination of whether a listed product meets code is subject to the design of the engineer of record and the review and approval by the local authority having jurisdiction.  The Fire TAC agreed with staff’s analysis and unanimously voted to approve the staff analysis.

Question: 2)   Do we have to separate the one integrated system into two separate control panels?

Answer:    Yes, as per 909.16 of the FBC, Building, separate control panels are required.  However, as per section 909.16.2 of the FBC, Building, an integrated system is permitted as designed by the engineer of record and approved by the local authority having jurisdiction. The Fire TAC agreed with staff’s analysis and unanimously voted to approve the staff analysis.

 

Question 3)   As a minimum code compliant system does 909 require the Fire Fighter smoke control panel to be a separate graphic display panel?

Answer: Answer is not possible, The term “graphic display” is not utilized in Section 909.16. Determination of whether a product meets code is subject to the design of the engineer of record and review and approval from the local building authority having jurisdiction. The Fire TAC agreed with Mr. Apfelbeck’s motion and unanimous voted to approve the motion.

Question 4) To meet minimum code compliance will the installation of a UL listed integrated Fire Alarm and Smoke Control system that meets all the elements of 909.16 meet the intent of 909 for a Fire Fighter smoke control panel?

Answer: No, as per 909.16 of the FBC, Building, and separate control panels are required.  However, as per section 909.16.2 of the FBC, Building, an integrated system is permitted as designed by the engineer of record and approved by the local authority having jurisdiction. The Fire TAC agreed with staff’s analysis and unanimously voted to approve the staff analysis.

April Hammonds, General Counsel raised some concerns on the integrity of the petition as this particular issue could be already resolved as stated by the petitioner which would require a new petition for declaratory statement to be applied for regarding a different situation. The TAC requested that Counsel research the standing of the request and report her findings to the FBC on whether the DEC Statement should be dismissed or addressed.

 

5)

Other TAC Business. Having no other TAC business, the meeting was closed after a Motion and a Second to Adjourn.

 

Staff Contacts: Robert Benbow Planning Analyst (850) 717-1828 Robert.benbow@myfloridalicense.com or Mo Madani, Manager mo.madani@dbpr.state.fl.us (850) 717-1825