Issue: DS-2014-083 Petitioner Eric a Neilinger, Representing Fire
Alarm Systems and Security INC. seeks a Declaratory Statement on 2010 Florida
Building Code new building, high rise chapter 9, section 909.1, 909.12, to
include 12.1 through 12.3, 909.16 to include 909.16.1 through 909.16.3.
Petitioner
seeks clarification of the following questions:
1) Does a UL
listed integrated Fire alarm and smoke control system meet the intent of
909.12?
2) Do we have to
separate the one integrated system into two separate control panels?
3) As a minimum
code compliant system does 909 require the Fire Fighter smoke control panel to
be a separate graphic display panel?
4) To meet
minimum code compliance will the installation of a UL listed integrated Fire Alarm
and Smoke Control system that meets all the elements of 909.16 meet the intent of 909 for a Fire
Fighter smoke control panel?
Background:
This
applicant is proposing to install a
Honeywell UL listed Integrated combination fire alarm system/smoke control
system in compliance with NFPA and Florida Building Code 909. The system has
all of the functions and requirements as stated in 909 for a smoke control
panel and is listed for its intended use. The Contractor and their consultant
is requiring in addition to the combination smoke control panel an additional
separate graphic annunciator that duplicates the combination panel switches and
lights. We are looking to the FBC to issue an opinion.
2010 Florida Building
Code, Building
Section 202
Definitions
APPROVED. Acceptable to the code official or authority having
jurisdiction.
403.4 Emergency systems.
The detection, alarm and emergency systems of high-rise buildings
shall comply with Sections 403.4.1 through 403.4.8.
[F] 403.4.1 Smoke detection.
Smoke detection shall be provided in accordance with Section
907.2.13.1.
[F] 403.4.2 Fire alarm system.
A fire alarm system shall be provided in accordance with Section
907.2.13.
[F] 403.4.3 Emergency voice/alarm communication system.
An emergency voice/alarm communication system shall be provided in
accordance with Section 907.5.2.2.
[F] 403.4.4 Emergency responder radio coverage.
Emergency responder radio coverage shall be provided in accordance
with the Florida Fire Prevention Code.
[F] 403.4.5 Fire command.
A fire command center complying with Section 911 shall be provided
in a location approved by the fire department.
403.4.6 Smoke removal.
Smoke control shall be provided in accordance with Section 909.
Exception: I-2 occupancies that comply with Sections 407, 419.3.7
and 420.3.17 shall not require smoke control systems in accordance with Section
909.
[F] 403.4.7 Standby power.
A standby power system complying with Chapter 27 shall be provided
for standby power loads specified in Section 403.4.7.2.
[F] 403.4.7.1 Special requirements for standby power systems.
If the standby system is a generator set inside a building, the
system shall be located in a separate room enclosed with 2-hour fire barriers
constructed in accordance with Section 707 or horizontal assemblies constructed
in accordance with Section 712, or both. System supervision with manual start
and transfer features shall be provided at the fire command center.
[F] 403.4.7.2 Standby power loads.
The following are classified as standby power loads:
1. Power and lighting
for the fire command center required by Section 403.4.5;
2. Ventilation and
automatic fire detection equipment for smokeproof enclosures; and
3. Standby power
shall be provided for elevators in accordance with Sections 1006.2.4, 3003,
3007 and 3008.
[F] 403.4.8 Emergency power systems.
An emergency power system complying with Chapter 27 shall be
provided for emergency power loads specified in Section 403.4.8.1.
[F] 403.4.8.1 Emergency power loads.
The following are classified as emergency power loads:
1. Exit signs and
means of egress illumination required by Chapter 10;
2. Elevator car
lighting;
3. Emergency
voice/alarm communications systems;
4. Automatic fire
detection systems;
5. Fire alarm
systems; and
6. Electrically
powered fire pumps.
902.1 Definitions
ANNUNCIATOR. A unit containing one or more indicator lamps, alphanumeric
displays or other equivalent means in which each indication provides status
information about a circuit, condition or location. [F]
FIRE ALARM CONTROL UNIT.
A system component that receives inputs from
automatic and manual fire alarm devices and may be capable of supplying power
to detection devices and transponder(s) or off-premises transmitter(s). The
control unit may be capable of providing a transfer of power to the
notification appliances and transfer of condition to relays or devices. [F]
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS
907.1 General. [F]
This section covers the application,
installation, performance and maintenance of fire alarm systems and their
components.
907.1.1 Construction documents. [F]
Construction documents for
fire alarm systems shall be of sufficient clarity to indicate the location,
nature and extent of the work proposed and show in detail that it will conform
to the provisions of this code, the Florida Fire Prevention Code,
and relevant laws, ordinances, rules and regulations, as determined by the
building official.
907.1.2 Fire alarm shop drawings.
[F]
Shop drawings for fire alarm systems shall be submitted for review and approval
prior to system installation, and shall include, but not be limited to, all of
the following:
1. A floor plan that indicates the use
of all rooms.
2. Locations of alarm-initiating
devices.
3. Locations of alarm notification
appliances, including candela ratings for visible alarm notification
appliances.
4. Location of fire alarm control unit,
transponders and notification power supplies.
5. Annunciators.
6. Power connection.
7. Battery calculations.
8. Conductor type and sizes.
9. Voltage drop calculations.
10. Manufacturers' data sheets
indicating model numbers and listing information for equipment, devices and
materials.
11. Details of ceiling height and
construction.
12. The interface of fire safety control
functions.
13. Classification of the supervising
station.
F] 907.1.3 Equipment.
Systems and components shall be listed and approved for the purpose
for which they are installed.
[F] 907.2.6.1.1 Smoke alarms.
Single- and multiple-station smoke
alarms shall be installed in accordance with Section 907.2.11.
[F] 907.2.11 Single- and
multiple-station smoke alarms.
Listed single- and multiple-station
smoke alarms complying with UL 217 shall be
installed in accordance with Sections 907.2.11.1 through 907.2.11.4 and NFPA
72.
[F] 907.2.11.1 Group R-1.
An approved single-station smoke alarm
shall be installed in every guestroom and every living area and sleeping room
within a guest suite.
[F] 907.2.11.2 Groups R-2, R-3, R-4 and
I-1.
Single- or multiple-station smoke alarms
shall be installed and maintained in Groups R-2, R-3, R-4 and I-1 regardless of
occupant load at all of the following locations:
1. On
the ceiling or wall outside of each separate sleeping area in the immediate
vicinity of bedrooms.
2. In
each room used for sleeping purposes.
Exception: Single- or multiple-station
smoke alarms in Group I-1 occupanices shall not be required where smoke
detectors are provided in the sleeping rooms as part of an automatic smoke
detection system.
3. In
each story within a dwelling unit, including basements but not including crawl
spaces and uninhabitable attics. In dwellings or dwelling units with split
levels and without an intervening door between the adjacent levels, a smoke
alarm installed on the upper level shall suffice for the adjacent lower level
provided that the lower level is less than one full story below the upper
level.
[F] 907.2.11.3 Interconnection.
Where more than one smoke alarm is
required to be installed within an individual dwelling unit or sleeping unit in
Group R-1, R-2, R-3 or R-4, the smoke alarms shall be interconnected in such a
manner that the activation of one alarm will activate all of the alarms in the
individual unit. The alarm shall be clearly audible in all bedrooms over
background noise levels with all intervening doors closed.
[F] 907.2.11.4 Power source.
In new construction, required smoke
alarms shall receive their primary power from the building wiring where such
wiring is served from a commercial source and shall be equipped with a battery
backup. Smoke alarms with integral strobes that are not equipped with battery
backup shall be connected to an emergency electrical system. Smoke alarms shall
emit a signal when the batteries are low. Wiring shall be permanent and without
a disconnecting switch other than as required for overcurrent protection.
Exception: Smoke alarms are not required
to be equipped with battery backup where they are connected to an emergency
electrical system.
F] 907.2.13 High-rise buildings.
High-rise buildings shall be provided with
an automatic smoke detection system in accordance with Section 907.2.13.1, a
fire department communication system in accordance with Section 907.2.13.2 and
an emergency voice/alarm communication system in accordance with Section 907.5.2.2.
Exceptions:
1. Airport
traffic control towers in accordance with Sections 907.2.22 and 412.
2. Open
parking garages in accordance with Section 406.3.
3. Buildings
with an occupancy in Group A-5 in accordance with Section 303.1.
4. Reserved.
5. Buildings
with an occupancy in Group H-1, H-2 or H-3 in accordance with Section 415.
6. In
Group I-1 and I-2 occupancies, the alarm shall sound at a constantly attended
location and general occupant notification shall be broadcast by the emergency
voice/alarm communication system.
[F] 907.2.13.1 Automatic smoke
detection.
Automatic smoke detection in high-rise
buildings shall be in accordance with Sections 907.2.13.1.1 and 907.2.13.1.2.
[F] 907.2.13.1.1 Area smoke detection.
Area smoke detectors shall be provided in accordance with this
section. Smoke detectors shall be connected to an automatic fire alarm system.
The activation of any detector required by this section shall operate the
emergency voice/alarm communication system in accordance with Section 907.5.2.2.
Smoke detectors shall be located as follows:
1. In each mechanical
equipment, electrical, transformer, telephone equipment or similar room which
is not provided with sprinkler protection.
2. In each elevator
machine room and in elevator lobbies.
[F] 907.2.13.1.2 Duct smoke detection.
Duct smoke detectors complying with Section 907.3.1 shall be
located as follows:
1. In the main return
air and exhaust air plenum of each air-conditioning system having a capacity
greater than 2,000 cubic feet per minute (cfm) (0.94 m3/s). Such detectors
shall be located in a serviceable area downstream of the last duct inlet.
2. At each connection
to a vertical duct or riser serving two or more stories from a return air duct
or plenum of an air-conditioning system. In Group R-1 and R-2 occupancies, a
smoke detector is allowed to be used in each return air riser carrying not more
than 5,000 cfm (2.4 m3/s) and serving not more than 10 air inlet openings.
[F] 907.8 Inspection, testing and maintenance.
The maintenance and testing schedules and procedures for fire alarm
and fire detection systems shall be in accordance with the Florida Fire
Prevention Code.
SECTION 909 SMOKE CONTROL
SYSTEMS
909.1 Scope and purpose. [F]
This section applies to mechanical or passive smoke
control systems when they are required by other provisions of this code. The
purpose of this section is to establish minimum requirements for the design,
installation and acceptance testing of smoke control systems that are intended
to provide a tenable environment for the evacuation or relocation of occupants.
These provisions are not intended for the preservation of contents, the timely
restoration of operations or for assistance in fire suppression or overhaul
activities. Smoke control systems regulated by this section serve a different
purpose than the smoke- and heat-venting provisions found in Section 910. Mechanical smoke control systems shall not be considered
exhaust systems under Chapter 5 of the Florida
Building Code, Mechanical.
909.12 Detection and control systems.
Fire detection systems providing control input or
output signals to mechanical smoke control systems or elements thereof shall
comply with the requirements of Section 907. Such systems shall be equipped with a control unit complying
with UL 864 and listed as smoke
control equipment.
909.12.1 Wiring. [F]
In addition to meeting requirements of Chapter 27 of the Florida Building Code, Building, all wiring, regardless of voltage, shall be fully enclosed
within continuous raceways.
909.12.2 Activation. [F]
Smoke control systems shall be activated in
accordance with this section.
909.12.3 Automatic control. [F]
Where completely automatic control is required
or used, the automatic-control sequences shall be initiated from an
appropriately zoned automatic
sprinkler system complying
with Section 903.3.1.1, manual controls that are readily accessible to the fire
department and any smoke detectors required by engineering analysis.
Fans within the building shall be shown on the fire-fighter's
control panel. A clear indication of the direction of airflow and the
relationship of components shall be displayed. Status indicators shall be
provided for all smoke control equipment, annunciated by fan
and zone, and by pilot-lamp-type indicators as follows:
1. Fans, dampers and other operating equipment in
their normal status-WHITE.
2. Fans, dampers and other operating equipment in
their off or closed status-RED.
3. Fans, dampers and other operating equipment in
their on or open status-GREEN.
4. Fans, dampers and other operating equipment in a
fault status-YELLOW/AMBER.
909.16 Fire-fighter's smoke control panel. [F]
A fire-fighter's smoke control panel for fire department emergency response purposes only shall
be provided and shall include manual control or override of automatic control
for mechanical smoke control systems. The panel shall be
located in a fire command center complying with
Section in highrise buildings or buildings with
smoke-protected assembly seating. In all other
buildings, the fire-fighter's smoke control panel shall be installed in an approved location
adjacent to the fire alarm control panel. The fire-fighter's smoke control
panel shall comply with Sections 909.16.1 through 909.16.3.
909.16.1 Smoke control systems. [F]
Fans within the building shall be shown on the fire-fighter's
control panel. A clear indication of the direction of airflow and the
relationship of components shall be displayed. Status indicators shall be
provided for all smoke control equipment, annunciated by fan and zone, and by
pilot-lamp-type indicators as follows:
1. Fans, dampers and other operating equipment in
their normal status-WHITE.
2. Fans, dampers and other operating equipment in
their off or closed status-RED.
3. Fans, dampers and other operating equipment in
their on or open status-GREEN.
4. Fans, dampers and other operating equipment in a
fault status-YELLOW/AMBER.
909.16.2
Smoke control panel. [F]
The fire-fighter's control panel shall provide control capability
over the complete smoke-control system equipment within the building as
follows:
1. ON-AUTO-OFF control over each individual piece of operating
smoke control equipment that can also be controlled from other sources within
the building. This includes stairway pressurization fans; smoke exhaust
fans; supply, return and exhaust fans; elevator shaft fans and other operating
equipment used or intended for smoke control purposes.
2. OPEN-AUTO-CLOSE control over individual dampers relating to smoke control and that
are also controlled from other sources within the building.
3. ON-OFF or OPEN-CLOSE control over smoke control and other
critical equipment associated with a fire or smoke emergency and that can only
be controlled from the fire-fighter's control panel.
Exceptions:
1. Complex systems, where approved,
where the controls and indicators are combined to control and indicate all
elements of a single smoke zone as a unit.
2. Complex systems, where approved,
where the control is accomplished by computer interface using approved, plain English
commands.
909.16.3 Control action and
priorities. [F]
The firefighter's control panel actions shall be as follows:
1. ON-OFF and OPEN-CLOSE control actions shall have the highest
priority of any control point within the building. Once issued from the
fire-fighter's control panel, no automatic or manual control from any other
control point within the building shall contradict the control action. Where
automatic means are provided to interrupt normal, nonemergency equipment
operation or produce a specific result to safeguard the building or equipment
(i.e., duct freezestats, duct smoke detectors, high-temperature cutouts,
temperature-actuated linkage and similar devices), such means shall be capable
of being overridden by the fire-fighter's control panel. The last control
action as indicated by each fire-fighter's control panel switch position shall
prevail. In no case shall control actions require the smoke control system to assume
more than one configuration at any one time.
Exception: Power disconnects
required by Chapter 27 of
the Florida Building Code,
Building.
2. Only the AUTO position of each three-position fire-fighter's
control panel switch shall allow automatic or manual control action from other
control points within the building. The AUTO position shall be the NORMAL,
nonemergency, building control position. Where a fire-fighter's control panel
is in the AUTO position, the actual status of the device (on, off, open,
closed) shall continue to be indicated by the status indicator described above.
When directed by an automatic signal to assume an emergency condition, the
NORMAL position shall become the emergency condition for that device or group
of devices within the zone. In no case shall control actions require the smoke
control system to assume more than one configuration at any one time.
SECTION 911 FIRE COMMAND CENTER
911.1 General. [F]
Where required by other sections of this code and
in all buildings classified as high-rise buildings by this code, a fire command
center for fire department operations shall be provided and shall comply with
Sections 911.1.1 through 911.1.5.
911.1.1 Location and access. [F]
The location and accessibility of the fire command center shall be approved by the fire chief.
911.1.2 Separation. [F]
The fire command center shall be separated from the remainder of the building
by not less than a 1-hour fire
barrier constructed in
accordance with Section 707 or horizontal
assembly constructed in
accordance with Section 712,
or both.
911.1.3 Size. [F]
The room shall be a minimum of 200 square feet (19 m2)
with a minimum dimension of 10 feet (3048 mm).
911.1.4 Layout approval. [F]
A layout of the fire command center and all features required by Section
911.1.5 to be contained therein shall be submitted for approval prior to
installation.
911.1.5 Required features. [F]
The fire command center shall comply with NFPA 72 and
shall contain the following features:
1. The emergency voice/alarm communication system control unit.
2. The fire department communications system.
3. Fire detection and alarm system annunciator.
4. Annunciator unit visually indicating the location of the
elevators and whether they are operational.
5. Status indicators and controls for air distribution systems.
6. The fire-fighter's control panel required by Section 909.16 for smoke control systems installed in
the building.
7. Controls for unlocking stairway doors simultaneously.
8. Sprinkler valve and waterflow detector display panels.
9. Emergency and standby power status indicators.
10. A telephone for fire department use with controlled access to
the public telephone system.
11. Fire pump status indicators.
12. Schematic building plans indicating the typical floor plan and
detailing the building core, means
of egress, fire protection systems, fire-fighting equipment and fire
department access and the location of fire
walls, fire barriers, fire partitions, smoke barriers and smoke partitions.
13. Work table.
14. Generator supervision devices, manual start and transfer
features.
15. Public address system, where specifically required by other
sections of this code.
16. Elevator fire recall switch in accordance with ASME A17.1.
17. Elevator emergency or standby power selector switch(es), where
emergency or standby power is provided.
Staff Analysis:
Question: 1) Does a UL listed integrated
Fire alarm and smoke control system meet the intent of 909.12?
Answer: Answer is not possible. The Commission has no authority to determine
whether a listed system meets the intent of the Code. In fact, determination of
whether a listed product meets code is subject to the design of the engineer of
record and the review and approval by the local authority having
jurisdiction.
Question: 2) Do we have to separate the
one integrated system into two separate control panels?
Answer: Yes, as per 909.16 of the FBC, Building, separate control panels are required. However, as per section 909.16.2 of the FBC,
Building, an integrated system is permitted as designed by the engineer of
record and approved by the local authority having jurisdiction.
Question 3) As a minimum code compliant system does 909
require the Fire Fighter smoke control panel to be a separate graphic display
panel?
Answer: Yes, as per sections 909.16.1 and 911.1.5 of
the FBC, Building, separate graphic display panel for the fire fighter smoke
control panel is required.
Question 4) To meet minimum code compliance will the
installation of a UL listed integrated Fire Alarm and Smoke Control system that
meets all the elements of 909.16 meet the intent of 909 for a Fire Fighter
smoke control panel?
Answer: No, as per 909.16 of the FBC, Building, and separate
control panels are required. However, as
per section 909.16.2 of the FBC, Building, an integrated system is permitted as
designed by the engineer of record and approved by the local authority having
jurisdiction.