FLORIDA BUILDING COMMISSION
BUILDING (STRUCTURAL)

TECHNICAL ADVISORY COMMITTEE

 

MEETING MINUTES

 

THURSDAY, AUGUST 6, 2015
9:00 A.M. ET – 10:34 A.M.

TELECONFERENCE/WEBINAR MEETING 
FROM TALLAHASSEE, FLORIDA

 

If requested, enter name, email address, click “join”

 TAC/POC MEMBERS AND OBJECTIVES

STRUCTURAL TAC MEMBERS PRESENT : James Schock; Chair, CW Macomber, Steve Strawn, Craig Parrino, Joe Hetzel, Daniel L. Lavrich, Do Y. Kim, Jaime Gascon, Warner Chang, David Compton, Cris Fardelmann

·         Objectives 

·         Considered, discussed and provided recommendations on two declaratory statements..

 MEETING AGENDA

OBJECTIVE

REVIEW OF OBJECTIVES WILL INCLUDE THE FOLLOWING:  Description of issue, discussion by TAC, public comment, TAC action

9:00 A.M.

 1)

Welcome and Opening, Roll Call

Reviewed and Approved of August 6, 2015 Meeting Agenda
Reviewed and Approved of 
June 25, 2015 Meeting Minutes

2)

The committee considered, discussed and provided recommendations to the Commission on the following declaratory statements:

 

DS2015-81 by Clifford A. Schulman, Esq. of Weiss Serota Helfman Cole Bierman, P.L.(Staff Analysis ) (Supporting Docs)

Questions:

 Question (1)  Is the building, including the System, regulated by the FBC?

 Answer:  (d)Yes, as per section 102.2. and 1601.1 of the Florida Building Code 5th Edition (2014), Building the project in question falls within the scope of the Florida Building Code

 

Question (2)  If yes, is the System governed by Chapter 30 ALI Standards?;

Answer: No, the project in question falls outside the scope of ALI standards

 

Question (3)   If not, does the FBC require that the entire System (including the lifting structure itself) be certified by an OSHA approved NRTL?

Answer: Since the system is anchored and attached to the structural elements of the building, the design and development of the system will fall within the technical scope of the FBC requiring that the building/structure be designed and constructed in accordance with the applicable material and design standard of the FBC and that the lifting structure be designed, tested and evaluated in accordance with the procedure developed by a registered design professional and tested by an approved agency as approved by the local authority having jurisdiction.

DS2015-084 by John Farinelli of JC Code & Construction Consultants, Inc. ( Letter_1) ( Letter 2) (Staff Analysis )

Question #1: When stucco applications are installed per ASTM C 926 as permitted under the Exception to Section R703.6.4, is compliance with Section 703.6.5 also required?

 

Answer:  No, If ASTM C 926 is used as an alternate method chosen by the designer/contractor then compliance with 703.6.5 is not required.

3)

No Comments from TAC and public

4)

Adjourned at 10:34 A.M.