Issue: DS 2015-079. Petitioner Mr. George Stefanovici seeks clarification on several projects/situations as follows:
Project: Ambay Esthetics – Transformations Surgery Center, new construction of outpatient health care facility with two operating rooms, exam rooms, offices and other support areas. Mechanical design consists of five rooftop packaged DX units, constant and variable air volume boxes. Each Operating Room is served by a dedicated constant volume rooftop air-conditioning unit.
5th
Edition (2014) Florida Building Code, Energy Conservation
C101.3 Intent. This code shall
regulate the design and construction of buildings for the effective use and
conservation of energy over the useful life of each building. This code is
intended to provide flexibility to permit the use of innovative approaches and
techniques to achieve this objective. This code is not intended to abridge
safety, health or environmental requirements contained in other applicable
codes or ordinances.
SECTION
R302 DESIGN CONDITIONS
R302.1 Interior
design conditions. The
interior design temperatures used for heating and cooling load calculations
shall be a maximum of 72°F (22°C) for heating and minimum of 75°F (24°C) for
cooling.
Question: Does Section C302.1 – i.e. minimum design temperature in cooling 75 deg F – apply to the Operating Room? Surgeons are requesting a maximum design temperature of 68 deg F.
Answer/Option #1: Yes. However, a maximum design temperature of 68
deg F may be allowed, if required by other applicable codes or ordinances as
permitted in Section C101.3 of the 5th Edition (2014) FBC, Energy
Conservation.
Answer/Option #2: Not possible. No technical
documentation is provided for the maximum design temperature of 68 deg F.
Project: Lake Gibson High School HVAC Upgrade
Complete replacement of the air-conditioning system in
an existing high school. The new system
consists of new air-cooled chillers, new constant volume chilled water air
handlers, variable air volume chilled water air handlers and general exhaust
fans.
5th
Edition (2014) Florida Building Code, Energy Conservation
C401.2
Application. Commercial
buildings shall comply with one of the following:
1. The
requirements of ANSI/ASHRAE/IESNA 90.1.
2. The
requirements of Sections C402, C403, C404 and C405. In addition, commercial
buildings shall comply with Section C406.2, C406.3 or C406.4.
3. The
requirements of Section C407, C402.4, C403.2, C404, C405.2, C405.3, C405.4,
C405.6 and C405.7. The building energy
cost shall be equal to or less than 85 percent of the standard reference design
building.
C401.2.1
Application to existing buildings. Additions, alterations and repairs to
existing buildings shall comply with one of the following:
1. Sections
C402, C403, C404 and C405; or
2.
ANSI/ASHRAE/IESNA 90.1.
Question: Does the
engineer have to follow one of the methods listed in Section C401.2.1 or is the
engineer allowed to prove compliance with the Energy Conservation code by using
the method described in Section C401.2.3?
Answer: For the project
in question, the engineer must follow one of the two compliance methods listed
under Section C401.2.1 of the 5th Edition (2014) FBC, Energy
Conservation.
Project:
Winter Haven Hospital – HVAC Upgrade
Direct
replacement of two roof mounted packaged DX air-conditioning units with new
equipment in an existing hospital. The
existing ductwork remains in place, only the roof mounted equipment is being
replaced.
C101.4.3
Additions, alterations, renovations or repairs. Additions,
alterations, renovations or repairs to an existing building, building system or
portion thereof shall conform to the provisions of this code as they relate to
new construction without requiring the unaltered portion(s) of the
existing
building or building system to comply with this code. Additions, alterations,
renovations or repairs shall not create an unsafe or hazardous condition or
overload existing building systems. An addition shall be deemed to comply with
this code if the addition alone complies or if the existing building and
addition comply with this code as a single building.
C101.4.7
Building systems and components. Thermal efficiency standards are set for
the following building systems and components where new products are installed
or replaced in existing buildings, and for which a permit must be obtained. New
products shall meet the minimum efficiencies allowed by this code for the
following systems
and components:
Heating,
ventilating or air conditioning systems.
Service water or
pool heating systems.
Electrical
systems and motors.
Lighting
systems.
Replacement
fenestration.
Exceptions:
…
4. Replacement
equipment that would require extensive revisions to other systems, equipment
or elements of a
building where such replacement is a like-for-like replacement, such as through
the-wall condensing units and PTACs, chillers,
and cooling
towers in confined spaces.
C401.2.1 Application
to existing buildings. Additions, alterations and repairs to existing
buildings shall comply with one of the following:
1. Sections
C402, C403, C404 and C405; or
2.
ANSI/ASHRAE/IESNA 90.1.
C403.3 Simple
HVAC systems and equipment (Prescriptive). This section applies to buildings
served by unitary or packaged HVAC equipment listed in Tables C403.2.3(1)
through
C403.2.3(8), each serving one zone and controlled by a single thermostat
in the zone served. It also applies to two pipe heating systems serving
one or more zones, where no
cooling system
is installed.
C403.3.1
Economizers. Each
cooling system that has a fan shall include either an air or water economizer meeting
the requirements of Sections C403.3.1.1 through C403.3.1.1.4.
Exception: Economizers are
not required for the systems listed below.
1. Individual
fan-cooling units with a supply capacity less than the minimum listed in Table
C403.3.1(1).
2. Where more
than 25 percent of the air designed to be supplied by the system is to spaces
that are designed to be humidified above 35°F (1.7 °C) dew-point temperature to
satisfy process needs.
3. Systems that
serve residential spaces where the system capacity is less than five
times the
requirement
listed in Table C403.3.1(1).
4. Systems
expected to operate less than 20 hours per week.
5. Where the use
of outdoor air for cooling will affect supermarket open refrigerated
casework
systems.
6. Where the
cooling efficiency meets or exceeds the efficiency requirements
in Table C403.3.1(2).
Question:
Does Section C403.3 require an economizer on the new single zone
constant volume DX air-conditioning units?
The equipment in question does not qualify as an exception as listed
under C403.3.1.1 through C403.3.1.1.6.
Answer: Yes.
As per Section C403.3.1 of the 5th Edition (2014) FBC, Energy
Conservation, an economizer is required.
Project: Lake Gibson High School HVAC Upgrade
Complete
replacement of the air-conditioning system in a high school. The new system consists of new air-cooled
chillers, new constant volume and variable air volume chilled water air
handlers.
C403.4 Complex
HVAC systems and equipment (Prescriptive). This section applies to buildings
served by HVAC equipment and systems not covered in Section C403.3.
C403.4.1
Economizers. Economizers
shall comply with Sections C403.4.1.1 through C403.4.1.4.
Question:
Section C403.4 is applicable to all systems not covered by Section
C403.3 – i.e. unitary or packaged HVAC equipment, each serving one zone and
controlled by a single thermostat. Therefore, is an economizer as described in
Section C403.4 required on an HVAC system consisting of air-cooled chillers,
variable air volume air handlers and variable air volume boxes?
Answer:
Yes. As per Section C403.4 of the
5th Edition (2014) FBC, Energy Conservation, an economizer is
required.
Project:
Ambay Esthetics – Transformations Surgery Center; new construction
of outpatient health care facility with two operating rooms, exam rooms,
offices and other support areas.
Mechanical design consists of five rooftop packaged DX units, constant
and variable air volume boxes. Each
Operating Room is served by a dedicated rooftop air-conditioning unit.
C403.2.6 Energy
recovery ventilation systems. Where the supply airflow rate of a fan
system exceeds the values specified in Table C403.2.6, the system shall include
an energy recovery system. The energy recovery system shall have the capability
to provide a change in the
enthalpy of the
outdoor air supply of not less than 50 percent of the difference between the
outdoor air and return air enthalpies, at design conditions. Where an air
economizer is required, the energy recovery system shall include a bypass or
controls which permit operation of the economizer as required by Section C403.4.
Exception: An energy
recovery ventilation system shall not be required in any of the following
conditions:
1. Where energy
recovery systems are prohibited by the Florida Building Code, Mechanical.
2. Laboratory
fume hood systems that include at least one of the following features:
2.1.
Variable-air-volume hood exhaust and room supply systems capable of reducing
exhaust and
makeup air volume to 50 percent or less of design values.
2.2. Direct
makeup (auxiliary) air supply equal to at least 75 percent of the exhaust
rate, heated no
warmer than 2°F (1.1°C) above room setpoint, cooled to no cooler
than 3°F (1.7°C)
below room set point, no humidification added, and no simultaneous
heating and
cooling used for dehumidification control.
3. Systems
serving spaces that are heated to less than 60°F (15.5°C) and are not cooled.
4. Where more
than 60 percent of the outdoor heating energy is provided from site-recovered
or site solar energy.
5. Heating
energy recovery in Climate Zones 1 and 2.
6. Cooling
energy recovery in Climate Zones 3C, 4C, 5B, 5C, 6B, 7 and 8.
7. Systems
requiring dehumidification that employ energy recovery in series with the
cooling coil.
8. Where the
largest source of air exhausted at a single location at the building exterior
is less than 75 percent of the design outdoor air flow rate.
9. Systems
expected to operate less than 20 hours per week at the outdoor air percentage
covered
by Table
C403.2.6.
Question:
if an air handling unit is provided with a wraparound heat pipe coil, is
it acceptable to not provide an Energy Recovery Ventilation System per
paragraph C403.2.6.7?
Answer:
No. Wraparound heat pipe coil
does not fall within the scope of exception C403.2.6.7 of the 5th
Edition (2014) FBC, Energy Conservation.
Project: Newsome High School Classroom Building
Addition
A new
16-classroom building will be added to an existing high school. The new air-conditioning system will consist
of a new air-cooled chiller and two variable air volume chilled water air
handlers and new general exhaust fans.
Project: Lake
Gibson School HVAC Upgrade High
Complete
replacement of the air-conditioning system in an existing high school. The new system consists of new air –cooled
chiller and two variable air volume chilled water air handlers and new general
exhaust fans.
C403.2.6 Energy
recovery ventilation systems. Where the supply airflow rate of a fan
system exceeds the values specified in Table C403.2.6, the system shall include
an energy recovery system. The energy recovery system shall have the capability
to provide a change in the
enthalpy of the
outdoor air supply of not less than 50 percent of the difference between the
outdoor air and return air enthalpies, at design conditions. Where an air
economizer is required, the energy recovery system shall include a bypass or
controls which permit operation of the economizer as required by Section C403.4.
Exception: An energy
recovery ventilation system shall not be required in any of the following
conditions:
1. Where energy
recovery systems are prohibited by the Florida Building Code, Mechanical.
2. Laboratory
fume hood systems that include at least one of the following features:
2.1.
Variable-air-volume hood exhaust and room supply systems capable of reducing
exhaust and
makeup air volume to 50 percent or less of design values.
2.2. Direct
makeup (auxiliary) air supply equal to at least 75 percent of the exhaust
rate, heated no
warmer than 2°F (1.1°C) above room setpoint, cooled to no cooler
than 3°F (1.7°C)
below room set point, no humidification added, and no simultaneous
heating and
cooling used for dehumidification control.
3. Systems
serving spaces that are heated to less than 60°F (15.5°C) and are not cooled.
4. Where more
than 60 percent of the outdoor heating energy is provided from site-recovered
or site solar energy.
5. Heating
energy recovery in Climate Zones 1 and 2.
6. Cooling
energy recovery in Climate Zones 3C, 4C, 5B, 5C, 6B, 7 and 8.
7. Systems requiring
dehumidification that employ energy recovery in series with the cooling coil.
8. Where the
largest source of air exhausted at a single location at the building exterior
is less than 75 percent of the design outdoor air flow rate.
9. Systems
expected to operate less than 20 hours per week at the outdoor air percentage
covered
by Table
C403.2.6.
Question: Is paragraph C403.2.6.8 applicable only
to projects in existing buildings or new buildings as well?
Answer: Paragraph C403.2.6.8 applies to both
projects as applicable.