Staff
Analysis for Declaratory Statement Request
DS2016-048
Issue: Petitioner
seeks a Declaratory Statement on an interpretation of Exception 1 of Section
1609.1.2. In relation to a product applying for Product Approval under Rule
61G20-3.
Question:
Would an opening
protection system that is tested and analyzed for load resistance, is
non-porous in accordance with ASTM E1996, has been tested for cycling and is
used in accordance with aforesaid limits of use a. through k. be within the
exemption requirements of Section 1609.1.2 Protection of openings and not
require to be tested to an impact test?
Background:
The
Petitioner, Ted Berman of Ted Berman and Associates LLC is seeking a Florida
product approval “FL 1979” for their Plysnap hurricane protection system to be used for
protection of openings. The system
consists of 7/16” wood panels attached to a structure with screws that support
a wedge that keep the wood panels in position.
The system would enclose the opening to be protected and is considered a
non-porous system in accordance with ASTM E1996. The Plysnap hurricane protection system has
been tested in accordance with TAS 202 (load test) and TAS 203 (cyclic test). The petitioner is a consulting engineering
firm working for a client firm of Eye Protection 2, LLC, located at 339
Spectrum Rd, Summerville SC 29486. This
client is seeking approval for their plysnap
hurricane protection system to be used for protection of openings.
The
product approval is being applied for with the following limits of use:
a) Minimum
thickness of wood panels 7/16 inch.
b) Maximum
Panel span 8 feet.
c) Permitted
use in one and two story buildings classified as Group R-3 or R4 occupancy.
d) Panels
shall be precut so that they shall be attached to the framing surrounding the opening
containing the product.
e) Panels
shall be predrilled as required for the anchorage method.
f) Panels
shall be secured with the attachment hardware provided.
g) Attachments
shall be designed to resist the components and cladding loads determined in
accordance with the provisions of ASCE 7
h) Anchors
shall be corrosion resistant permanently installed on the building.
i)
Buildings shall have a mean roof height
of 45 feet or less.
j)
Wind velocity shall be less than 140
mph.
k) Not be
used on essential facilities.
The petitioner
would like to know if an opening protection system that is test and analyzed
for load resistance, is non-porous in accordance with ASTM 1996, has been
tested for cycling, and used in accordance with the aforesaid limits of above,
would be within the exemption requirements of Florida Building Code, Building, Section
1609.1.2, Exception 4, Protection of openings and not required to be tested to
an impact test. Petitioner respectfully believes
that the answer is yes.
-----
REFERENCES:
5th Edition (2014) Florida Building
Code, Building
Chapter 16
Section 1609.1.2
1609.1.2 Protection of openings. In wind-borne debris regions, glazed openings in
buildings shall be impact
resistant or protected
with an impact-resistant covering meeting the requirements of SSTD 12,
ANSI/DASMA 115 (for
garage doors and rolling doors) or TAS 201, 202 and 203, AAMA 506. ASTM E 1996
and ASTM E 1886 referenced herein, or an approved impact-resistant standard as
follows:
1. Glazed openings
located within 30 feet (9144 mm) of grade shall meet the requirements of the
large missile test of
ASTM E 1996.
2. Glazed openings
located more than 30 feet (9144 mm) above grade shall meet the provisions of
the
small missile test of
ASTM E 1996.
3. Storage sheds that are
not designed for human habitation and that have a floor area of 720
square feet (67 m2) or
less are not required to comply with the mandatory windborne debris impact
standards of this code.
4. Openings in sunrooms,
balconies or enclosed porches constructed under existing roofs or decks
are not required to be
protected provided the spaces are separated from the building interior by a
wall and all openings in
the separating wall are protected in accordance with Section 1609.1.2
above. Such spaces shall
be permitted to be designed as either partially enclosed or enclosed
structures.
Exceptions:
1. Wood structural panels
with a minimum thickness of 7/16 inch (11.1 mm) and maximum panel
span of 8 feet (2438 mm)
shall be permitted for opening protection in one- and two-story build-
ings classified as Group R-3 or R-4 occupancy. Panels
shall be precut so that they shall be
attached to the framing
surrounding the opening containing the product with the glazed opening.
Panels shall be
predrilled as required for the anchorage method and shall be secured with the
attachment hardware
provided. Attachments shall be designed to resist the components and cladding
loads determined in
accordance with the provisions of ASCE 7, with corrosion-resistant attachment
hardware provided and
anchors permanently installed on the building. Attachment in accordance
with Table 1609.1.2 with
corrosion-resistant attachment hardware provided and anchors permanently installed on the building is permitted for buildings with a mean roof height of 45 feet (13 716 mm) or less where Vasd deter-
mined in accordance with Section 1609.3.1 does
not exceed
140 mph (63 m/s).
2. Glazing in Risk Category I buildings as defined in Section
1604.5, including greenhouses that
are occupied for growing plants on a production or
research basis, without public access shall be per-
mitted to be unprotected.
3. Glazing in Risk Category II, III or IV buildings
located over 60 feet (18 288 mm)
above
the
ground
and over 30 feet
(9144 mm) above aggregate surface roofs located within 1,500 feet (458m) of the building shall be permitted to be unprotected.
TABLE 1609.1.2
WIND-BORNE DEBRIS PROTECTION FASTENING SCHEDULE FOR WOOD STRUCTURAL PANELSa, b, c, d
FASTENER TYPE |
FASTENER SPACING (inches) |
||
Panel Span ≤ 4 feet |
4 feet < Panel Span ≤ 6 feet |
6 feet < Panel Span ≤ 8 feet |
|
No. 8 wood-screw- based anchor with 2- inch embedment length |
16 |
10 |
8 |
No. 10 wood-screw- based anchor with 2- inch embedment length |
16 |
12 |
9 |
1/4 -inch diameter lag-screw-based anchor with 2-inch embedment length |
16 |
16 |
16 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.448 N, 1 mile per hour = 0.447 m/s.
a) This table is based on a Vasd determined in accordance with Section 1609.3.1, of 140 mph and a 45-foot mean roof height.
b) Fasteners shall be installed at opposing ends of the wood structural panel. Fasteners shall be located a minimum of 1 inch from the edge of the panel.
c) Anchors shall penetrate through the exterior wall covering with an embedment length of 2 inches minimum into the building frame. Fasteners shall be located a minimum of 21/ inches from the edge of concrete block or concrete.
d) Where panels are attached to masonry or masonry/stucco, they shall be attached using vibration-resistant anchors having a minimum ultimate withdrawal capacity of 1,500 pounds.
1609.1.2.4
Impact-resistant coverings.
1609.1.2.4.1
Impact-resistant coverings shall be tested at 1.5 times the design pressure
(positive or negative) expressed in pounds per square feet as determined by Section
1609 or ASCE 7, for which the specimen is to be tested. The design pressures,
as determined from ASCE 7, are permitted to be multiplied by 0.6.
1609.1.2.4.2 Impact-resistant coverings.
Impact resistant coverings shall be labeled in accordance with the provisions
of Section 1710.8.
Current approval with similar scope to the
application in question:
Product as approved
affirms compliance with ASTM E 1886 and SSTD 12.
5th
Edition (2014) Florida Building Code, Building
CHAPTER 1 SCOPE
AND ADMINISTRATION
[A] 104.11
Alternative materials, design and methods of
construction and
equipment. The
provisions of this code
are not intended
to prevent the installation of any material or
to prohibit any
design or method of construction not specifically
prescribed by
this code, provided that any such alternative
has been approved.
An alternative material, design or
method of
construction shall be approved where the building
official finds that the
proposed design is satisfactory and
complies with
the intent of the provisions of this code, and
that the
material, method or work offered is, for the purpose
intended, at
least the equivalent of that prescribed in this code
in quality,
strength, effectiveness, fire resistance, durability
and
safety.
Staff anslysis:
Question: Would an opening protection system that is tested and analyzed for load
resistance, is non-porous in accordance with ASTM E1996, has been tested for
cycling and is used in accordance with aforesaid limits of use a. through k. be
within the exemption requirements of Section 1609,1,2 Protection of openings
and not require to be tested to an impact test?
Answer:
Option #1/Petitioner: Petitioner respectfully believes that the answer is yes. Section 1609.1.2 Protection of Opening is clear in requiring the impact testes on numerals 1 and 2, but the Exemption is added and the Plysnap hurricane protection system when tested and analyzed for loads, subject to a cycle test, and non-porous in accordance with ASTM E1996 and limit its use in accordance with the aforesaid limit a through k complies with the exemption requirements of Section 1609.1.2. Therefore the product has complied with all the requirements of the Florida Building Code, 5th Edition (2014) and a Florida product approval may be granted.
Option
#2/Staff: The
product in question is a proposed alternative to the Wood Structural Panels
(prescriptive specification method for protection of opening) as specified in
Section 1609.1.2, Exception, of the 5th Edition (2014) Florida
Building Code “FBC”, Building. As per
Section 104.11 of the Florida Building Code, Building, an alternative method of
construction to that prescribed in the FBC is subject to review and approval by
the local building official, when such alternative is substantiated to
be equivalent of that prescribed in the FBC in quality, strength,
effectiveness, durability and safety.
Therefore, the Florida Building Commission has no authority to approve
said alternate as part of the State Product Approval Program.
Option #3/Staff: The answer is No. The product in question must also demonstrate compliance with the appropriate impact resistance standard(s) as required by Section 1609.1.2.