Issue DS 2018-043: The petitioner Allen R. Finfrock of Finfrock DMC is seeking a declaratory statement on if the fire barrier of a floor and ceiling assembly is the ceiling, would the continuity of a fire barrier be maintained if the barrier stops at the ceiling and the joint is sealed in accordance with Section 707.8?
Background:
Finfrock is a
design/build/manufacturer who has patented a precast concrete floor and ceiling
assembly called the "Dual Deck" that consists of two layers of
concrete separated by a steel truss system. This system has a UL listing for a two-hour
fire rating. The bottom (ceiling) slab is the fire barrier and the top (floor)
slab creates the interstitial space. Finfrock is seeking clarification on the
2017 Florida Building Code, Section 707, Fire Barriers, and Section 707.5,
Continuity, to insure that the interpretation between various jurisdictions is
consistent with the intent of the code and is consistent with the corresponding
section in the Florida Fire Prevention Code, Section 8.3 (code excerpt below).
In the past, different jurisdictions have had varying interpretations as to the
intent of the code as it applies to a floor and ceiling assembly.
Finfrock is
designing a nine story multifamily building for the Orlando area. This project will be constructed using
precast concrete products which will include exterior walls, shear walls,
supporting walls for double tees (garage area) and dualDecks (floor and ceiling
assembly). The building will have an
interior stair well with a corridor leading to the exterior. The code requires
that this corridor be considered as an extension of the 2-hour rated stairway
exit. As such, it is considered and “exist passageway” which is required to be
constructed with “fire barrier” in lieu of a “fire partition”. Fire barrier walls have the “continuity”
requirements per FBC Section 707.5. The
corridor will have a precast concrete Dual Deck as it’s’ ceiling. Drawings are attached for clarification.
2017 Florida Building
Code 6th Edition
[A]101.4.5 Fire prevention.
For provisions related to fire
prevention, refer to the Florida Fire Prevention Code. The Florida
Fire Prevention Code shall apply to matters affecting or relating to
structures, processes and premises from the hazard of fire and explosion
arising from the storage, handling or use of structures, materials or devices;
from conditions hazardous to life, property or public welfare in the occupancy
of structures or premises; and from the construction, extension, repair, alteration or
removal of fire suppression, and alarm systems or fire hazards in the structure
or on the premises from occupancy or operation.
707.5
Continuity.
Fire barriers shall extend from the top of the
foundation or floor/ceiling assembly below to the underside of the floor or
roof sheathing, slab or deck above and shall be securely attached thereto.
Such fire barriers shall be continuous through concealed
space, such as the space above a suspended ceiling. Joints and voids at intersections
shall comply with Sections 707.8 and 707.9
Exceptions:
1.
Shaft
enclosures shall be permitted to terminate at a top enclosure complying
with Section 713.12.
2.
Interior
exit stairway and ramp enclosures
required by Section 1023 and exit access stairway and ramp enclosures
required by Section 1019 shall be permitted to terminate at a top
enclosure complying with Section 713.12.
707.8 Joints.
Joints made in or between fire
barriers, and joints made at the intersection of fire barriers with
underside of a fire-resistance-rated floor or roof sheathing, slab or deck
above, and the exterior vertical wall intersection shall comply
with Section 715.
715.1 General.
Joints installed in or between
fire-resistance-rated walls, floor or floor/ceiling assemblies and roofs or
roof/ceiling assemblies shall be protected by an approved fire-resistant
joint system designed to resist the passage of fire for a time period
not less than the required fire-resistance rating of the wall,
floor or roof in or between which the system is installed. Fire-resistant
joint systems shall be tested in accordance with Section 715.3.
2018 Florida Fire Prevention Code 6th Edition
Section 8.3 - Fire Barriers
8.3.1.2(2) - The fire
barriers are continuous from outside wall to outside wall or from one fire
barrier to another, and from the floor to the bottom of the interstitial space,
provided that the construction assembly forming the bottom of the interstitial
space has a fire resistance rating not less than that of the fire barrier.
Staff Analysis:
Question : If
the fire barrier of a floor and ceiling assembly is the ceiling, would the
continuity of a fire barrier be maintained if the barrier stops at the ceiling
and the joint is sealed in accordance with Section 707.8?
Answer: The application
of the product in question “a precast concrete floor and ceiling assemble (DualDeck)”
is a proposed alternative to the prescribed fire barrier continuity provisions
of Sections 707.5 of the 6th Edition (2017) Florida Building Code
“FBC”, Building. As per Sections 104.11 of the 6th Edition (2017) Florida
Building Code, Building, an alternative method of construction to that
prescribed in the FBC is subject to review and approval by the local building
official, when such alternative is substantiated to be equivalent of that
prescribed in the FBC in quality, strength, effectiveness, durability and
safety.