Rana,

 

We appreciate the chance to respond to the complaint about Pocahontas Aluminum FL 12903-R1 and the use of incorrect installation drawings.  First, Keystone Certifications does not inspect installation drawings to determine their origin.  We assume the manufacturer has generated the drawings themselves or has the required permission to use the drawings submitted.  In this case, we believed Pocahontas to have generated the drawings themselves.

 

The response to the accuracy of the drawings is two-fold.  First, the drawing does show the wrong dimensions between the hinges.  We are going to work with Pocahontas on changing the drawings, revising the application and getting that done prior to the next deadline.  Second, since the beginning of the certification in 2010, our inspections of this product at Pocahontas Aluminum’s manufacturing facility show no non-conformities with the door.  Therefore, the doors installed in the field are being manufactured in compliance with the certification authorization and test report description.

 

Please let us know if you need any further information from us.

 

Thank you.

 

Steven M. Urich, PE

Building Envelope Program Manager

Keystone Certifications, Inc.