5th
Edition (2014) Florida Building Code Residential
CHAPTER 42 SWIMMING POOLS [ELECTRICAL PROVISIONS]
E4201.2
Definitions.
LOW VOLTAGE
CONTACT LIMIT. A
voltage not
exceeding the
following values:
1. 15 volts
(RMS) for sinusoidal AC
2. 21.2 volts
peak for nonsinusoidal AC
3. 30 volts for
continuous DC
4. 12.4 volts
peak for DC that is interrupted at a rate of 10
to 200 Hz
NO-NICHE
LUMINAIRE. A
luminaire intended for installation above or below the water without a niche.
DRY-NICHE
LUMINAIRE. A
luminaire intended for installation in the floor or wall of a pool, spa or
fountain in a niche that is sealed against the entry of water.
WET-NICHE
LUMINAIRE. A
luminaire intended for installation in a forming shell mounted in a pool or
fountain structure where the luminaire will be completely surrounded by water.
THROUGH-WALL
LIGHTING ASSEMBLY. A
lighting assembly intended for installation above grade, on or through the wall
of a pool, consisting of two interconnected groups of
components
separated by the pool wall.
E4205.2
Luminaires and related equipment. Other than listed low-voltage luminaires
not requiring grounding, all through-wall lighting assemblies, wet-niche,
dry-niche, or no-niche luminaires shall be connected to an insulated copper equipment
grounding conductor sized in accordance with Table E3908.12 but not smaller
than 12 AWG. The equipment grounding conductor between the wiring chamber of
the secondary winding of a transformer and a junction box shall be sized in
accordance with the overcurrent device in such circuit. The junction box,
transformer enclosure, or other enclosure in the supply circuit to a wet-niche
or no-niche
luminaire and
the field-wiring chamber of a dry-niche luminaire shall be grounded to the
equipment grounding terminal of the panelboard. The
equipment grounding terminal shall be
directly
connected to the panelboard enclosure. The equipment grounding
conductor shall be installed without joint or splice.
Exceptions:
1. Where more
than one underwater luminaire is supplied by the same branch circuit, the
equipment grounding conductor, installed between the junction boxes,
transformer enclosures, or other enclosures in the supply circuit to wet-niche
luminaires, or between the field-wiring compartments of dry-niche luminaires,
shall be permitted to be terminated on grounding terminals.
2. Where an
underwater luminaire is supplied from a transformer, ground-fault
circuit-interrupter, clockoperated switch, or a
manual snap switch that is located between the panelboard
and a junction box connected to the conduit that extends directly to the underwater
luminaire, the equipment grounding conductor shall be permitted to terminate on
grounding terminals on the transformer, ground-fault circuit- interrupter,
clock-operated switch enclosure, or
an outlet box
used to enclose a snap switch.
E4206.4
Underwater luminaires. The design of an underwater luminaire supplied from
a branch circuit either directly or by way of a transformer or power supply
meeting the
requirements of
Section E4206.1, shall be such that, where the fixture is properly installed
without a ground-fault circuitinterrupter, there is
no shock hazard with any likely combination
of fault
conditions during normal use (not relamping). In addition,
a ground-fault circuit-interrupter shall be installed in the branch circuit
supplying luminaires operating at more
than the
low-voltage contact limit, such that there is no shock hazard during relamping. The installation of the ground-fault circuit-interrupter
shall be such that there is no shock hazard
with any likely
fault-condition combination that involves a person in a conductive path from
any ungrounded part of the branch circuit or the luminaire to ground.
Compliance with this requirement shall be obtained by the use of a listed underwater
luminaire and by installation of a listed groundfault
circuit-interrupter in the branch circuit or a listed transformer or power
supply for luminaires operating at more than the low-voltage contact limit.
Luminaires that depend on submersion for safe operation shall be inherently
protected against the hazards of overheating when not submerged.
E4206.4.1
Maximum voltage. Luminaires
shall not be installed for operation on supply circuits over 150 volts between
conductors.
E4206.4.2
Luminaire location. Luminaires
mounted in walls shall be installed with the top of the fixture lens not less
than 18 inches (457 mm) below the normal water level of the pool, except where
the luminaire is listed and identified for use at a depth of not less than 4
inches (102 mm) below the normal water level of the pool. A luminaire facing
upward shall have the lens adequately guarded to prevent contact by any person
or shall be listed for use without a guard.
E4206.5
Wet-niche luminaires. Forming shells shall be installed for the mounting
of all wet-niche underwater luminaires and shall be equipped with provisions
for conduit entries. Conduit shall extend from the forming shell to a suitable junction
box or other enclosure located as provided in Section E4206.9. Metal parts of
the luminaire and forming shell in contact with the pool water shall be of
brass or other approved corrosion-resistant metal.
The end of
flexible-cord jackets and flexible-cord conductor terminations within a
luminaire shall be covered with, or encapsulated in, a suitable potting
compound to prevent the entry of water into the luminaire through the cord or
its conductors. If present, the
grounding connection within a luminaire shall be similarly treated to protect
such connection from the deteriorating effect of pool water in the event of water
entry into the luminaire. Luminaires
shall be bonded to and secured to the forming shell by a positive locking
device that ensures a low-resistance
contact and
requires a tool to remove the luminaire from the forming shell.
E4206.5.1
Servicing. All
wet-niche luminaires shall be removable from the water for inspection, relamping, or other maintenance. The forming shell location
and length of cord in the forming shell shall permit personnel to place the
removed luminaire on the deck or other dry location
for such
maintenance. The luminaire maintenance location shall be accessible without
entering or going into the pool water.
E4206.6
Dry-niche luminaires. Dry-niche luminaires shall have provisions for
drainage of water. Other than listed low voltage luminaires not requiring
grounding, a dry-niche luminaire
shall have means
for accommodating one equipment grounding conductor for each conduit entry.
Junction boxes shall not be required but, if used, shall not be required to be elevated
or located as specified in Section E4206.9 if the luminaire is specifically
identified for the purpose.
E4206.7 No-niche
luminaires. No-niche
luminaires shall be listed for the purpose and shall be installed in accordance
with the requirements of Section E4206.5. Where connection to a forming shell is specified, the connection shall be to the
mounting bracket.