FLORIDA
BUILDING COMMISSION
ELECTRICAL
TECHNICAL ADVISORY COMMITTEE
MINUTES
MONDAY, DECEMBER 7, 2015
2:00 P.M.-2:40 P.M.
TELECONFERENCE MEETING FROM TALLAHASSEE,
FLORIDA
|
|
TAC/POC
MEMBERS AND OBJECTIVES |
ELECTRICAL TAC MEMBERS Present: Kevin Flanagan - Chair,
Joseph Territo, David Rice, Clarence Tibbs, Oriol Haage,
Dwight Wilkes, Ken Castronovo, Neal Burdick, Shane Gerwig |
|
MEETING
AGENDA |
|
OBJECTIVE |
REVIEW OF OBJECTIVES
WILL INCLUDE THE FOLLOWING: Description of issue, discussion by TAC, public
comment, TAC action |
1) |
2:00 PM - Welcome and Opening,
Roll Call Reviewed and Approved
of December 7, 2015 Meeting Agenda Reviewed and Approved of October 14, 2015
Meeting Minutes |
2) |
The
committee considered, discussed and provided recommendations to the
Commission on the following declaratory statement: DS2015-125 by Gary
R. Beaumont of Beaumont Electric Co. Staff Analysis Question: Can electrical engineers design commercial construction projects
to allow feeders to have more than a 2% voltage drop, as long as the feeders
and branch circuits combined shall be sized for a maximum of 5% voltage drop
to meet the intent of FBC – Energy Conservation – 2014 – C405.7.4” Answer: No. As per Section C405.7.3.1 of the 5th Edition
(2014) FBC, Energy Conservation, feeder and customer owned service conductor
must be sized for a maximum voltage drop of 2 percent at design load. |
3) |
TAC and
Public Comment |
4) |
Adjourned
at 2:40 |
STAFF CONTACTS: Joe Bigelow – Planning Analyst joe.bigelow@myfloridalicense.com
(850) 717-1829 or Mo Madani,
Manager mo.madani@myfloridalicense.com
Teleconference Process and Etiquette
URL:
Note: This document is available to any person requiring materials in alternate format upon request. Contact the Department of Business and Professional Regulation, Suite 90, 1940 N. Monroe, Tallahassee, Florida 32399 or call 850-487-1824.