Florida
Building Commission
CODE ADMINISTRATION
Technical Advisory Committee Meeting
MINUTES
December 7, 2015 at 10:00 A.M.
Meeting was held
via teleconference/webinar:
https://global.gotomeeting.com/join/968410349
Teleconference: 1-866-899-4679 Access Code: 968-410-349
public point of
access: Department of Business and Professional Regulation
Northwood Centre,
Suite 90A, 1940 North Monroe Street, Tallahassee, FL 32399
(850) 487-1824
TAC Objectives |
Code Administration TAC Members
Present: Bob Boyer, Dick Browdy, Don Brown, David Gilson, Richard
Goff, John O’Connor. Code Administration TAC Members
Absent: Chairman: Jay Carlson; Hamid Bahadori, Bill
Dumbaugh Staff Present: Mo
Madani, April Hammonds, Nick Duval, Jim Hammers, Marlita Peters Guests Present:
Joe Hetzel, Jeff Sunie, Jaime Gascon, Joe Belcher, Brad Schiffer |
Objective – To consider, discuss
and provide recommendations for consideration by the Commission on requests
for Declaratory Statement. |
|
|
|
|
1) |
Welcome and Opening Remarks. Meeting began at
10:12am once quorum was established.
Chairman Carlson was excused prior to meeting for a medical emergency. |
2) |
Roll Call: Roll was taken and a quorum was present. |
3) |
Review and Approval
of today’s Meeting Agenda: Motion was entered by
Bob Boyer to accept the altered Agenda with the removal of item 5 due to withdrawal of request for
declaratory statement – DS2015-112 by David Galassi of Marion County Building
Safety Department, was seconded by John O’Connor. Unanimous vote of approval. |
4) |
Review and Approval
of Meeting Minutes of October 5, 2015 Motion
by Bob Boyer, seconded by John O’Connor, to accept the previous minutes of
October 5, 2015 as posted. Unanimous
vote of approval. |
5) |
WITHDRAWN : DS 2015-112 by David Galassi of
Marion County Building Safety Department
Staff analysis |
6) |
To consider and discuss the
following Declaratory Statement request: DS2015-134 by Joseph Hetzel of
Door & Access Systems Manufacturers Association International
(DASMA) Mr.
Joe Hetzel provided a brief overview of his request for declaratory statement
regarding air leakage requirements related to high speed doors. Mr. Mo Madani provided the staff analysis
stating: Question 1) Can the maximum air leakage rate requirement for
high speed doors as shown in Table C402.5.2 of the 2015 IECC be used for the
high speed door to be installed in the facility in question, to meet the
intent of the Florida Energy Code Fifth Edition based on technical
justification? Our understanding is that the answer is Yes,
provided that the authority having jurisdiction approves the use of the Table
per the "alternate method" allowance in the Code Answer/Staff: The answer is yes, provided that the
authority having jurisdiction approves the use of Table C402.5.2 of the 2015
IECC for the high speed door in question in accordance with Section C102,
Alternate Material –Method of Construction, Design or instillation System, of
the 5th Edition (2014) FBC, Energy Conservation. Question 2) Is the
Florida Energy Code Fifth Edition Section C102, "Alternate Materials -
Methods of Construction, Design or Insulating Systems", applicable
toward use of the Table described in Question #1? Our
understanding is the answer is Yes, provided that the authority having
jurisdiction finds the Table referenced in Question #1 to be itself
applicable to the door in question. Answer: Please see answer
to question 1. Motion
was provided by Dick Browdy and seconded by Bob Boyer to accept the staff
analysis as presented. Unanimous vote
of approval. |
7) |
Public
Comment – Joe Hetzel thanked staff for their work. |
8) |
Member Comment – None provided. |
9) |
Scheduling of next
meeting to be determined based on need. – To be determined. |
10) |
Stand Adjourned: Time: 10:26am |
|
|
Staff
Contacts: Marlita
Peters, Marlita.peters@myfloridalicense.com,; Mo Madani, mo.madani@myfloridalicense.com
Note: This document is available to any person
requiring materials in alternate format upon request. Contact the Department of Business and
Professional Regulation, Office of Codes and Standards, 1940 N. Monroe Street,
Suite 90, Tallahassee, Florida 32399-0772 or call 850-487-1824.