Florida Building Commission
December 15, 2015
Legal Report
Hilton
University of Florida Conference Center
1714
SW 34th Street
Gainesville,
Florida
CODE ADMIN. and
ENERGY TECHNICAL ADVISORY COMMITTEE
(TAC)
DS2014-134 by Joseph
Hetzel of Door & Access Systems manufacturers Association International
(DASMA)
Question 1:
Can the maximum air leakage rate
requirement for high speed doors as shown in Table C402.5.2 of the 2015 IECC be
used for the high speed door to be installed in the facility in question, to
meet the intent of the Florida Energy Code Fifth Edition based on technical
justification? Our understanding is that the answer is Yes,
provided that the authority having jurisdiction approves the use of the Table
per the "alternate method" allowance in the Code
Answer:
The answer is yes, provided that the authority
having jurisdiction approves the use of Table C402.5.2 of the 2015 IECC for the
high speed door in question in accordance with Section C102, Alternate Material
–Method of Construction, Design or instillation System, of the 5th Edition
(2014) FBC, Energy Conservation.
Question 2:
Is the
Florida Energy Code Fifth Edition Section C102, "Alternate Materials -
Methods of Construction, Design or Insulating Systems", applicable toward
use of the Table described in Question #1? Our understanding is the
answer is Yes, provided that the authority having jurisdiction finds the
Table referenced in Question #1 to be itself applicable to the door in
question.
Answer: Please see answer to question 1.
ELECTRICAL and ENERGY TECHNICAL
ADVISORY COMMITTEE (TAC)
DS2015-125 by Gary R.
Beaumont of Beaumont Electric Co.
Question:
Can electrical
engineers design commercial construction projects to allow feeders to have more
than a 2% voltage drop, as long as the feeders and branch circuits combined
shall be sized for a maximum of 5% voltage drop to meet the intent of FBC –
Energy Conservation – 2014 – C405.7.4”
Answer:
No. As
per Section C405.7.3.1 of the 5th Edition (2014) FBC, Energy
Conservation, feeder and customer owned service conductor must be sized for a
maximum voltage drop of 2 percent at design load.
FIRE TECHNICAL ADVISORY COMMITTEE (TAC)
DS2015-113 by David
Galassi of Marion County Building Safety Department
Question:
Using table 508.4, does
installing a 2 hour separation between the “U” use and the
“R” use eliminate the requirement of sprinkling for the Residential
use per FBC 903.2.8?
Answer:
No. As per Sections 420.4 and 903.2.8 of the 5th Edition
(2014) FBC, Building, an automatic sprinkler system is required to be provided
throughout the building in question.
MECHANICAL TECHNICAL ADVISORY COMMITTEE (TAC)
DS2015-136 by Julien
Croteau, Condo unit owner
Denied.
This is due to the facts that the issue in question is pertaining to
“past conduct of another” and that the Florida Building Commission has no
authority to address declaratory statements regarding prior editions of the
Florida Building Code.
ROOFING TECHNICAL ADVISORY COMMITTEE
(TAC)
DS2015-109 by Robin
Davies of Bracken Engineering
Question:
Does the repair
of roof coverings performed in accordance with Chapter 6 of the 5th Edition
(2014) Florida Building Code, Existing Building need to comply with the
requirements of Section 708 Reroofing?
Answer:
No, as per Section
606.2.1 of the 5th Edition (2014) FBC, Existing Building “the
Code), the project in question is permitted to be restored to
its predamage condition without meeting the requirements of Section
708.1.1 of the Code. Building materials to be used in the
restoration of the project in question must be in accordance with Section 602.2
of Code.
DS2015-135 by Robin
Davies of Bracken Engineering
Question:
Does the repair of
roof coverings performed in accordance with Chapter 6 of the 5th Edition (2014)
Florida Building Code, Existing Building need to comply with the requirements
of Section 708 Reroofing?
Answer:
No, as per Section
606.2.1 of the 5th Edition (2014) FBC, Existing Building “the Code), the
project in question is permitted to be restored to
its predamage condition without meeting the requirements of Section
708.1.1 of the Code. Building materials to be used in the
restoration of the project in question must be in accordance with Section 602.2
of Code.