(E6460 AS)
Chapter
27 – Electrical Systems
Option #1: No change – keep as is
Section 2703 Lightning
Protection
2703.1 Lightning
Protection. A lightning protection
system shall be provided for all new buildings and additions in accordance with
NFPA 780, Standard for the Installation of Lightning Protection Systems.
2703.2 Where additions are constructed to existing
building, the existing building’s lightning protection system, if connected to
the new lightning protection system, shall be inspected and brought into
compliance with current standards.
2703.3 Surge protection devices shall be installed for
all normal and emergency electrical systems in accordance with NFPA 70, National
Electrical Code.
Exceptions:
1. One- and two-family
dwellings
2. Lightning protection shall not be required
for any building or addition where shown unnecessary by evaluation using the Risk
Assessment Guide in NFPA 780, Standard for the Installation of Lightning
Protection Systems or an alternative method approved by the authority
having jurisdiction.
Option #2: Revise as
follows:
Section 2703 Lightning
Protection 2703.1 Lightning
Protection. A lightning
protection system shall be provided for all new buildings and additions in
accordance with NFPA 780, Standard for the Installation of Lightning
Protection Systems, UL
96A, Installation Requirements for Lightning Requirement, HBP-21 or
other alternative equivalent standard for the installation of lightning protection systems. 2703.2 Where additions are constructed to existing
building, the existing building’s lightning protection system, if connected
to the new lightning protection system, shall be inspected and brought into
compliance with current standards. 2703.3 Surge protection devices shall be installed
for all normal and emergency electrical systems in accordance with NFPA 70, National
Electrical Code. Exceptions: 1. One- and two-family
dwellings 2. Lightning
protection shall not be required for any building or addition where shown
unnecessary by evaluation using the Risk Assessment Guide in NFPA 780,
Standard for the Installation of Lightning Protection Systems or an
alternative method approved by the authority having jurisdiction. |
Option #3: Delete Section 2703 as follows:
Section 2703 Lightning Protection.
|