ENERGY
CODE REPORT FOR
EXISTING
BUILDING REPLACEMENT SYSTEMS
SUBJECT |
RENOVATION3/ALTERATION |
BUILDING SYSTEMS1,2,3 |
|
HVAC equipment replacement |
|
Duct sealing |
Residential:
At the time of total replacement of HVAC evaporators and condensing units, all accessible (min. 30” clearance) joints and seams in the air distribution system shall be inspected and sealed where needed; certified by contractor.
Commercial/Residential: This provision does not apply to partial replacement of equipment (i.e. where the air distribution system is not independent to the partial replacement of equipment). An HVAC “system” includes all components connected by a joint air distribution system. |
Equipment sizing calculation |
An a/c contractor or licensed Florida PE shall submit a nationally recognized method based sizing calculation to the code official at the time of permit application for total replacement of the condensing and evaporator components of HVAC systems in accordance with Florida law and the provisions of Sec. 403.6.2.2 or 403.6.2.3. Residential: 1. Several “recognized” sizing calculation methods for existing buildings are available from HVAC equipment manufacturers and ACCA accredited software that are subject to approval by the code official. 2. Per Section 101.54 of the FBC-EB, original systems installed on buildings constructed under the 1993 Energy Code or later have already been sized for the building and, without changes to the building, may be assumed to have been sized per code. 3. If a copy of a previous sizing calculation is provided, it is deemed to meet code. Commercial/Residential: This provision does not apply to partial replacement of equipment (i.e. where the air distribution system is not independent to the partial replacement of equipment). An HVAC “system” includes all components connected by a joint air distribution system. |
Duct insulation levels |
Residential:
Section 403.2.1 requires ducts located in attics or on roofs to be insulated to a minimum of R-8. Tables 402.1.1 and 402.1.1.3 (Prescriptive method) require ducts to be R-6 and located in conditioned space. Section 405.2 (Performance method) requires all supply and return ducts not completely inside the building thermal envelope to be insulated to at least R-6. Ergo: R-8 isn’t a minimum code requirement. |
Matched indoor/outdoor units |
Matched systems may be verified by one of the following means.
|
Duct testing |
Residential Replacement or extension of an existing air distribution system is not required to be tested. |
RENOVATIONS1,5,7 |
|
Pool filtration pumps6 |
If cost of job exceeds 30% of assessed value of pool structure, meet Sec. 403.9.4 requirements If cost of job does not exceed 30% of assessed value of pool structure, does not have to meet Energy Code requirements. |
In general, Florida law trumps what’s in the code. Florida law has been incorporated into the FBC-Energy Conservation in Table 101.4.1.
Ducts & AHU
installed substantially leak free per Section 403.2.2.1. Test by Class 1 BERS
rater required.
Exception: Ducts
installed onto an existing air distribution system as part of an addition or
renovation; duct must be R-6 installed per Sec. 503.2.7.2