Deletion legend:
[1- Default – Not related to structural wind resistance design]
[2- Fire/Life Safety]
[3- Covered in model base code]
[4- Code Cycle Modification to be submitted to strike section and
refer to appropriate FBC,B sections]
SECTION
R4411
[4- Code Cycle Modification to be submitted to strike section and
refer to appropriate FBC,B sections]
HIGH-VELOCITY
HURRICANE ZONES — GYPSUM BOARD AND PLASTER
R4411.1 Lathing.
R4411.1.1 General.
Lath shall be gypsum, metal or wire lath, as set forth herein, and shall
conform to the Standard Specification for Interior Lathing and Furring , ANSI
A42.4.
R4411.1.2 Gypsum
lath. Gypsum lath shall conform to the Standard Specification for Gypsum Lath ,
ASTM C 37.
R4411.1.2.1 Gypsum
lath shall be nailed to wood supports, at intervals not to exceed 5 inches (127
mm), with 13-gauge galvanized or blued nails having 19/64 inch (7.5 mm)
diameter flat heads (7.5 mm). Nails shall be not less than 11/8 inches (29 mm)
long for 3/8 inch (9.5 mm) lath nor less than 11/4 inches (32 mm) for 1/2 inch
(12.7 mm) lath. Each 16-inch (406 mm) width of lath shall be secured to each
support with not less than five nails except that where fire-resistive-rated
construction is not required, there shall not be less than four nails.
R4411.1.2.2 Lath
shall be secured to horizontal or vertical metal supports by means of approved
special clips.
R4411.1.2.3 The
center-to-center spacing of wood supports shall not exceed 16 inches (406 mm)
for 3/8 inch (9.5 mm) gypsum lath and shall not exceed 24 inches (610 mm) for
1/2 inch (12.7 mm) gypsum lath.
R4411.1.2.4 The
center-to-center spacing for gypsum lath applied to metal studs shall not
exceed that set forth herein above for wood supports except that 3/8 inch (9.5
mm) gypsum lath may be applied to metal studs spaced 24 inches (610 mm) on
centers where a minimum of 3/4-inch (19 mm), three-coat plaster is applied over
the lath.
R4411.1.2.5 Lath
shall be applied with face side out and with the long dimension at right angles
to the framing members. Joints shall be broken in each course, except that end
joints may fall on one support when such joints are covered with 3-inch- wide
(76 mm) strips of metal lath. Lath shall be butted together.
R4411.1.2.6 Corner
bead and inside angle reinforcing shall not be required.
R4411.1.2.7 No
interior lath shall be applied until the roof is on and the building is dried
in.
R4411.1.3 Metal and
wire lath.
R4411.1.3.1 Metal and
wire lath and metal accessories embedded in the plaster shall be galvanized or
otherwise rust-resistant by approved means. Weight tags shall be left on all
metal or wire lath until approved by the building official.
R4411.1.3.2 The
weight of metal and wire lath and the spacing of supports shall conform to the
requirements set forth in Table R4411.1.3.2.
TABLE R4411.1.3.2
WEIGHTS OF METAL AND
WIRE LATH*
TYPE OF LATH MINIMUM WGT. (lb per sq yd) MAXIMUM SPACING OF SUPPORTS (in.)
For Walls For Ceilings
Flat Expanded Metal
Lath 2.5 16 0
Flat Expanded Metal Lath
3.4 16
16
Flat Rib Metal Lath 2.75 16
12
Flat Rib Metal Lath 3.4 19
19
3/8" Rib Metal
Lath 3.4 24 24
Sheet-Metal Lath 4.5 24
24
Wire Lath 2.48 16
12
Wire Fabric ** 16
16
For SI: 1 inch = 25.4 mm, 1 square yard = 0.8361 m2.
* V-stiffened that expanded metal lath of
equal rigidity and weight is permissible on the same spacings as 3/8" rib
metal lath.
** Paper-backed wire fabric, No. 16-gauge wire,
2" x 2" mesh, with stiffner.
R4411.1.3.3 All metal
lath shall be lapped 1 inch (25 mm) minimum.
R4411.1.3.4 All
attachments for securing metal lath, wire lath and wire fabric to supports
shall be spaced not more than 6 inches (152 mm) apart, and side laps shall be
secured to supports and be tied between supports at not to exceed 9 inches (229
mm) intervals.
R4411.1.3.5 Metal and
wire lath shall be attached to vertical wood supports with the equivalent of 4d
galvanized or blue common nails driven to a penetration of at least 3/4 inch
(19 mm) and bent over to engauge not less than three strands of lath. Metal and
wire lath shall be attached to ceiling joists or other horizontal wood supports
with the equivalent of No. 11-gauge, barbed, galvanized or blued nails 11/2 (38
mm) inches long having a head not less than 3/8 inch (9.5 mm) in diameter.
R4411.1.3.6 Metal and
wire lath shall be attached to horizontal and vertical metal supports with the
equivalent of No. 8 galvanized sheet-metal screws.
R4411.1.4 Nonbearing
lath and plaster partitions.
R4411.1.4.1 Where
reinforced plaster or pneumatically placed plaster partitions are used, they
shall have vertical steel or iron channels with a depth of not less than
one-third of the thickness of the partition and spaced not more than 24 inches
(610 mm) on centers. The thickness of metal in the channels shall not be less
than 16 U.S. standard gauge or light gauge steel studs.
R4411.1.4.2 Hollow
nonbearing partitions of reinforced plaster or pneumatically placed plaster
shall have a shell thickness of not less than 3/4 inch (19 mm).
R4411.1.4.3 Metal
reinforcing shall be as set forth in Table R4411.1.3.2, and gypsum lath shall
not be less than 3/8 inch (9.5 mm) in thickness. The minimum thickness of metal
lath and plaster partitions shall be not less than 2 inches (51 mm) or 1/84 of
the distance between supports.
R4411.1.5 Suspended
and furred plaster ceilings.
R4411.1.5.1 General.
Suspended or furred plaster ceilings shall be designed and constructed as set
forth herein.
R4411.1.5.2 Main
runners. Main runners or carriers shall be rolled steel channels not less than
the sizes and weights set forth in Table R4411.1.5.2.
A main runner shall
be located not more than 6 inches (152 mm) from parallel walls to support the
ends of cross furring. The ends of main runners at walls shall be supported by
hangers located not more than 12 inches (305 mm) from such ends. Splices in
main runners shall be lapped 12 inches (305 mm) and tied, each end, with double
loops of No. 16-gauge wire.
TABLE R4411.1.5.2
SPANS AND SPACING OF
MAIN RUNNERS
MINIMUM SIZE AND TYPE
MAXIMUM SPAN BETWEEN HANGERS OR SUPPORTS
MAXIMUM CENTER-TO-CENTER SPACING
OF RUNNERS
3/4" - 0.3 lb
per ft 2'-0" 3'-0"
1-1/2" - 0.475
lb per ft 3'-0" 4'-0"
1-1/2" - 0.475
lb per ft 3'-6" 3'-6"
1-1/2" - 0.475
lb per ft 4'-0" 3'-0"
1-1/2" - 1.12 lb
per ft 4'-0" 5'-0"
2" -1.26 lb per
ft 5'-0" 5'-0"
1-1/2" x
1-1/2" x 3/16" angle 5'-0"
5'-0"
For SI: 1 in. = 25.4 mm;1 lb/ft = 1.4882 kg/m.
R4411.1.5.3 Cross
furring. Cross furring, or spacers, for various spacing of main runners or
other supports shall be not less than as set forth in Table R4411.1.5.3.
TABLE R4411.1.5.3
SIZES OF CROSS
FURRING IN SUSPENDED AND FURRED CEILINGS
SIZE AND TYPE MAXIMUM SPAN BETWEEN SUPPORTS MAXIMUM SPACING
1/4" pencil rods
Up to 2'-0" 12"
3/4" channels Up to 3'-0" 24"
3/4" channels Up to 4'-0" 16"
For SI: 1 in. = 25.4 mm.
R4411.1.5.3.1 Cross
furring shall be securely saddle-tied to the main runners by not less than two strands
of No. 16 W and M gauge galvanized wire or equivalent approved attachments.
Cross furring shall be attached to joists or beams with double No. 14 W and M
gauge galvanized wire or equivalent approved attachments.
Splices in cross furring shall be lapped 8
inches (203 mm) and tied, each end, with double loops of No. 16-gauge wire.
R4411.1.5.4 Hangers.
Hangers supporting suspended ceilings shall be not less than as set forth in
Table R4411.1.5.4.
TABLE R4411.1.5.4
HANGERS SUPPORTING
SUSPENDED CEILINGS
CEILING AREA
SUPPORTED (SQUARE FEET) MINIMUM SIZE OF
HANGER
12.5 8-gauge wire
16 6-gauge wire
18 3/16" rod
22.5 1/4" rod
50 1" x 3/16" flat bar
For SI: 1 in. = 25.4 mm.
R4411.1.5.4.1 Hangers
shall be saddle-tied or wrapped around main runners to develop the full
strength of the hangers. Hangers shall be fastened to or embedded in the
structural framing, masonry or concrete. Lower ends of flat-strap hangers shall
be bolted with 3/8 inch (9.5 mm) bolts to runner channels or bent tightly
around corners and bolted to the main part of the hanger. Where the area of a
plastered ceiling exceeds 100 square feet (93 m2), suitable methods to resist
uplift forces shall be provided for each 64 square feet (6 m2) of ceiling.
[1- Default – Not related to
structural wind resistance design]
SECTION R4411.2
HIGH VELOCITY
HURRICANE ZONES-PLASTER
R4411.2.1 General.
R4411.2.1.1 Gypsum
plastering shall conform to the Standard Specification for Gypsum Plastering ,
ANSI A42.1.
R4411.2.1.2
Plastering with gypsum, hardwall, lime or cement plaster shall be three-coat
work when applied over metal and wire lath and shall be not less than two-coat
work when applied over gypsum lath or gypsum block.
R4411.2.1.3 Portland
cement plaster shall not be applied directly to gypsum lath.
R4411.2.1.4 In no
case shall a brush coat be accepted as a required coat where three-coat work is
required by this section.
R4411.2.1.5 Grounds
shall be installed to provide for the thickness of plaster, as set forth in
Table R4411.2.1.5, as measured from the face of the lath.
TABLE R4411.2.1.5
REQUIRED THICKNESS OF
INTERIOR PLASTER
TYPE OF LATH THICKNESS OF PLASTER
Metal or wire lath 5/8" minimum
Gypsum lath 1/2" minimum
For SI: 1 in. = 25.4 mm.
R4411.2.1.6 If
monolithic-concrete ceiling surfaces require more than 3/8 inch (9.5 mm) of
plaster to produce desired lines or surfaces, metal lath or wire lath shall be
attached thereto; except that special bonding agents approved by the building
official may be used.
R4411.2.1.7 The
building official may require test holes to be made for the purpose of
determining the thickness of plaster.
R4411.2.2 Materials.
R4411.2.2.1
Aggregates.
R4411.2.2.1.1
Inorganic aggregates used for plaster and stucco shall conform to the Standard
Specification for Inorganic Aggregates for Use In Gypsum Plaster , ASTM C 35,
except that graduation of locally produced sand shall be such that the fineness
modulus is between 1.20 and 2.35.
R4411.2.2.1.2
Aggregates shall be quarried or washed in fresh water and shall contain not
more than 1/20 of 1 percent salt, by weight.
R4411.2.2.2 Gypsum.
Gypsum plaster shall conform to the Standard Specification for Gypsum Plaster ,
ASTM C 28.
R4411.2.2.3 Lime.
Lime shall conform to the Standard Specification for Quicklime for Structural
Purposes , ASTM C 5, and the Standard Specification for Special Finish Hydrated
Lime , ASTM C 206.
R4411.2.2.4 Keene's
cement. Keene's cement shall conform to the Standard Specification for Keene's
Cement , ASTM C 61.
R4411.2.2.5 Portland
cement.
R4411.2.2.5.1
Portland cement shall conform to the Standard Specification for Portland Cement
, ASTM C 150.
R4411.2.2.5.2
Approved types of plasticity agents may be added to Portland cement in the
manufacturing process or when mixing the plaster, but in no case shall the
amount of the plasticity agent exceed 10 percent of the volume of cement in the
plaster mixture.
R4411.2.2.6 Masonry
cement. Masonry cement shall be Type II and shall conform to the Standard
Specification for Masonry Cement , ASTM C 91.
R4411.2.3
Proportioning and mixing.
R4411.2.3.1 Base
coats. The proportions of sand, vermiculite or perlite to 100 pounds (45.4 kg)
of gypsum neat plaster shall not exceed the requirements in this section.
R4411.2.3.1.1 Gypsum
or hardwall plaster. Gypsum or hardwall plaster shall be proportioned in
accordance with Section R4411.2.3.1.1.
TABLE R4411.2.3.1.1
GYPSUM AND HARDWALL
PLASTER
APPLICATION METHOD DAMP LOOSE SAND (lb) VERMICULITE
OR PERLITE
(cu ft)
TWO-COAT WORK
(DOUBLE-UP METHOD)
(1) Over gypsum lath
(2) Over Masonry2
250
300
21/2
3
THREE-COAT WORK
(1) First (scratch)
coat over lath
(2) First (scratch)
coat over masonry
(3) All second
(brown) coats
2001
300
3001
2
3
3
1. Except over
monolithic concrete.
2. In lieu of the
proportioning specified, the proportions may be 100 lb of gypsum neat plaster
to not more than 250 lb of damp, loose sand or 2-1/2 cu ft of vermiculite or
perlite, provided this proportioning is used for both scratch and brown coats.
R4411.2.3.1.2
Wood-fiber gypsum plaster. Wood-fiber gypsum plaster for use on all types of
lath shall be mixed with water only and shall be mixed in the proportion of one
part of plaster to one part of sand, by weight, for use on masonry.
R4411.2.3.1.3 Ready
mixed plaster. Gypsum ready-mixed plaster shall be in the proportion of 100
pounds (45.4 kg) of gypsum neat plaster to not more than 250 lb (113 kg) of
sand; or when vermiculite or perlite is used as an aggregate, the proportions
shall be 100 pounds (45.4 kg) of gypsum neat plaster to not more than 21/2
cubic feet (0.07 m3) vermiculite or perlite.
R4411.2.3.1.4
Portland-cement plaster. For three-coat work, the first two coats shall be
required for the first two coats of exterior stucco (see Section R4411.3).
R4411.2.3.1.5 Masonry
cement plaster. For two- or three-coat work, all work shall be set forth in
Section R4411.2.
R4411.2.3.2 Finish
coats for gypsum or lime plaster. The finish coats shall be mixed and
proportioned in accordance with this section.
R4411.2.3.2.1 Smooth
white finish, mixed in the proportion of not less than one part gypsum gaging
plaster to three parts lime putty, by volume, or an approved prepared gypsum
trowel finish.
R4411.2.3.2.2
Sand-float finish, mixed in the proportion of one-half part of Keene's cement
to two parts of lime putty and not more than four and one-half parts of sand,
by volume, or an approved gypsum sand-float finish.
R4411.2.3.2.3 Keene's
cement finish, mixed in the proportion of three parts Keene's cement to one
part lime putty, by volume.
R4411.2.3.2.4 Lime
sand-float finish, mixed in the proportion of three parts lime putty to three
parts sand, by volume.
R4411.2.3.2.5 Finish
coat for perlite or vermiculite aggregate plasters, mixed in the proportion of
1 cubic foot (28 339 cc) of aggregate to 100 pounds (45 kg) of unfibered gypsum
plaster, or mixed according to manufacturer's specifications.
R4411.2.3.3 Finish
coat for Portland cement plaster. Finish coats for interior Portland cement
plaster shall be one of the following:
1. As required for the third coat of
exterior stucco (see Section R4410.4).
2. A gauged cement plaster mixed in proportion
of one part Portland cement to not more than 15 percent lime putty and not more
than four parts of sand, by volume.
R4411.2.3.4 Finish
coat for masonry cement plaster. Finish coat for masonry cement plaster shall
be as set forth in Section R4411.2.4.2.3.
R4411.2.4
Application.
R4411.2.4.1 Base
coats.
R4411.2.4.1.1 Gypsum
plaster. The scratch coat shall be applied with sufficient material and
pressure to form a full key or bond.
R4411.2.4.1.1.1 For
two-coat work it shall be doubled back to bring the plaster out to grounds and
straightened to a true surface and left rough to receive the finish coat.
R4411.2.4.1.1.2 For
three-coat work, the scratch (first) coat shall be scratched to a rough
surface. The brown (second) coat shall be applied after the scratch coat has
set firm and hard, brought out to grounds, straightened to a true surface with
rod and darby and left rough, ready to receive the finish (third) coat.
R4411.2.4.1.1.3 The
finish coat shall be applied to a practically dry base coat or to a thoroughly
dry base coat which has been evenly wetted by brushing or spraying. The use of
excessive water shall be avoided in the application of all types of finish coat
plastering.
R4411.2.4.1.2
Portland-cement plaster. The first two coats shall be as required for the first
two coats of exterior stucco, except that the interval between the first and
second coats shall be not less than 24 hours.
R4411.2.4.1.3 Masonry
cement plaster. Where masonry cement is the only cementitious material, the
second coat may be applied to the base coat as soon as the base coat has
attained sufficient strength and rigidity to support the second (finish) coat.
R4411.2.4.2 Finish.
R4411.2.4.2.1 Smooth
white finish shall be applied over the base coat that has set for a period of
not less than 24 hours and is surface-dry. Thickness shall be from 1/16 inch to
1/8 inch (1.6 to 3.3 mm).
R4411.2.4.2.2
Sand-float finish shall be applied over the set base coat that is not quite
dry.
R4411.2.4.2.3 Keene's
cement finish shall be applied over the set base coat that is not quite dry.
Thickness shall be from 1/16 inch to 1/8 inch (1.6 to 3.3 mm), unless finish
coat is marked off or is jointed; in which case, the thickness may be increased
as required by depth of marking or jointing.
R4411.2.4.2.4 The
finish coat for interior Portland-cement plastering shall be applied in the
same manner as required for the third coat of exterior stucco, except that
other types of finish coat may be applied as specified in Section R4410.4.
R4411.2.4.2.5 The
finish coat for lightweight aggregate plastering shall be from 1/16 inch to 1/8
inch (1.6 to 3.3 mm).
R4411.2.4.3 Plaster
on concrete.
R4411.2.4.3.1
Monolithic-concrete surfaces shall be clean, free from efflorescence, damp and
sufficiently rough to insure adequate bond.
R4411.2.4.3.2 Gypsum
plaster applied to monolithic-concrete ceilings shall be specially prepared
bond plaster for use on concrete, to which only water shall be added. Gypsum
plaster on monolithic walls and columns shall be applied over a scratch coat of
bond plaster, or other bonding material, before it has set. The brown coat
shall be brought out to grounds, straightened to a true surface and left rough,
ready to receive the finish coat.
R4411.2.4.3.3 Portland-cement
plaster applied to interior concrete walls or ceilings shall conform to
requirements for application to exterior concrete walls as specified in Section
R4411.3.
[1- Default – Not related to structural wind resistance
design]
SECTION
R4411.3
HIGH-VELOCITY
HURRICANE ZONES — STUCCO
R4411.3.1 General.
R4411.3.1.1 Portland
cement-based plaster shall be applied in accordance with ASTM C 926, excluding
Table 4 of that standard.
R4411.3.1.2 Stucco
base and finish coats, where required to meet fire-resistance requirements,
shall be mixed in proportion of at least one part Portland cement to a maximum
of two and one-half parts sand by volume.
R4411.3.1.3 Approved
manufacturing products may be used for base and finish coats.
R4411.3.1.4 Materials.
The materials of stucco shall conform to ASTM C 926.
R4411.3.1.5
Admixtures.
R4411.3.1.5.1
Plasticity agents shall be of approved types and amounts and, where added to
Portland cement in the manufacturing process, no additions shall be made later.
R4411.3.1.5.2 Color
may be added to the finish coat in approved amounts.
R4411.3.1.6
Application.
R4411.3.1.6.1 Stucco
applied to concrete or masonry to meet fire-resistance requirements shall
consist of at least two coats, and the total thickness shall be not less than
1/2 inch (12.7 mm).
R4411.3.1.6.2 Masonry
surfaces on which all stucco is applied shall be clean, free from
efflorescence, damp and sufficiently rough, or coated with an approved bonding
agent, to insure proper bond.
R4411.3.1.6.3 All
concrete surfaces shall be coated with an approved bonding agent or shall be
effectively roughened.
R4411.3.1.6.4 The
first coat shall be well forced into the pores of the masonry, shall be brought
out to grounds, straightened to a true surface and left rough enough to receive
the finish coat.
R4411.3.1.6.5 The
first coat shall be rodded and waterfloated to a true surface approximately
one-half the total thickness.
R4411.3.1.6.6 The
base coat shall be damp cured for a period of not less than 24 hours.
R4411.3.1.6.7 In lieu
thereof, the finish coat, where containing appropriate waterproofing or curing
admixtures, may be applied as soon as the base coat has attained initial set
and is sufficiently firm to receive the finish coat.
R4411.3.1.6.8 The
finish coat shall be applied over a uniformly damp but surface-dry base.
R4411.3.1.6.9 Stucco
shall be kept damp for a period of not less than 48 hours after application of
the finish coat.
R4411.3.1.6.10 In
lieu thereof, the finish coat may contain appropriate approved waterproofing or
curing agents.
[1- Default – Not related to structural wind resistance
design]
R4411.3.2
Stucco on walls other than concrete or masonry.
R4411.3.2.1 General.
Stucco shall be as set forth in Section R4411.3.
[1- Default – Not related to structural wind resistance
design]
R4411.3.2.2
Moisture barrier.
Wood shall be covered with 15-pound (9 kg) roofing felt, or other approved
equally moisture-resisting layer, and metal reinforcement as set forth herein.
R4411.3.2.3
Metal reinforcement.
R4411.3.2.3.1 Stucco shall be reinforced with
galvanized expanded metal weighing no less than 1.8 pounds per square yard
(0.98 kg/m2), or galvanized welded or woven wire-fabric weighing no less than 1
pound per square yard (0.54 kg/m2).
R4411.3.2.3.2 All metal lathing shall be lapped not
less than 1 inch (25 mm).
R4411.3.2.3.3 Metal reinforcement shall be furred
out from the backing by an approved method.
R4411.3.2.3.4 Fastenings into wood sheathing or
wood framing shall be by galvanized nails, with heads not less than 3/8 inch
(9.5 mm) in diameter, driven to full penetration, using a minimum of two nails
per square foot (0.093 m2), or by approved staples having equal resistance to
withdrawal.
R4411.3.2.3.5 The fastening of rib-lath to metal
members shall be by #8 galvanized sheet-metal screws, using a minimum of two
screws per square foot (0.093 m2).
R4411.3.2.4
Application.
R4411.3.2.4.1 Stucco applied on metal lath shall be
three-coat work applied to a total thickness of not less than 1/2 inch (12.7
mm) thickness except as required to meet fire resistance requirements.
R4411.3.2.4.2 The first coat shall be forced
through all openings in the reinforcement to fill all spaces and scored
horizontally.
R4411.3.2.4.3 The second coat shall be applied
after the first coat has set sufficiently to provide a rigid backing.
R4411.3.2.4.4 The third coat shall be applied as
soon as the second coat has attained initial set.
R4411.3.3
Pneumatically placed stucco.
R4411.3.3.1
Pneumatically-placed stucco shall consist of a mixture of one part Portland
cement to not more than five parts sand, conveyed through a pipe or flexible
tube and deposited by pressure in its final position.
R4411.3.3.2 Rebound
material may be screened and re-used as sand in an amount not greater than 25
percent of the total sand in any batch.
R4411.3.3.3
Plasticity agents may be used as specified in Section R4411.3.1.5.1.
[1- Default – Not related to structural wind resistance
design]
SECTION
R4411.4
HIGH-VELOCITY
HURRICANE ZONES — GYPSUM BOARD PRODUCTS AND ACCESSORY ITEMS
R4411.4.1 General.
R4411.4.1.1 Gypsum
wallboard products and related items and accessories to be used with or without
the addition of plaster for partitions, walls and ceilings shall be as set
forth in this section.
R4411.4.1.2 Where
required to be fire resistive, such assemblies shall also comply with Chapter 7
the Florida Building Code, Building .
[1- Default –
Not related to structural wind resistance design]
R4411.4.2
Standards. The
following standards are adopted as set forth in Chapter 43.
Application and finishing of gypsum panel products GA-216-07
Fire Resistance
Design Manual GA-600-06.
Specification for Gypsum
Wallboard, ASTM C 36.
Specification for
General Requirements for Zinc-Coated (Galvanized) Steel Sheets, by the Hot-Dip
Process, ASTM A 525.
Specification for
Light-gauge Steel Studs, Runners, and Rigid Furring Channels, ASTM C 645.
Specification for Joint
Treatment Materials for Gypsum Wallboard Construction, ASTM C 475.
R4411.4.3 Gypsum
wallboard.
R4411.4.3.1 The
gypsum wallboard shall comply with the standards set forth in Section
R4411.4.2, and single or multiple system combinations shall be not less than
1/2 inch (12.7 mm) in thickness.
R4411.4.3.2 The span
between supports for gypsum wallboard shall be not more than 24 inches (610 mm)
for 1/2 inch (12.7 mm) thick and 5/8 inch (17.1 mm) thick wallboard.
R4411.4.3.3 Gypsum
wallboard used in fire-rated assemblies shall be of a type for which test
ratings are available.
[1- Default –
Not related to structural wind resistance design]
R4411.4.4 Wood studs and wood ceiling supports.
Wood studs and wood ceiling supports shall comply with Section R4409.
R4411.4.5 Steel
studs, ceiling supports and track runners.
R4411.4.5.1 Steel
studs and runners used to construct fire-resistive walls or partitions shall be
hot-dipped galvanized in accordance with ASTM A 525, coating designation G40,
minimum and be of channel or "C" Type shape. The total thickness of
the base metal plus coating shall not be less than 0.0184 inch (0.467 mm)
unpainted and not less than 0.0194 inch (0.493 mm) if coated and painted. Studs
and runners shall comply with ASTM C 645 and have a base metal thickness,
before application of any coating, of not less than 0.0179 inch (0.455 mm).
Structural properties of such studs and runners shall comply with ASTM C 645.
R4411.4.5.1.1 Steel
studs supporting wall hung plumbing fixtures shall be doubled or not less than
20 gauge with a minimum effective moment of inertia equal to 0.864 inch4 (360
m4).
R4411.4.5.1.2 Such
studs shall be rigidly connected top and bottom to prevent significant end
rotation or displacement.
R4411.4.5.1.3 A
horizontal member securely fastened to not less than two studs shall be
installed for the attachment of each wall hung plumbing fixture.
R4411.4.5.2 The
unsupported height of partitions shall comply with the loads and deflections
set forth in Section R4403 and where wallboard is suitably attached, the
composite action may be accounted for in the design.
R4411.4.5.3 Steel
ceiling supports shall comply with Section R4411.1.5.
R4411.4.5.4 Steel
studs track runners and ceiling supports in walls, including curtain walls, shall
comply with ASTM A 525.
Exception: Such
members in interior nonload-bearing walls need not be galvanized but shall
comply with ASTM C 645.
R4411.4.6
Attachments.
R4411.4.6.1
Attachments shall be as set forth herein and for fire-rated assemblies shall
also conform to the material and conditions of the assembly tested.
R4411.4.6.2
Attachment to wood supporting members shall conform to the standard set forth
in Section R4411.4.2.
R4411.4.6.3 Nails and
screws attaching gypsum wallboard shall, without substantially fracturing the
surface paper, be driven below the surface and spotted with finishing joint
compound.
R4411.4.6.4
Attachment to metal members shall be in accordance with Sections R4411.4.6.4.1
through R4411.4.6.4.5.
R4411.4.6.4.1 Gypsum
wallboard shall be attached to metal members by self-drilling, self-tapping
sheet metal screws.
R4411.4.6.4.2 The
spacing of screws attaching gypsum wallboard to metal studs and runners, shall
be not more than 12 inches (305 mm) on center.
R4411.4.6.4.3 Screw
for attaching gypsum wallboard to metal studs shall be not less than 7/8 inch
(22.2 mm) long for 1/2 inch (17.7 mm) wallboard or 1 inch (25.4 mm) long for
5/8 inch (17.1 mm) wallboard.
R4411.4.6.4.4 Screws
attaching gypsum wallboard shall be driven below the surface and spotted with
finishing compound.
R4411.4.6.4.5 Runners
shall be fastened to the ceiling, contiguous walls and partitions and to the
floor at intervals not exceeding 24 inches (610 mm) on center. Such attachment
may be by nails penetrating the base material not less than 5/8 inch (17.1 mm)
or by self-drilling, self-tapping sheet metal screws attaching metal to metal.
[1- Default – Not related to structural wind resistance
design]
SECTION R4411.5
HIGH-VELOCITY
HURRICANE ZONES — SUSPENDED AND FURRED CEILINGS
R4411.5.1 General.
Lath and plaster ceilings shall be as set forth in this section.
R4411.5.2 Suspended
and furred ceilings, other than lath and plaster where providing fire
protection shall comply with Chapter 7 of the Florida Building Code, Building .
R4411.5.3 Suspended
and furred ceilings, other than lath and plaster, shall be suspended and
supported in conformance with the conditions of fire tests or, if not tested,
as recommended by the manufacturer or as required for structural stability.
[1- Default –
Not related to structural wind resistance design]
SECTION R4411.6
HIGH-VELOCITY
HURRICANE ZONES — ASBESTOS
R4411.6.1 Asbestos
cement shall not be permitted for use under this code.
[1- Default –
Not related to structural wind resistance design]
SECTION R4411.7
HIGH-VELOCITY
HURRICANE ZONES — TILE
R4411.7.1 Ceramic and
Portland cement floor tile shall be set on a concrete slab or on wood sheathing
on wood joists protected by a waterproof membrane.
R4411.7.2 Floor tile
shall be set in a mortar bed of one part Portland cement to three parts
aggregate or otherwise bedded in an approved adhesive material.
R4411.7.2.1 Ceramic
and Portland cement wall tile used in areas subject to frequent wearing shall
be backed with masonry, stucco on wire lath or approved tile backer board.
R4411.7.2.2 Wall tile
used in areas not subject to frequent wearing shall be backed by a cladding
having the rigidity of stucco on wire lath and shall be bedded in cement mortar
or other approved adhesive material.
R4411.7.3 Portland
cement or other porous tile shall be soaked in water not less than 1 hour
before placing.
R4411.7.4 Built-in
tubs with overhead showers shall have waterproof joints between the tub and the
wall and floor.
[1- Default – Not related to
structural wind resistance design]