Deletion legend:
[1- Default – Not related to structural wind resistance design]
[2- Fire/Life Safety]
[3- Covered in model base code]
[4- Code Cycle Modification to be submitted to strike section and
refer to appropriate FBC,B sections]
SECTION
R4413
[4- Code Cycle Modification to be submitted to strike section and
refer to appropriate FBC,B and FBC,P sections]
HIGH-VELOCITY
HURRICANE ZONES — STORM DRAINAGE
R4413.1
General.
R4413.1.1
Scope. The provisions
of this section shall govern the materials, design, construction and
installation of storm drainage.
R4413.1.2
Where required. All
roofs, paved areas, yards, courts and courtyards shall drain into a separate
storm sewer system, or a combined sewer system, or to an approved place of
disposal. For one- and two-family dwellings, and where approved, storm water is
permitted to discharge onto flat areas, such as streets or lawns, provided that
the storm water flows away from the building.
R4413.1.3
Prohibited drainage.
Storm water shall not be drained into sewers intended for sewage only.
R4413.1.4
Tests. The conductors
and the building storm drain shall be tested in accordance with Section 312 of
the Florida Building Code, Plumbing .
R4413.1.5
Continuous flow. The
size of a drainage pipe shall not be reduced in the direction of flow.
R4413.1.6
Fittings and connections.
All connections and changes in direction of the storm drainage system shall be
made with approved drainage-type fittings in accordance with Table R4413.1.6
herein. The fittings shall not obstruct or retard flow in the system.
TABLE
R4413.1.6
FITTINGS
FOR CHANGE IN DIRECTION
TYPE OF FITTING PATTERN CHANGE IN DIRECTION
Horizontal to vertical Vertical to horizontal Horizontal to horizontal
Sixteenth bend X X
X
Eighth bend X X
X
Sixth bend X X
X
Quarter bend X Xa
Xa
Short sweep X Xa,b
Xa,b
Long sweep X X
X
Sanitary tee Xc
Wye X X
X
Combination wye and
eighth bend X X X
For SI: 1 inch = 25.4 mm.
a. The fittings shall only be permitted for a
2-inch or smaller fixture drain.
b. Three inches and larger.
c. For a limitation on double sanitary tees, see
Section 706.3 of the Florida Building Code, Plumbing.
R4413.1.7
Roof design. Roofs
shall be designed for the maximum possible depth of water that will pond
thereon as determined by the relative levels of roof deck and overflow weirs,
scuppers, edges or serviceable drains in combination with the deflected
structural elements. In determining the maximum possible depth of water, all
primary roof drainage means shall be assumed to be blocked.
R4413.1.8 Cleanouts
required. Cleanouts shall be installed in the storm drainage system and
shall comply with the provisions of this code for sanitary drainage pipe
cleanouts.
SECTION
R4413.2
HIGH
VELOCITY HURRICANE ZONES — MATERIALS
R4413.2.1
General. The
materials and methods utilized for the construction and installation of storm
drainage systems shall comply with this section.
R4413.2.2
Inside storm drainage conductors.
Inside storm drainage conductors installed above ground shall conform to one of
the standards listed in Table R4413.2.2 herein.
TABLE
R4413.2.2
ABOVE-GROUND
DRAINAGE AND VENT PIPE
MATERIAL STANDARD
Acrylonitrile butadiene
styrene (ABS) plastic pipe ASTM D 2661; ASTM F 628; CSA B181.1
Brass pipe ASTM B 43
Cast-iron pipe ASTM A 74; CISPI 301;
ASTM A 888
Copper or copper-alloy
pipe ASTM B 42; ASTM B 302
Copper or copper-alloy
tubing (Type K, L, M or DWV) ASTM
B 75; ASTM B 88;
ASTM B 251; ASTM B 306
Galvanized steel pipe ASTM A 53
Glass pipe ASTM C 1053
Polyolefin pipe CSA CAN/CSA-B181.3
Polyvinyl chloride (PVC)
plastic pipe (Type DWV) ASTM D 2665;
ASTM D 2949; ASTM F 891;
CSA CAN/CSA-B181.2
R4413.2.3
Underground building storm drain pipe.
Underground building storm drain pipe shall conform to one of the standards
listed in Table R4413.2.3 herein.
TABLE
R4413.2.3
UNDERGROUND
BUILDING DRAINAGE AND VENT PIPE
MATERIAL STANDARD
Acrylonitrile butadiene
styrene (ABS) plastic pipe ASTM D
2661; ASTM F 628; CSA B181.1
Asbestos-cement pipe ASTM C 428
Cast-iron pipe ASTM A 74; CISPI 301;
ASTM A 888
Copper or copper-alloy
tubing (Type K or L) ASTM B 75; ASTM B
88;
ASTM B 251
Polyolefin pipe CSA CAN/CSA-B181.3
Polyvinyl chloride (PVC)
plastic pipe (Type DWV) ASTM D 2665;
ASTM D 2949; ASTM F 891;
CSA CAN/CSA-B181.2
R4413.2.4
Building storm sewer pipe.
Building storm sewer pipe shall conform to one of the standards listed in Table
R4413.2.4.
R4413.2.5
Subsoil drain pipe.
Subsoil drains shall be open-jointed, horizontally split or perforated pipe
conforming to one of the standards listed in Table R4413.2.5.
R4413.2.6
Roof drains. Roof
drains shall conform to ASME A112.21.2.
R4413.2.7
Fittings. Pipe
fittings shall be approved for installation with the piping material installed,
and shall conform to the respective pipe standards or one of the standards
listed in Table R4413.2.7. The fittings shall not have ledges, shoulders or
reductions capable of retarding or obstructing flow in the piping. Threaded
drainage pipe fittings shall be of the recessed drainage type.
TABLE
R4413.2.4
BUILDING
STORM SEWER PIPE
MATERIAL STANDARD
Acrylonitrile butadiene
styrene (ABS) plastic pipe ASTM D
2661; ASTM D 2751; ASTM F 628
Asbestos-cement pipe ASTM C 428
Cast-iron pipe ASTM A 74; CISPI 301;
ASTM A 888
Concrete pipe ASTM C 14; ASTM C 76;
CSA A257.1;
CSA CAN/CSA A257.2
Copper or copper-alloy
tubing (Type K, L, M or DWV) ASTM
B 75; ASTM B 88;
ASTM B 251; ASTM B 306
Polyvinyl chloride (PVC)
plastic pipe (Type DWV, SDR26, SDR35, SDR41, PS50 or PS100) ASTM D 2665; ASTM D 2797; ASTM D 3034;
ASTM F 891; CSA-B182.2;
CSA CAN/CSA-B182.4
Vitrified clay pipe ASTM C 4; ASTM C 700
TABLE
R4413.2.5
SUBSOIL
DRAIN PIPE
MATERIAL STANDARD
Asbestos-cement pipe ASTM C 508
Cast-iron pipe ASTM A 74; CISPI 301;
ASTM A 888
Polyethylene (PE)
plastic pipe ASTM F 405
Polyvinyl chloride (PVC)
plastic pipe (Type Sewer Pipe, PS25, PS50 or PS100) ASTM D 2729; ASTM F 891; CSA-B182.2;
CSA CAN/CSA-B182.4
Vitrified clay pipe ASTM C 4; ASTM C 700
TABLE
R4413.2.7
PIPE
FITTINGS
MATERIAL STANDARD
Acrylonitrile butadiene
styrene (ABS) plastic pipe ASTM D 2468
Cast iron ASME B16.4; ASME B16.12; ASTM A 888
Chlorinated polyvinyl
chloride (CPVC) plastic ASTM F
437; ASTM F 438; ASTM F 439
Copper or copper-alloy ASME B16.15; ASME B16.18; ASME B16.22;
ASME B16.23; ASME B16.26; ASME B16.29; ASME B16.32
Gray iron and ductile
iron AWWA C110
Malleable iron ASME B16.3
Plastic, general ASTM F 409
Polyethylene (PE)
plastic ASTM D 2609
Polyvinyl chloride (PVC)
plastic ASTM D 2464; ASTM D 2466;
ASTM D 2467;
CSA CAN/CSA-B137.2
Steel ASME B16.9; ASME B16.11; ASME B16.28
SECTION
R4413.3
RESERVED
SECTION
R4413.4
HIGH-VELOCITY
HURRICANE ZONES — CONDUCTORS AND CONNECTIONS
R4413.4.1
Prohibited use.
Conductor pipes shall not be used as soil, waste or vent pipes, and soil, waste
or vent pipes shall not be used as conductors.
R4413.4.2
Combining storm with sanitary drainage. The sanitary and storm drainage systems of a structure
shall be entirely separate except where combined sewer systems are utilized.
Where a combined sewer is utilized, the building storm drain shall be connected
in the same horizontal plane through a single-wye fitting to the combined sewer
at least 10 feet (3048 mm) downstream from any soil stack.
R4413.4.3
Floor drains. Floor
drains shall not be connected to a storm drain.
SECTION
R4413.5
HIGH-VELOCITY
HURRICANE ZONES- ROOF DRAINS
R4413.5.1
Strainers. Roof
drains shall have strainers extending not less than 4 inches (102 mm) above the
surface of the roof immediately adjacent to the roof drain. Strainers shall
have an available inlet area, above roof level, of not less than one and
one-half times the area of the conductor or leader to which the drain is
connected.
R4413.5.2
Flat decks. Roof
drain strainers for use on sun decks, parking decks and similar areas that are
normally serviced and maintained shall comply with Section R4413.5.1 or shall
be of the flat-surface type, installed level with the deck, with an available
inlet area not less than two times the area of the conductor or leader to which
the drain is connected.
R4413.5.3
Roof drain flashings.
The connection between roofs and roof drains which pass through the roof and
into the interior of the building shall be made water tight by the use of
approved flashing material.
SECTION
R4413.6
HIGH
VELOCITY HURRICANE ZONES- SIZE OF CONDUCTORS, LEADERS AND STORM DRAINS
R4413.6.1
General. The size of
the vertical conductors and leaders, building storm drains, building storm
sewers, and any horizontal branches of such drains or sewers shall be based on
the 100-year hourly rainfall rate indicated in Figure R4413.6.1 or on other
rainfall rates determined from approved local weather data.
R4413.6.2
Vertical conductors and leaders.
Vertical conductors and leaders shall be sized for the maximum projected roof
area, in accordance with Table R4413.6.2.
R4413.6.3
Building storm drains and sewers.
The size of the building storm drain, building storm sewer and their horizontal
branches having a slope of one-half unit or less vertical in 12 units
horizontal (4-percent slope) shall be based on the maximum projected roof area
in accordance with Table R4413.6.3. The minimum slope of horizontal branches
shall be one-eighth unit vertical in 12 units horizontal (1-percent slope)
unless otherwise approved.
R4413.6.4
Vertical walls. In
sizing roof drains and storm drainage piping, one-half of the area of any
vertical wall that diverts rainwater to the roof shall be added to the
projected roof area for inclusion in calculating the required size of vertical
conductors, leaders and horizontal storm drainage piping.
R4413.6.5
Parapet wall scupper location.
Parapet wall roof drainage scupper and overflow scupper location shall comply
with the requirements of the Florida Building Code, Residential .
R4413.6.6
Size of roof gutters.
The size of semicircular gutters shall be based on the maximum projected roof
area in accordance with Table R4413.6.6.
SECTION
R4413.7
HIGH-VELOCITY
HURRICANE ZONES- SECONDARY (EMERGENCY) ROOF DRAINS
R4413.7.1 Secondary drainage required.
Secondary (emergency) roof drains or scuppers shall be provided where the roof
perimeter construction extends above the roof in such a manner that water will
be entrapped if the primary drains allow buildup for any reason.
R4413.7.2 Separate systems required. Secondary
roof drain systems shall have piping the end point of discharge separate from
the primary system. Discharge shall be above grade, in a location which would
normally be observed by the building occupants or maintenance personnel.
FIGURE R4413.6.1
100-YEAR, 1-HOUR
RAINFALL (inches)
EASTERN UNITED STATES
For SI: 1 inch = 25.4 mm.
Source: National Weather
Service, National Oceanic and Atmospheric Administration, Washington, D.C.
TABLE R4413.6.2
SIZE OF VERTICAL
CONDUCTORS AND LEADERS
DIAMETER OF LEADER
(inches)a HORIZONTALLY PROJECTED ROOF
AREA (square feet)
Rainfall Rate (inches
per hour)
1 2 3
4 5 6 7 8
9 10 11 12
2 2,880 1,440
960 720
575 480
410 360
320 290
260 240
3 8,800 4,400
2,930 2,200
1,760 1,470
1,260 1,100
980 880
800 730
4 18,400 9,200
6,130 4,600
3,680 3,070
2,630 2,300
2,045 1,840
1,675 1,530
5 34,600 17,300
11,530 8,650 6,920 5,765 4,945
4,325 3,845
3,460 3,145
2,880
6 54,000 27,000
17,995 13,500 10,800
9,000 7,715 6,750 6,000 5,400
4,910 4,500
8 116,000 58,000 38,660
29,000 23,200 19,315
16,570 14,500 12,890
11,600 10,545 9,660
For SI: 1 inch = 25.4 mm,1 square foot = 0.0929 m2.
a. Sizes indicated are the diameter of circular
piping. This table is applicable to piping of other shapes provided the
cross-sectional shape fully encloses a circle of the diameter indicated in this
table.
TABLE R4413.6.3
SIZE OF HORIZONTAL STORM
DRAINAGE PIPING
SIZE OF HORIZONTAL
PIPING (inches) HORIZONTALLY PROJECTED
ROOF AREA (square feet)
Rainfall Rate (inches
per hour)
1 2 3
4 5 6
1/8unit vertical in 12
units horizontal (1-percent slope)
3 3288 1644
1096 822
657 548
4 7520 3760
2506 1800
1504 1253
5 13360 6680
4453 3340
2672 2227
6 21400 10700
7133 5350
4280 3566
8 46000 23000
15330 11500
9200 7600
10 82800 41400
27600 20700
16580 13800
12 133200 66600
44400 33300
26650 22200
15 218000 109000
72800 59500 47600 39650
1/4unit vertical in 12
units horizontal (2-percent slope)
3 4640 2320
1546 1160
928 773
4 10600 5300
3533 2650
2120 1766
5 18800 9440
6293 4720
3776 3146
6 30200 15100
10066 7550
6040 5033
8 65200 32600
21733 16300
13040 10866
10 116800 58400
38950 29200
23350 19450
12 188000 94000
62600 47000
37600 31350
15 336000 168000
112000 84000 67250 56000
1/2unit vertical in 12
units horizontal (4-percent slope)
3 6576 3288
2295 1644
1310 1096
4 15040 7520
5010 3760
3010 2500
5 26720 13360
8900 6680
5320 4450
6 42800 21400
13700 10700
8580 7140
8 92000 46000
30650 23000
18400 15320
10 171600 85800
55200 41400
33150 27600
12 266400 133200
88800 66600 53200 44400
15 476000 238000
158800 119000 95300
79250
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2.
TABLE R4416.6.6
SIZE OF SEMICIRCULAR
ROOF GUTTERS
DIAMETER OF GUTTERS (inches)
HORIZONTALLY PROJECTED ROOF
AREA (square feet)
Rainfall rate (inches
per hour)
1 2 3 4 5 6
1/16 unit vertical in 12
units horizontal (0.5-percent slope)
3 680 340
226 170
136 113
4 1440 720
480 360
288 240
5 2500 1250
834 625
500 416
6 3840 1920
1280 960
768 640
7 5520 2760
1840 1380
1100 918
8 7960 3980
2655 1990
1590 1325
10 14400 7200
4800 3600
2880 2400
1/8 unit vertical in 12
units horizontal (1-percent slope)
3 960 480
320 240
192 160
4 2040 1020
681 510
408 340
5 3520 1760
1172 880
704 587
6 5440 2720
1815 1360
1085 905
7 7800 3900
2600 1950
1560 1300
8 11200 5600
3740 2800
2240 1870
10 20400 10200
6800 5100
4080 3400
1/4 unit vertical in 12
units horizontal (2-percent slope)
3 1360 680
454 340
272 226
4 2880 1440
960 720
576 480
5 5000 2500
1668 1250
1000 834
6 7680 3840
2560 1920
1536 1280
7 11040 5520
3860 2760
2205 1840
8 15920 7960
5310 3980
3180 2655
10 28800 14400
9600 7200
5750 4800
1/2 unit vertical in 12
units horizontal (4-percent slope)
3 1920 960
640 480
384 320
4 4080 2040
1360 1020
816 680
5 7080 3540
2360 1770
1415 1180
6 11080 5540
3695 2770
2220 1850
7 15600 7800
5200 3900
3120 2600
8 22400 11200
7460 5600
4480 3730
10 40000 20000
13300 10000
8000 6660
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2.
R4413.7.3
Sizing of secondary drains.
Secondary (emergency) roof drain systems shall be sized in accordance with
Section R4413.6 based on the rainfall rate for which the primary system is
sized in Tables R4416.6.2, R4413.6.3 and R4413.6.6. Scuppers shall be sized to
prevent the depth of ponding water from exceeding that for which the roof was
designed as determined by Section R4413.1.7. Scuppers shall not have an opening
dimension of less than 4 inches (102 mm). The flow through the primary system
shall not be considered when sizing the secondary roof drain system.
TABLE R4413.7
SIZING SCUPPERS FOR A 5
INCHES PER HOUR RATE OF RAINFALL
HORIZONTALLY
PROJECTED ROOF AREA (SQUARE FEET)
HEAD IN INCHES LENGTH OF WEIR IN INCHES
4 6 8
12 16 20 24
1 230 346
461 692
923 1153
1384
2 641 961
1282 1923
2564 3205
3846
3 1153 1730
2307 3461
4615 5769
6923
4 1794 2692
3589 5384
7179 8974
10769
For SI: 1 inch = 25.4 mm, 1 square foot = .0929 m2.
Note: to adjust this
table for other than a 5-inch design rainfall rate multiply the square footage
on the table by 5 then divide by the local design rainfall rate.
Example: For 4 inches of
design rainfall rate a 4-inch long scupper with a 1-inch head would accommodate
287 square feet. 230 x 5.4 = 287.