Deletion legend:

[1- Default – Not related to structural wind resistance design]

[2- Fire/Life Safety]

[3- Covered in model base code]

[4- Code Cycle Modification to be submitted to strike section and refer to appropriate FBC,B sections]

 

SECTION R4413

[4- Code Cycle Modification to be submitted to strike section and refer to appropriate FBC,B and FBC,P sections]

HIGH-VELOCITY HURRICANE ZONES — STORM DRAINAGE

 

R4413.1 General.

 

R4413.1.1 Scope. The provisions of this section shall govern the materials, design, construction and installation of storm drainage.

 

R4413.1.2 Where required. All roofs, paved areas, yards, courts and courtyards shall drain into a separate storm sewer system, or a combined sewer system, or to an approved place of disposal. For one- and two-family dwellings, and where approved, storm water is permitted to discharge onto flat areas, such as streets or lawns, provided that the storm water flows away from the building.

 

R4413.1.3 Prohibited drainage. Storm water shall not be drained into sewers intended for sewage only.

 

R4413.1.4 Tests. The conductors and the building storm drain shall be tested in accordance with Section 312 of the Florida Building Code, Plumbing .

 

R4413.1.5 Continuous flow. The size of a drainage pipe shall not be reduced in the direction of flow.

 

R4413.1.6 Fittings and connections. All connections and changes in direction of the storm drainage system shall be made with approved drainage-type fittings in accordance with Table R4413.1.6 herein. The fittings shall not obstruct or retard flow in the system.

 

TABLE R4413.1.6

FITTINGS FOR CHANGE IN DIRECTION

 

 

TYPE OF FITTING PATTERN          CHANGE IN DIRECTION    

Horizontal to vertical   Vertical to horizontal   Horizontal to horizontal          

Sixteenth bend            X          X          X         

Eighth bend     X          X          X         

Sixth bend       X          X          X         

Quarter bend   X          Xa        Xa       

Short sweep    X          Xa,b     Xa,b    

Long sweep    X          X          X         

Sanitary tee     Xc                               

Wye     X          X          X         

Combination wye and eighth bend     X          X          X         

 

 

For SI:   1 inch = 25.4 mm.

a.  The fittings shall only be permitted for a 2-inch or smaller fixture drain.

b.  Three inches and larger.

c.  For a limitation on double sanitary tees, see Section 706.3 of the Florida Building Code, Plumbing.     

 

R4413.1.7 Roof design. Roofs shall be designed for the maximum possible depth of water that will pond thereon as determined by the relative levels of roof deck and overflow weirs, scuppers, edges or serviceable drains in combination with the deflected structural elements. In determining the maximum possible depth of water, all primary roof drainage means shall be assumed to be blocked.

 

R4413.1.8 Cleanouts required. Cleanouts shall be installed in the storm drainage system and shall comply with the provisions of this code for sanitary drainage pipe cleanouts.

 

SECTION R4413.2

HIGH VELOCITY HURRICANE ZONES — MATERIALS

 

R4413.2.1 General. The materials and methods utilized for the construction and installation of storm drainage systems shall comply with this section.

 

R4413.2.2 Inside storm drainage conductors. Inside storm drainage conductors installed above ground shall conform to one of the standards listed in Table R4413.2.2 herein.

 

TABLE R4413.2.2

ABOVE-GROUND DRAINAGE AND VENT PIPE

 

 

MATERIAL      STANDARD  

Acrylonitrile butadiene

 styrene (ABS) plastic pipe     ASTM D 2661; ASTM F 628; CSA B181.1   

Brass pipe       ASTM B 43    

Cast-iron pipe             ASTM A 74; CISPI 301;

ASTM A 888  

Copper or copper-alloy pipe   ASTM B 42; ASTM B 302      

Copper or copper-alloy tubing (Type K, L, M or DWV)          ASTM B 75; ASTM B 88;

ASTM B 251; ASTM B 306    

Galvanized steel pipe             ASTM A 53    

Glass pipe       ASTM C 1053            

Polyolefin pipe             CSA CAN/CSA-B181.3         

Polyvinyl chloride (PVC) plastic pipe (Type DWV)    ASTM D 2665; ASTM D 2949; ASTM F 891;

CSA CAN/CSA-B181.2         

 

R4413.2.3 Underground building storm drain pipe. Underground building storm drain pipe shall conform to one of the standards listed in Table R4413.2.3 herein.

 

 

 

TABLE R4413.2.3

UNDERGROUND BUILDING DRAINAGE AND VENT PIPE

 

 

MATERIAL      STANDARD  

Acrylonitrile butadiene styrene (ABS) plastic pipe     ASTM D 2661; ASTM F 628; CSA B181.1   

Asbestos-cement pipe           ASTM C 428  

Cast-iron pipe             ASTM A 74; CISPI 301;

ASTM A 888  

Copper or copper-alloy tubing (Type K or L) ASTM B 75; ASTM B 88;

ASTM B 251  

Polyolefin pipe             CSA CAN/CSA-B181.3         

Polyvinyl chloride (PVC) plastic pipe (Type DWV)    ASTM D 2665; ASTM D 2949; ASTM F 891;

CSA CAN/CSA-B181.2         

 

R4413.2.4 Building storm sewer pipe. Building storm sewer pipe shall conform to one of the standards listed in Table R4413.2.4.

 

R4413.2.5 Subsoil drain pipe. Subsoil drains shall be open-jointed, horizontally split or perforated pipe conforming to one of the standards listed in Table R4413.2.5.

 

R4413.2.6 Roof drains. Roof drains shall conform to ASME A112.21.2.

 

R4413.2.7 Fittings. Pipe fittings shall be approved for installation with the piping material installed, and shall conform to the respective pipe standards or one of the standards listed in Table R4413.2.7. The fittings shall not have ledges, shoulders or reductions capable of retarding or obstructing flow in the piping. Threaded drainage pipe fittings shall be of the recessed drainage type.

 

TABLE R4413.2.4

BUILDING STORM SEWER PIPE

 

 

MATERIAL      STANDARD  

Acrylonitrile butadiene styrene (ABS) plastic pipe     ASTM D 2661; ASTM D 2751; ASTM F 628

Asbestos-cement pipe           ASTM C 428  

Cast-iron pipe             ASTM A 74; CISPI 301;

ASTM A 888  

Concrete pipe             ASTM C 14; ASTM C 76;

CSA A257.1;

CSA CAN/CSA A257.2         

Copper or copper-alloy tubing (Type K, L, M or DWV)          ASTM B 75; ASTM B 88;

ASTM B 251; ASTM B 306    

Polyvinyl chloride (PVC) plastic pipe (Type DWV, SDR26, SDR35, SDR41, PS50 or PS100)       ASTM D 2665; ASTM D 2797; ASTM D 3034; ASTM F 891; CSA-B182.2;

CSA CAN/CSA-B182.4         

Vitrified clay pipe         ASTM C 4; ASTM C 700       

 

 

 

 

TABLE R4413.2.5

SUBSOIL DRAIN PIPE

 

 

MATERIAL      STANDARD  

Asbestos-cement pipe           ASTM C 508  

Cast-iron pipe             ASTM A 74; CISPI 301;

ASTM A 888  

Polyethylene (PE) plastic pipe            ASTM F 405   

Polyvinyl chloride (PVC) plastic pipe (Type Sewer Pipe, PS25, PS50 or PS100)    ASTM D 2729; ASTM F 891; CSA-B182.2;

CSA CAN/CSA-B182.4         

Vitrified clay pipe         ASTM C 4; ASTM C 700       

 

TABLE R4413.2.7

PIPE FITTINGS

 

 

MATERIAL      STANDARD  

Acrylonitrile butadiene styrene (ABS) plastic pipe     ASTM D 2468            

Cast iron         ASME B16.4; ASME B16.12; ASTM A 888  

Chlorinated polyvinyl chloride (CPVC) plastic            ASTM F 437; ASTM F 438; ASTM F 439      

Copper or copper-alloy           ASME B16.15; ASME B16.18; ASME B16.22; ASME B16.23; ASME B16.26; ASME B16.29; ASME B16.32           

Gray iron and ductile iron        AWWA C110

Malleable iron ASME B16.3  

Plastic, general           ASTM F 409   

Polyethylene (PE) plastic        ASTM D 2609            

Polyvinyl chloride (PVC) plastic         ASTM D 2464; ASTM D 2466; ASTM D 2467;

CSA CAN/CSA-B137.2         

Steel    ASME B16.9; ASME B16.11; ASME B16.28            

 

SECTION R4413.3

RESERVED

 

SECTION R4413.4

HIGH-VELOCITY HURRICANE ZONES — CONDUCTORS AND CONNECTIONS

 

R4413.4.1 Prohibited use. Conductor pipes shall not be used as soil, waste or vent pipes, and soil, waste or vent pipes shall not be used as conductors.

 

R4413.4.2 Combining storm with sanitary drainage. The sanitary and storm drainage systems of a structure shall be entirely separate except where combined sewer systems are utilized. Where a combined sewer is utilized, the building storm drain shall be connected in the same horizontal plane through a single-wye fitting to the combined sewer at least 10 feet (3048 mm) downstream from any soil stack.

 

R4413.4.3 Floor drains. Floor drains shall not be connected to a storm drain.

 

 

 

SECTION R4413.5

HIGH-VELOCITY HURRICANE ZONES- ROOF DRAINS

 

R4413.5.1 Strainers. Roof drains shall have strainers extending not less than 4 inches (102 mm) above the surface of the roof immediately adjacent to the roof drain. Strainers shall have an available inlet area, above roof level, of not less than one and one-half times the area of the conductor or leader to which the drain is connected.

 

R4413.5.2 Flat decks. Roof drain strainers for use on sun decks, parking decks and similar areas that are normally serviced and maintained shall comply with Section R4413.5.1 or shall be of the flat-surface type, installed level with the deck, with an available inlet area not less than two times the area of the conductor or leader to which the drain is connected.

 

R4413.5.3 Roof drain flashings. The connection between roofs and roof drains which pass through the roof and into the interior of the building shall be made water tight by the use of approved flashing material.

 

SECTION R4413.6

HIGH VELOCITY HURRICANE ZONES- SIZE OF CONDUCTORS, LEADERS AND STORM DRAINS

 

R4413.6.1 General. The size of the vertical conductors and leaders, building storm drains, building storm sewers, and any horizontal branches of such drains or sewers shall be based on the 100-year hourly rainfall rate indicated in Figure R4413.6.1 or on other rainfall rates determined from approved local weather data.

 

R4413.6.2 Vertical conductors and leaders. Vertical conductors and leaders shall be sized for the maximum projected roof area, in accordance with Table R4413.6.2.

 

R4413.6.3 Building storm drains and sewers. The size of the building storm drain, building storm sewer and their horizontal branches having a slope of one-half unit or less vertical in 12 units horizontal (4-percent slope) shall be based on the maximum projected roof area in accordance with Table R4413.6.3. The minimum slope of horizontal branches shall be one-eighth unit vertical in 12 units horizontal (1-percent slope) unless otherwise approved.

 

R4413.6.4 Vertical walls. In sizing roof drains and storm drainage piping, one-half of the area of any vertical wall that diverts rainwater to the roof shall be added to the projected roof area for inclusion in calculating the required size of vertical conductors, leaders and horizontal storm drainage piping.

 

R4413.6.5 Parapet wall scupper location. Parapet wall roof drainage scupper and overflow scupper location shall comply with the requirements of the Florida Building Code, Residential .

 

R4413.6.6 Size of roof gutters. The size of semicircular gutters shall be based on the maximum projected roof area in accordance with Table R4413.6.6.

 

 

 

 

 

 

SECTION R4413.7

HIGH-VELOCITY HURRICANE ZONES- SECONDARY (EMERGENCY) ROOF DRAINS

 

R4413.7.1 Secondary drainage required. Secondary (emergency) roof drains or scuppers shall be provided where the roof perimeter construction extends above the roof in such a manner that water will be entrapped if the primary drains allow buildup for any reason.

 

R4413.7.2 Separate systems required. Secondary roof drain systems shall have piping the end point of discharge separate from the primary system. Discharge shall be above grade, in a location which would normally be observed by the building occupants or maintenance personnel.

 

 

 

FIGURE R4413.6.1

100-YEAR, 1-HOUR RAINFALL (inches)

EASTERN UNITED STATES

 

 

For SI:   1 inch = 25.4 mm.

Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, D.C.          

 

TABLE R4413.6.2

SIZE OF VERTICAL CONDUCTORS AND LEADERS

 

 

DIAMETER OF LEADER (inches)a HORIZONTALLY PROJECTED ROOF AREA (square feet)         

Rainfall Rate (inches per hour)          

1          2          3          4          5          6          7          8          9          10        11        12       

2          2,880   1,440   960      720      575      480      410      360      320      290      260      240     

3          8,800   4,400   2,930   2,200   1,760   1,470   1,260   1,100   980      880      800      730     

4          18,400             9,200   6,130   4,600   3,680   3,070   2,630   2,300   2,045   1,840   1,675   1,530  

5          34,600             17,300             11,530             8,650   6,920   5,765   4,945   4,325   3,845   3,460   3,145             2,880  

6          54,000             27,000             17,995             13,500             10,800             9,000   7,715   6,750   6,000             5,400   4,910   4,500  

8          116,000           58,000             38,660             29,000             23,200             19,315             16,570             14,500             12,890             11,600             10,545             9,660  

 

 

For SI:   1 inch = 25.4 mm,1 square foot = 0.0929 m2.

a.  Sizes indicated are the diameter of circular piping. This table is applicable to piping of other shapes provided the cross-sectional shape fully encloses a circle of the diameter indicated in this table.          

 

TABLE R4413.6.3

SIZE OF HORIZONTAL STORM DRAINAGE PIPING

 

 

SIZE OF HORIZONTAL PIPING (inches)    HORIZONTALLY PROJECTED ROOF AREA (square feet)         

Rainfall Rate (inches per hour)          

1          2          3          4          5          6         

1/8unit vertical in 12 units horizontal (1-percent slope)         

3          3288    1644    1096    822      657      548     

4          7520    3760    2506    1800    1504    1253   

5          13360 6680    4453    3340    2672    2227   

6          21400 10700 7133    5350    4280    3566   

8          46000 23000 15330 11500 9200    7600   

10        82800 41400 27600 20700 16580 13800

12        133200            66600 44400 33300 26650 22200

15        218000            109000            72800 59500 47600 39650

1/4unit vertical in 12 units horizontal (2-percent slope)         

3          4640    2320    1546    1160    928      773     

4          10600 5300    3533    2650    2120    1766   

5          18800 9440    6293    4720    3776    3146   

6          30200 15100 10066 7550    6040    5033   

8          65200 32600 21733 16300 13040 10866

10        116800            58400 38950 29200 23350 19450

12        188000            94000 62600 47000 37600 31350

15        336000            168000            112000            84000 67250 56000

1/2unit vertical in 12 units horizontal (4-percent slope)         

3          6576    3288    2295    1644    1310    1096   

4          15040 7520    5010    3760    3010    2500   

5          26720 13360 8900    6680    5320    4450   

6          42800 21400 13700 10700 8580    7140   

8          92000 46000 30650 23000 18400 15320

10        171600            85800 55200 41400 33150 27600

12        266400            133200            88800 66600 53200 44400

15        476000            238000            158800            119000            95300 79250

 

 

For SI:   1 inch = 25.4 mm, 1 square foot = 0.0929 m2.       

 

TABLE R4416.6.6

SIZE OF SEMICIRCULAR ROOF GUTTERS

 

 

DIAMETER OF GUTTERS (inches)             HORIZONTALLY PROJECTED ROOF AREA (square feet)         

Rainfall rate (inches per hour)           

1          2          3          4          5          6         

1/16 unit vertical in 12 units horizontal (0.5-percent slope)   

3          680      340      226      170      136      113     

4          1440    720      480      360      288      240     

5          2500    1250    834      625      500      416     

6          3840    1920    1280    960      768      640     

7          5520    2760    1840    1380    1100    918     

8          7960    3980    2655    1990    1590    1325   

10        14400 7200    4800    3600    2880    2400   

1/8 unit vertical in 12 units horizontal (1-percent slope)        

3          960      480      320      240      192      160     

4          2040    1020    681      510      408      340     

5          3520    1760    1172    880      704      587     

6          5440    2720    1815    1360    1085    905     

7          7800    3900    2600    1950    1560    1300   

8          11200 5600    3740    2800    2240    1870   

10        20400 10200 6800    5100    4080    3400   

1/4 unit vertical in 12 units horizontal (2-percent slope)        

3          1360    680      454      340      272      226     

4          2880    1440    960      720      576      480     

5          5000    2500    1668    1250    1000    834     

6          7680    3840    2560    1920    1536    1280   

7          11040 5520    3860    2760    2205    1840   

8          15920 7960    5310    3980    3180    2655   

10        28800 14400 9600    7200    5750    4800   

1/2 unit vertical in 12 units horizontal (4-percent slope)        

3          1920    960      640      480      384      320     

4          4080    2040    1360    1020    816      680     

5          7080    3540    2360    1770    1415    1180   

6          11080 5540    3695    2770    2220    1850   

7          15600 7800    5200    3900    3120    2600   

8          22400 11200 7460    5600    4480    3730   

10        40000 20000 13300 10000 8000    6660   

 

 

For SI:   1 inch = 25.4 mm, 1 square foot = 0.0929 m2.       

 

R4413.7.3 Sizing of secondary drains. Secondary (emergency) roof drain systems shall be sized in accordance with Section R4413.6 based on the rainfall rate for which the primary system is sized in Tables R4416.6.2, R4413.6.3 and R4413.6.6. Scuppers shall be sized to prevent the depth of ponding water from exceeding that for which the roof was designed as determined by Section R4413.1.7. Scuppers shall not have an opening dimension of less than 4 inches (102 mm). The flow through the primary system shall not be considered when sizing the secondary roof drain system.

 

TABLE R4413.7

SIZING SCUPPERS FOR A 5 INCHES PER HOUR RATE OF RAINFALL

 

 

            HORIZONTALLY PROJECTED ROOF AREA (SQUARE FEET)

HEAD IN INCHES      LENGTH OF WEIR IN INCHES       

4          6          8          12        16        20        24       

1          230      346      461      692      923      1153    1384   

2          641      961      1282    1923    2564    3205    3846   

3          1153    1730    2307    3461    4615    5769    6923   

4          1794    2692    3589    5384    7179    8974    10769

 

 

For SI:   1 inch = 25.4 mm, 1 square foot = .0929 m2.

Note: to adjust this table for other than a 5-inch design rainfall rate multiply the square footage on the table by 5 then divide by the local design rainfall rate.

Example: For 4 inches of design rainfall rate a 4-inch long scupper with a 1-inch head would accommodate 287 square feet. 230 x 5.4 = 287.