MECHANICAL with Votes 2016-04-13 Local
Technical Amendments to the 2014 5th
Edition Florida Building Code |
|||||||||||||||||||||
JURISDICTION |
DOCUMENT with TECHNICAL AMENDMENT |
TEXT OF TECHNICAL
AMENDMENT |
TAC REVEW |
||||||||||||||||||
Broward
County |
Florida
Building Code, Mechanical Ch. 3 General Regulations |
Florida Building Code Mechanical, 5th Edition (2014) Amendment to Section [M] 307.2.1 307.2.1
Condensate drainage collection, use or disposal. Condensate from all cooling coils and evaporators of equipment
served by an onsite cooling tower in a building or structure wherein the
aggregate cooling capacity of the equipment exceeds 65,000 Btu/hr shall be
collected and conveyed from the drain pan outlet and discharged to the
cooling tower. Where an on-site cooling tower is not installed the
condensate from all cooling coils and evaporators shall be conveyed from
the drain pan outlet to an approved place of disposal. Such piping shall maintain
a minimum horizontal slope in the direction of discharge of not less than
one-eighth unit vertical in 12 units horizontal (1-percent slope). Condensate
shall not discharge into a street, alley or other areas so as to cause
nuisance Exceptions: 1.
Condensate from cooling
coils and evaporators is not required to be collected and conveyed to an
on-site cooling tower; provided 1.1 through 1.3 are met: 1.1 The
equipment comprises 10% or less of the total capacity of the cooling tower
system 1.2 The
equipment is located in an isolated or remote area 1.3 The size
of the equipment is 65,000 Btu/hr or less 2.
In existing buildings
condensate may be collected and conveyed to a cooling tower or discharged to
an approved place of disposal. |
Mechanical TAC Vote: (2nd Calleja for negative roll call 1 Yes 6 No NAR not acceptable for state-wide use. |
||||||||||||||||||
Broward County |
Florida
Building Code, Mechanical Ch. 9 Specific Appliances |
Florida Building Code Mechanical, 5th Edition (2014) Amendment to Section 908 908.5.1 New cooling towers,
including cooling tower replacements shall be operated with conductivity controllers,
as well as make-up and blowdown (bleed off) meters
and shall achieve a minimum of 8 cycles of concentration. 908.5.2 The quality of cooling
tower water shall comply with the equipment manufacturers guidelines. 908.5.3 Cooling towers shall be
equipped with efficient drift eliminators that achieve drift reduction to a
maximum of 0.002% of the recirculated water volume for counterflow
towers and 0.005% of the recirculated water flow for cross-flow towers. 908.5.4 An affidavit of
compliance demonstrating compliance with section 908.5 Florida Building Code
shall be submitted by the property manager/owner to the local water provider
every 12 months following system installation. The affidavit shall be signed
by the service provider and include all dates of service within the reporting
period and verified system operation at a minimum of 8 cycles of
concentration. Exception: Cooling
water tower systems utilizing reclaimed water for makeup water are exempt
from the provisions of section 908.5.1 thru 908.5.4 Florida Building
Code-Mechanical. |
Mechanical TAC Vote: (2nd Crum for negative roll call 1 Yes 6 No NAR not needed for state-wide use. |
||||||||||||||||||
Pinellas
County Construction
Licensing Board |
|
1509.6.5 Mechanical Units. Roof mounted mechanical units shall be mounted
on curbs raised a minimum of 8 inches (203 mm) above the roof surface, or where roofing
materials extend beneath the unit, on raised equipment supports providing a minimum
clearance height in accordance with Table 1509.6.5. Exception: In buildings where the existing rooftop
equipment, in the opinion of the building official, provides sufficient clearance to repair,
recover, replace and/or maintain the roofing system or any of its components, such existing equipment need
not comply with Table 1509.6.5.
Exception: When
removing or replacing roof mounted mechanical units for individual units
and/or spaces within multi-unit buildings the
individual units mav be reinstalled utilizing the
existing system of attachment. At such time of reroofing of the
building all mechanical units must be brought into compliance with this code section. |
Mechanical and Roofing TACs. Vote: 2nd Calleja for negative roll call 0 yes 7 No Not needed for State-wide use. |
||||||||||||||||||
Pinellas County Construction Licensing Board
(PCCLB) |
Florida
Building Code, Residential |
AMEND EXISTING SECTION M1411.3 Condensate disposal. Condensate
from all cooling coils or evaporators shall be conveyed from the drain pan outlet to an
approved place of disposal. Such piping shall maintain a minimum horizontal slope in the
direction of discharge of not less than 1/8 unit vertical in 12 units horizontal (1-percent
slope). Condensate shall not discharge into a street, alley or other areas where it would cause a
nuisance. Pipe Insulation: All primary condensate drain within unconditioned areas shall be
insulated. |
Mechanical TAC 2nd Crum for neg roll call 0 Yes 7 No NAR not needed for state-wide use |
||||||||||||||||||
Pinellas
County Construction
Licensing Board |
Florida
Building Code, Residential |
AMEND EXISTING SECTION M1411.3 Condensate disposal. Condensate
from all cooling coils or evaporators shall be conveyed from the drain pan outlet to an
approved place of disposal. Such piping shall maintain a minimum horizontal slope in the
direction of discharge of not less than 1/8 unit vertical in 12 units horizontal (1-percent
slope). Condensate shall not discharge into a street, alley or other areas where it would cause a
nuisance. Pipe Insulation: All primary condensate drain within unconditioned areas shall be
insulated. |
Mechanical TAC 2nd Crum for neg roll call 0 yes 7 No NAR not needed for state-wide use. |
||||||||||||||||||
|
|
|
|