1509.6.5 Mechanical Units. Roof mounted mechanical units shall be mounted
on curbs raised a minimum of 8 inches (203 mm) above the roof surface, or where roofing
materials extend beneath the unit, on raised equipment supports providing a minimum
clearance height in accordance with Table 1509.6.5. Exception: In buildings where the existing rooftop
equipment, in the opinion of the building official, provides sufficient clearance to repair,
recover, replace and/or maintain the roofing system or any of its components, such existing equipment need
not comply with Table 1509.6.5.
Exception: When
removing or replacing roof mounted mechanical units for individual units
and/or spaces within multi-unit buildings the
individual units mav be reinstalled utilizing the existing system of attachment. At such time of reroofing of the
building all mechanical units must be brought into compliance with this code section. |