Jeff I will not be attending the January FBC meeting since I will be in St Louis attending the ANSI A117.1 Committee meeting. I do have one comment for the TAC as it relates to the new code; when the statute got changed adding section 553.509(2)(a) which states that -any person, firm, or corporation that owns, manages, or operates a residential multifamily dwelling, including a condominium, that is at least 75 feet high and contains a public elevator, as described in s. 399.035(2) and (3) and rules adopted by the Florida Building Commission, shall have at least one public elevator that is capable of operating on an alternate power source for emergency purposes. Alternate power shall be available for the purpose of allowing all residents access for a specified number of hours each day over a 5-day period following a natural disaster, manmade disaster, emergency, or other civil disturbance that disrupts the normal supply of electricity. The alternate power source that controls elevator operations must also be capable of powering any connected fire alarm system in the building.

(b) At a minimum, the elevator must be appropriately prewired and prepared to accept an alternate power source and must have a connection on the line side of the main disconnect, pursuant to National Electric Code Handbook, Article 700. In addition to the required power source for the elevator and connected fire alarm system in the building, the alternate power supply must be sufficient to provide emergency lighting to the interior lobbies, hallways, and other portions of the building used by the public. Residential multifamily dwellings must have an available generator and fuel source on the property or have proof of a current contract posted in the elevator machine room or other place conspicuous to the elevator inspector affirming a current guaranteed service contract for such equipment and fuel source to operate the elevator on an on-call basis within 24 hours after a request. By December 31, 2006, any person, firm or corporation that owns, manages, or operates a residential multifamily dwelling as defined in paragraph (a) must provide to the local building inspection agency verification of engineering plans for residential multifamily dwellings that provide for the capability to generate power by alternate means. Compliance with installation requirements and operational capability requirements must be verified by local building inspectors and reported to the county emergency management agency by December 31, 2007.
(c) Each newly constructed residential multifamily dwelling, including a condominium, that is at least 75 feet high and contains a public elevator, as described in s. 399.035(2) and (3) and rules adopted by the Florida Building Commission, must have at least one public elevator that is capable of operating on an alternate power source for the purpose of allowing all residents access for a specified number of hours each day over a 5-day period following a natural disaster, manmade disaster, emergency, or other civil disturbance that disrupts the normal supply of electricity. The alternate power source that controls elevator operations must be capable of powering any connected fire alarm system in the building. In addition to the required power source for the elevator and connected fire alarm system, the alternate power supply must be sufficient to provide emergency lighting to the interior lobbies, hallways, and other portions of the building used by the public. Engineering plans and verification of operational capability must be provided by the local building inspector to the county emergency management agency before occupancy of the newly constructed building.
(d) Each person, firm, or corporation that is required to maintain an alternate power source under this subsection shall maintain a written emergency operations plan that details the sequence of operations before, during, and after a natural or manmade disaster or other emergency situation. The plan must include, at a minimum, a life safety plan for evacuation, maintenance of the electrical and lighting supply, and provisions for the health, safety, and welfare of the residents. In addition, the owner, manager, or operator of the residential multifamily dwelling must keep written records of any contracts for alternative power generation equipment. Also, quarterly inspection records of life safety equipment and alternate power generation equipment must be posted in the elevator machine room or other place conspicuous to the elevator inspector, which confirm that such equipment is properly maintained and in good working condition, and copies of contracts for alternate power generation equipment shall be maintained on site for verification. The written emergency operations plan and inspection records shall also be open for periodic inspection by local and state government agencies as deemed necessary. The owner or operator must keep a generator key in a lockbox posted at or near any installed generator unit.
(e) Multistory affordable residential dwellings for persons age 62 and older that are financed or insured by the United States Department of Housing and Urban Development must make every effort to obtain grant funding from the Federal Government or the Florida Housing Finance Corporation to comply with this subsection. If an owner of such a residential dwelling cannot comply with the requirements of this subsection, the owner must develop a plan with the local emergency management agency to ensure that residents are evacuated to a place of safety in the event of a power outage resulting from a natural or manmade disaster or other emergency situation that disrupts the normal supply of electricity for an extended period of time. A place of safety may include, but is not limited to, relocation to an alternative site within the building or evacuation to a local shelter.
(f) As a part of the annual elevator inspection required under s. 399.061, certified elevator inspectors shall confirm that all installed generators required by this chapter are in working order, have current inspection records posted in the elevator machine room or other place conspicuous to the elevator inspector, and that the required generator key is present in the lockbox posted at or near the installed generator. If a building does not have an installed generator, the inspector shall confirm that the appropriate prewiring and switching capabilities are present and that a statement is posted in the elevator machine room or other place conspicuous to the elevator inspector affirming a current guaranteed contract exists for contingent services for alternate power is current for the operating period.

This is not in the latest draft version of Chapter 11 of the 2007 FBC and needs to be put in to the code since it is in the statutes. If you have any
questions please let us know. Enjoy the meeting.