Legal Report
December 12, 2007
DCA07-DEC-179 by
Alan Fallik,
Committee Action:
Question - Does section 3109 of the Florida Building Code, Building, prohibit a space which is located below the lowest structural horizontal member (refer to section 3109.3) and above the FEMA National Flood Insurance Program established base flood elevation (see enclosed diagram), and fully enclosed in accordance with the provisions of sections 3109.4.1 and 3109.4.2 from being used for commercial purposes?
Answer - yes, the lowest horizontal structural members must be set at or above the elevation established by FDEP report titled 100 Year Storm Elevation Requirements for Habitable Structures Located Seaward of a CCCL. All Occupancy classifications except S and U shall be prohibited in this space.
Staff Recommendation:
Question - Does section 3109 of the Florida Building Code, Building, prohibit a space which is located below the lowest structural horizontal member (refer to section 3109.3) and above the FEMA National Flood Insurance Program established base flood elevation (see enclosed diagram), and fully enclosed in accordance with the provisions of sections 3109.4.1 and 3109.4.2 from being used for commercial purposes?
Answer - No, section 3109 does not address or prohibit the use of such space for commercial purposes with the exception that the space may not be used for living, sleeping, eating or cooking (i.e. residences, hotels and restaurants) subject to the permit requirements of the Florida Department of Environmental Protection.
ISSUE: DCA07-DEC-182. Petitioner seeks a Declaratory Statement concerning wind design for mechanical systems in existing buildings.
Committee Action:
1. To the
question, Are exterior mounted mechanical units (Cooling towers, fluid coolers,
etc), which are subjected to wind forces, required to have the mechanical
structure and anchorage designed to withstand the applied wind force?, the
answer YES, mechanical equipment and supports being replaced during a Level 1
Alteration shall meet the wind design criteria in Section 1609 of the current
edition of the
2. To the
question, Are exterior mounted mechanical units (cooling towers, fluid coolers,
etc), which are subjected to wind forces, required to have the wind design data
on all construction documents?, the answer is YES, information related to wind
loads shall be shown on the construction documents.
ISSUE: DCA07-DEC-183.
Petitioner seeks a Declaratory Statement on an interpretation of Section
407.1.2 of the
Committee Action:
1a. To the question, Are the wind forces the
mechanical equipment applies to the building, to be determined from the wind
design criteria that was in effect when the building was originally permitted,
or is the current Florida Building wind criteria for mechanical equipment to be
used?, the answer is that mechanical equipment and supports being replaced
during a Level 1 Alteration shall meet the wind design criteria of the current
code, not the code in effect when the building was originally constructed. Section 407.1.2 of the
1b. To
the question, On a Level 1 Alteration, which was permitted when the mechanical
equipment was not required to be designed for wind forces, does the new
mechanical equipment structure need to be designed for the wind forces?, the
answer is YES, the new mechanical equipment structure needs to be designed for
wind forces specified in the 2004 Florida Building Code for both the structure
and anchorage of mechanical equipment.
DCA07-DEC-194 by Gary Swartz, E-Z Taping System, Inc.
To the question, To the Question
does their product, E-Z Fire Tape fall under the scope of Rule 9B-72
Answer: No, Based on Rule 9B-72.010
Definitions, this product falls outside the scope of Rule 9B-72.
DCA07-DEC-252 by James
DiPietro, Broward County Board of Rules and Appeals, proposed to authorize
building officials within
Committee Action:
Reinstatement of an existing permit is more analogous to a ministerial function, with little or no impact on the identified minimum standards, and for which flexibility should be recognized to allow for an appropriate response to local resources and conditions. The element of the proposal that relates to reinstatement of expired permits is not an impermissible local amendment.
Issue: DCA07-DEC-255. Withdrawn by
petitioner. The petitioner seeks a declaratory statement for
installation requirements for a
Staff
Recommendations: Staff provides
following for consideration:
Question
One: Will Product testing per ANSI/DASMA
108 qualify all of the door assembly components, including fasteners
attaching the garage door assembly to the vertical wood jambs?
Answer:
No, the door assembly
components, including fasteners attaching the garage door assembly must be
provided with documentation that demonstrates that they meet the material
requirements of the code sections 1714.5.4.1 which require anchoring systems to
provide equal or greater anchoring performance to the manufacturers
installation instructions, as demonstrated by accepted engineering practice.
Question
Two: Will engineering analysis
qualify the jamb-to-building frame fasteners if sufficient factor of safety is
demonstrated ? (emphasis added)
Answer:
Yes. Section 1714.5.4.1 of the
FBC, requires anchoring systems to provide equal or greater anchoring
performance to the manufacturers installation instructions, as demonstrated by accepted
engineering practice. (emphasis added)
DCA07-DEC-269 by Emil Veksenfeld, PE
Deferred for further information.
Issue: FL 9024 Referral to Structural TAC from Product Approval POC- FL9024 Referral to Structural TAC from Product Approval POC
Modulous of Elasticity (MOE) – Whether the test needs to be done on the OSB or the “Agriboard” Composite? Recommend the product be approved. There is no specific information in the Florida Building Code or the reference material (including reference standards), to show that the MOE has to be done on the component (OSB) or the composite “Agriboard”