Issue: DCA10-DEC- 243.  The Petitioner “Mr. Timothy Graboski” is requesting clarification regarding the applications of Section 1507.7.1 of the 2007 Florida Building Code.  The Petitioner’s question is as follows:

Question: For the project in question and using the Table 1507.2.7.1 and using the wind speed of 140 mph, is the asphalt shingle product classified as ASTM D3161 Class F or TAS 107 qualifying for this project?

Background:

1.      Project description/Situation: The Petitioner is a State of Florida certified roofing contractor and in the process of providing a roofing quotation for a project located in Broward County, wind zone of 140 having and exposure C category and a roof mean height of 22 feet.  The specified roof covering is asphalt shingles.

 

2.      2007 Florida Building Code:

 

    1507.2.10 Wind Resistance of Asphalt Shingles. Asphalt Shingles shall be classified in accordance with ASTM D3161, TAS 107 or ASTM D7158 to resist the basic wind speed per Figure 1609. Shingles classified as ASTM D3161 Class D or ASTM D7158 Class G are acceptable for use in the 100-mph wind zone. Shingles classified as ASTM D3161 Class F, TAS 107 or ASTM D 7158 Class H are acceptable for use in all wind zones. Asphalt shingle wrappers shall indicate compliance with one of the required classifications as shown in Table 1507.2.10.

TABLE 1507.2.10 WIND RESISTANCE OF ASPHALT SHINGLES

MAXIMUM BASIC WIND
SPEED
MPH (per Figure 1609)

CLASSIFICATION

100

ASTM D 3161 Class D or ASTM D 7158
Class G or TAS 107

110

ASTM D 3161 Class F or ASTM D 7158
Class G or TAS 107

120

ASTM D 3161 Class F or ASTM D 7158
Class G or TAS 107

130

ASTM D 3161 Class F or ASTM D 7158
Class H or TAS 107

140

ASTM D 3161 Class F or ASTM D 7158
Class H or TAS 107

150

ASTM D 3161 Class F or ASTM D 7158
Class H or TAS 107

 

Staff recommendation:

Question: For the project in question and using the Table 1507.2.7.1 and using the wind speed of 140 mph, is the asphalt shingle product classified as ASTM D3161 Class F or TAS 107 qualifying for this project?

Answer: Yes.  According to Section 1507.2.10, shingles classified as ASTM D3161 Class F, TAS 107 or ASTM D7158 Class H is acceptable for use in all wind speed zones.