Minutes
FLORIDA BUILDING COMMISSION
Fire Technical Advisory Committee
February 5, 2007
3:00 P.M - 5:00 P.M.
Embassy Suites Hotel
3705 Spectrum Boulevard
Tampa , Florida 33612
813-977-7066
Meeting Objective:
1 Call to Order review/approve agenda and minutes.
Fire TAC Nick D'Andrea, Chairman
Joe Belcher, Jeff Gross, Brad Schiffer, James Goodloe, and Jim Schock.
2 Discuss and provide recommendation on the following request for Declaratory Statement:
DCA07-DEC-002 by Kari Hebrank, with the 4 th Floor Advocacy
Question: Is the 975 gallon maximum allowable quantity limit for corrosive liquids shown in Table 414.2.4 modified by the provisions contained in Note f to said table, thus allowing maximum capacity of 1,950 gallons of liquid if the provisions of the Florida Fire Prevention Code for an outside control area have been satisfied.
Answer: Yes. Table 414.2.4 of the Florida Building Code Building, allows maximum quantities of 975 gallons with an increase of 100 percent in outdoor control areas in accordance with Section 414.6.
Issue: DCA07-DEC-011. The petitioner Mr. Billy Tyson, CBO, is requesting an interpretation of Section 703.4.1 and Chapter 35 ASTM E 136 of the Florida Building Code, Building.
Question 1: Does the CBPB flooring element have to be noncombustible in Type II-B construction?
Answer: yes, in Type IIB construction, flooring assembly is required to be noncombustible.
Question 2: Does CBPB tested to ASTM E-136 with a modified ten (10) minute test comply with the Florida Building Code requirement for noncombustibility?
Answer: No. Neither the code or the standards allow for modification of ASTM E -136. Thus the product in question is combustible.
3 Adjourn at 3:30 PM.