DRAFT
ENERGY
CODE GUIDELINES FOR
EXISTING
BUILDING REPLACEMENT SYSTEMS
SUBJECT |
RENOVATION3/ALTERATION |
BUILDING SYSTEMS1,2,3 |
|
HVAC equipment replacement |
|
Duct sealing |
Residential:
At the time of total replacement of HVAC evaporators and condensing units, all accessible (min. 30” clearance) joints and seams in the air distribution system shall be inspected and sealed where needed; certified by contractor.
Commercial/Residential: This provision does not apply to partial replacement of equipment. |
Sizing calculation |
An a/c contractor or licensed Florida PE shall submit a nationally recognized method based sizing calculation to the code official at the time of permit application for total replacement of the condensing and evaporator components of HVAC systems in accordance with Florida law and the provisions of Sec. 403.6.2.2 or 403.6.2.3. Residential: 1. Several “nationally recognized” sizing calculation methods for existing buildings are available from HVAC equipment manufacturers. Approval by code official. 2. Per Section 101.54 of the FBC-EB, original systems installed on buildings constructed under the 1993 Energy Code or later have already been sized for the building and, without changes to the building, may be assumed to have been sized per code. 3. If a copy of a previous sizing calculation is provided, it is deemed to meet code. Commercial/Residential: This provision does not apply to partial replacement of equipment. |
Duct testing |
Residential Replacement or extension of an existing air distribution system is not required to be tested. |
RENOVATIONS1,5,7 |
|
Windows |
If cost of job exceeds 30% of assessed value of structure, meet Sec. 402 requirements. If cost of job does not exceed 30% of assessed value of structure, don’t have to meet Energy Code requirements. |
Pool filtration pumps6 |
If cost of job exceeds 30% of assessed value of structure, meet Sec. 403.9.4 requirements If cost of job does not exceed 30% of assessed value of structure, don’t have to meet Energy Code requirements. |
In general, Florida law trumps what’s in the code. Florida law has been incorporated into the FBC-Energy Conservation in Table 101.4.1.
Ducts & AHU
installed substantially leak free per Section 403.2.2.1. Test by Class 1 BERS
rater required.
Exception: Ducts
installed onto an existing air distribution system as part of an addition or
renovation; duct must be R-6 installed per Sec. 503.2.7.2