Proposal 1:
Remove the requirement of a projection factor of 0.5 for prescriptive measures for shell buildings
TABLE 502.1.1.1 (1)
ENVELOPE PRESCRIPTIVE MEASURES FOR SHELL BUILDINGS1,2
Building Element |
Mandatory |
Roof: Absorptance R-value (U-value) |
≤ 0.22 R-40 (≤U-0.025) |
Wall: Above grade
wall: Absorptance R-value (U-value) Below grade wall: |
≤ 0.3 R-30 (≤ U-0.032) No
requirement |
Raised Floor Insulation R-value (U-value) |
R-30 (≤ U-0.032) |
Window: U-factor SHGC 0-40% WW Ratio 40-50% WW Ratio >
50% WW Ratio Overhang Projection Factor (PF) |
≤ 0.45 0.25 0.19 Not allowed3
|
Door: U-value Swinging
Non-swinging |
U-0.70 U-1.45 |
Skylights: SHGC Skylight U-value |
≤ 0.19 ≤ 1.36 |
1Equipment and
lighting shall meet the efficiencies of Section 503, 504 and 505, respectively.
2Per Section
101.4.9 of the FBC-EC, the building
shall demonstrate compliance with Section 506 when completion of the building
is permitted.
3Buildings with greater than 50%
WW Ratio shall comply with Section 506.
4 PF 0.5 =
Projection half the distance of window height.
Justification: A projection factor will not provide enough return on investment in terms of energy savings for fenestration having SHGC values as low as 0.25.
Proposal 2:
A new renovations/alterations prescriptive values table is proposed for the 2010 Florida Building Energy Code. The proposed table is as below:
TABLE 502.1.1.1 (2)
ENVELOPE PRESCRIPTIVE MEASURES
FOR RENOVATIONS AND ALTERATIONS1
Building Element |
Mandatory |
Roof: Absorptance R-value
(U-value) |
≤ 0.22
|
Exterior Wall: Above grade wall: Absorptance R-value (U-value) Below
grade wall: |
≤ 0.3
No
requirement |
Raised Floor Insulation
R-value (U-value) |
|
Window:
U-factor
SHGC (by window area) 0-40%
WW Ratio >40 WW Ratio |
≤ 0.45 0.25
|
Skylights:
SHGC
Skylight U-value |
≤ 0.19 ≤ 1.36 |
Opaque Door U-value Swinging
Non-swinging |
≤ U-0.7 ≤ U-1.45 |
Justification for suggested changes:
1) Roof R-value change: Justification is that both the latest ASHRAE and IECC codes have those as the maximum recommended values. Also, during the analysis conducted earlier, it was found that there are clearly diminishing returns for increasing R-values for the roof beyond this number
2) Wall R-value change: Justification is that both the latest ASHRAE and IECC codes have those as the maximum recommended values. Also, during the analysis conducted earlier, it was found that there are clearly diminishing returns for increasing R-values for the exterior walls beyond this number
3) Floor R-value change: Justification is that the latest ASHRAE and IECC codes have R-19 as the maximum recommended insulation.
4) SHGC: SHGC was changed to accommodate suggestions that very low SHGC values impede visible light transmittance (VLT) leading to curtailment of daylighting as a viable energy saving measure
Proposal 3:
[MX1]Should we restrict this to climate zone 2 only?