DS2012-039 STAFF ANALYSIS
ISSUE: DS2012-039. Petitioner seeks a Declaratory Statement on an interpretation of Table 402.1.1.3 of the Florida Building Code, Energy Conservation.
Petitioner in DS2012-039 seeks
clarification of the following questions:
1a. Are the Equivalent U-Factors given in Table
402.1.1.3 of the FBC-EC for mass walls correct?
1b. If the answer is YES, then what is the
basis of this determination, considering that the U-Factor of a mass wall
component is technically deemed to represent the thermal transmittance of the
entire mass wall composite, including all materials and the internal and
external air film transmittances of the component?
1c. If the answer is NO, then how will Table
402.11.3 of the FBC-EC be modified to correct the Equivalent U-Factors for mass
walls?
Situation:
The Florida Solar Energy Center has submitted its
EnergyGauge USA v 3.0 code compliance software for approval as a UA Alternative
code compliance calculation method. On implementing the UA Alternative method
into EnergyGauge USA as prescribed by the FBC-EC, an
inconsistency in the mass wall Equivalent U-Factors given in Table 402.1.1.3
became apparent. Petitioner seeks remediation of this UA Alternative
inconsistency in order that the UA Alternative becomes equivalent to the
performance-based method in Section 405 of the code.
Petitioner maintains that the problem is that Table
402.1.1.3 of the FBC-EC for the U-Factor alternative is
technically incorrect with respect to the minimum Component R-Values prescribed
by Table 402.1.1. This is evidenced by the nationally-accepted engineering
standard of practice provided in Chapter 27 of the ASHRAE Handbook
of Fundamentals. It is also evidenced by the fact that the method used to
determine the Equivalent U-Factor for mass walls in Table 402.1.1.3 of the FBC-EC differs from the
method used in the 2009 IECC.
Also, the Florida Building Commission has adopted the
principle of equivalence between Florida Code compliance methods, meaning that
the performance-based simulation method, the Equivalent U-Factor method and the
UA Alternative method should all be equivalent. In order to achieve this
equivalence, it is necessary that the U-Factors for mass walls be the same for
all methods.
Background:
1. Table 402.1.1 provides required prescriptive component R-values for mass walls as R-6 for exterior mass wall insulation application and R-7.8 for mass wall applications with 50 percent or more of the insulation applied on the interior of a mass wall. Likewise, Table 402.1.1.3 of the FBC-EC provides Equivalent U-Factors of 0.124 and 0.165 for interior and exterior mass wall insulation applications, respectively. These Equivalent U-Factors are permitted as an alternative compliance method (see Section 402.1.1.2) to the R-Value requirements of Table 402.1.1.
2. The mass wall U-Factors provided in Table 402.1.1.3 are not equivalent to the component R-Values provided in Table 402.1.1. Section 402.1.1.1 provides the definition of the component R-Values to which Table 402.1.1 applies as follows:
“402.1.1.1 R-value computation. Insulation material used in layers, such as framing cavity insulation and insulating sheathing, shall be summed to compute the component R-value. The manufacturer’s settled R-value shall be used for blown insulation. Computed R-values shall not include an R-value for other building materials or air films.” (emphasis added).
While Section 402.1.1.2 of the FBC-EC does not provide a definition for Equivalent U-Factor, it is widely accepted in engineering practice as the composite thermal transmittance of the building component form the interior air to the exterior air, including all materials within the building component and the air film resistances of the interior and exterior air films bounding the component. An example and discussion of the calculation of concrete block mass wall U-Factors using the parallel path and isothermal planes methods is provided by the 2009 ASHRAE Handbook of Fundamentals, Chapter 27, page 27.4.
3. Examination of Tables 402.1.1 and 402.1.3 in the 2009 International Energy Conservation Code (IECC) illustrates this basic difference between R-values and Equivalent U-Factors. IECC Table 402.1.1 prescribes R-Values for mass wall applications as R-3 for exterior applications and R-4 for applications where more than 50 percent of the insulation is on the mass wall interior (climate zone 1). IECC Table 402.1.3 provides Equivalent U-Factors of 0.197 and 0.17 for these exterior and interior insulation applications, respectively. Since thermal resistance and thermal transmittance are inversely related, the FBC-EC assumes that the Equivalent U-Factor is equal to the simple reciprocal of the insulation R-Value. However, examination of the 2009 IECC tables shows that this is not the case for the IECC.
In the 2009 IECC, the reciprocal of the R-3 exterior mass wall application in IECC Table 402.1.1 equals 0.333 yet the alternative Equivalent U-Factor given in IECC Table 402.1.3 is 0.197 (which is equivalent to an overall composite wall R-value, including air films, of 5.08). For the interior application, the simple reciprocal of R-4 is 0.25 while the IECC Table 402.1.3 Equivalent U-Factor is given as 0.17 (which is the equivalent to an overall composite wall R-value, including air films, of R-5.88). Thus, there is not a one-to-one reciprocal relationship between the component R-Value requirements of IECC Table 402.1.1 and the alternative Equivalent U-Factors of IECC Table 402.1.3. Therefore, the FBC-EC, which uses a one-to-one reciprocal relationship between the component R-Value and alternative Equivalent U-Factor, is not consistent with the methods employed in the 2009 IECC.
This same principle, albeit somewhat different for frame construction, is also in evidence for all other construction components listed in IECC Tables 402.1.1 and 402.1.3, where the simple reciprocal of the component insulation R-Value listed in IECC Table 402.1.1 is never used as the Equivalent U-Factor listed in IECC Table 402.1.3.
4. EnergyGauge USA FlaRes, which is a detailed DOE-2-based, detailed hourly simulation model, has functioned as Florida’s performance-based Code compliance software tool for a dozen years. It was used in the development of the 2010 FBC-EC to determine the equivalence between R-13 frame wall construction, which is the Florida baseline assumption (standard reference design) and CMU (Concrete Masonry Unit) construction throughout Florida. In order to conduct this evaluation, it was necessary to model typical Florida CMU construction in detail. Table 1 below provides the detailed construction and thermal resistance characteristics used to model typical Florida CMU construction in EnergyGauge USA v 3.0, which is now a Florida Building Commission-accredited Florida Code compliance software tool.
Table 1. Calculation of Typical Florida
Mass Wall U-Factors
Component Thermal Resistances |
Insulation
Position |
|
Inside |
Outside |
|
Exterior air film R-value |
0.17 |
0.17 |
Stucco R-value |
0.1999 |
0.1999 |
Exterior insulation R-value |
0 |
6 |
Concrete block R-value |
1.1002 |
1.1002 |
Interior insulation R-value |
7.8 |
0 |
Air space R-value |
0 |
0.92 |
Drywall R-value |
0.4508 |
0.4508 |
Interior air film R-value |
0.68 |
0.68 |
Composite R-value (in
series) |
10.4009 |
9.5209 |
U-Factor (1/R-composite) |
0.096146 |
0.105032 |
Staff Recommendations: Based on the above facts and circumstances, staff provides the following recommendations as answers to proponent’s questions:
Question1:
To the question (part a), Are the
Equivalent U-Factors given in Table 402.1.1.3 of the FBC-EC for mass walls
correct? Answer to this question
using the declaratory statement process is not possible. Further evaluation and
determination of this concern should be deferred for consideration during the code
change process.
To the question (part b), If the
answer is YES, then what is the basis of this determination, considering that
the U-Factor of a mass wall component is technically deemed to represent the
thermal transmittance of the entire mass wall composite, including all
materials and the internal and external air film transmittances of the
component? the answer is NA.
To the question (part c), If the
answer is NO, then how will Table 402.1.1.3 of the FBC-EC be modified to
correct the Equivalent U-Factors for mass walls? For answer to this question see answer to Question
(part a).