2010 ENERGY CODE FIXES: RULE 61G20.1.001
|
TEXT |
RATIONALE |
|||||
15 |
B-2.6 HVAC systems B-2.6.1 Standard reference design. [1 – 7, 10 No change, changes for 8 previously dealt with under 13] 9. The equipment
capacities for the standard reference design shall be sized
proportionally to the capacities in the proposed design based on
sizing runs; i.e., the ratio between the capacities used in the annual
simulations and the capacities determined by the sizing runs shall be the
same for both the proposed design and standard reference design.
|
Unintended results from the integration of previously adopted Florida-specific amendments with the model code. These Florida-specific clauses which were adopted from Chapter 11 of ASHRAE 90.1 were not previously in the code or in the program. By including them designers, in some cases, are facing an unanticipated increase in overall stringency of the code and, in other cases, there is potential of decreased stringency. |
|||||
16 |
TABLE B-2.2 SPECIFICATIONS FOR THE STANDARD REFERENCE AND PROPOSED
DESIGNS
|
Unintended results from the integration of previously adopted
Florida-specific amendments with the model code. These Florida-specific clauses which were
adopted from Chapter 11 of ASHRAE 90.1 were not previously in the code or in
the program. By including them, there is the potential of unintentionally decreasing
in stringency in some cases. |
|||||
17 |
TABLE 504.2 MINIMUM PERFORMANCE OF WATER-HEATING EQUIPMENT
|
Equivalency of standards. When updating Table 504.2 to ASHRAE 90.1-2010, a typographical error
was made which should be corrected. |