2010 ENERGY CODE FIXES: RULE 61G20.1.001
| 
   | 
  
   TEXT  | 
  
   RATIONALE  | 
 |||||
| 
   15  | 
  
   B-2.6 HVAC systems B-2.6.1 Standard reference design. [1 – 7, 10 No change, changes for 8 previously dealt with under 13] 9. The equipment
  capacities for the standard reference design shall be sized
  proportionally to the capacities in the proposed design based on
  sizing runs; i.e., the ratio between the capacities used in the annual
  simulations and the capacities determined by the sizing runs shall be the
  same for both the proposed design and standard reference design.
    | 
  
   Unintended results from the integration of previously adopted Florida-specific amendments with the model code. These Florida-specific clauses which were adopted from Chapter 11 of ASHRAE 90.1 were not previously in the code or in the program. By including them designers, in some cases, are facing an unanticipated increase in overall stringency of the code and, in other cases, there is potential of decreased stringency.  | 
 |||||
| 
   16  | 
  
   TABLE B-2.2 SPECIFICATIONS FOR THE STANDARD REFERENCE AND PROPOSED
  DESIGNS 
  | 
  
   Unintended results from the integration of previously adopted
  Florida-specific amendments with the model code.  These Florida-specific clauses which were
  adopted from Chapter 11 of ASHRAE 90.1 were not previously in the code or in
  the program. By including them, there is the potential of unintentionally decreasing
  in stringency in some cases.  | 
 |||||
| 
   17  | 
  
   TABLE 504.2 MINIMUM PERFORMANCE OF WATER-HEATING EQUIPMENT 
  | 
  
   Equivalency of standards. When updating Table 504.2 to ASHRAE 90.1-2010, a typographical error
  was made which should be corrected.  |