NEEDED
2010 ENERGY CODE FIXES: Public Comment
| 
   18  | 
  
   403.1 Controls  403.1.1
  Thermostat Provision (Mandatory).  At least one
  thermostat shall be provided for each separate heating and cooling system. 403.1. 403.1.  403.1. ------------- 401.2 Compliance. Projects shall comply with Sections 401,
  402.4, 402.5, and 403.1.1, 403.1.3, 403.1.4,
  403.2.2, 403.2.3, and 403.3 through 403.9 (referred to as the mandatory
  provisions) and either: 1.
  Sections 402.1 through 402.3, 403.1.2, 403.2.1 and 404.1
  (prescriptive); or 2.
  Section 405 (performance).  | 
  
   Conflicts within the
  updated code. Although Section 403.1,
  Controls, is labeled as Mandatory, it is unclear whether all control
  requirements are. Table B-1.1.2(1) allows controls other than programmable
  thermostats to be used. The proposed language would clarify that programmable
  thermostats are Prescriptive for compliance by Section 402.1, Compliance,
  rather than to compliance by Section 405 (performance). Changes are also
  proposed to Section 401.2 to clarify this conflict of code issue. Conflicts
  within the updated code. Submitted by the Florida
  Solar Energy Center.  | 
 ||||||
| 
   19  | 
  
   TABLE B-1.1.2(1) [rest of the table
  remains the same] SPECIFICATIONS FOR TH ESTANDARD
  REFERENCE AND PROPOSED DESIGNS 
  | 
  
   Conflicts within the
  updated code. When Florida’s baseline
  features were transferred to the FBC-EC,
  the design features for programmable thermostats contained in the EG USA
  computer program were not included in Table B-1.1.2(1). EG USA uses the
  indicated setback schedule to provide consistent credit for use of this
  device, which should be specified here to provide for consistency among code
  compliance software programs. Submitted by the Florida Solar Energy Center.  | 
 
| 
   20  | 
  
   405.6.6  Installation criteria for homes using the
  ceiling fan option. The ceiling fan option shall apply a 2% reduction
  in cooling energy use for the proposed design if one or more ceiling fans are
  installed in each of the bedrooms and a minimum of one ceiling fan is
  installed in all primary living areas (living rooms, family rooms, or great
  rooms). This shall not include spaces designed to be dining rooms or dining
  areas. Areas separated by permanently fixed archways, walls, or dividers
  shall be considered separate rooms. The following criteria shall be met: 1. Ceiling fans shall be installed with minimum
  fan blade diameters of no less than those listed in Table 405.6.5 for the
  size and shape of the room. 2. Where a primary living area is an
  "L-shaped" room and the smaller portion of this area is 8 feet by
  10 feet (2438 mm by 3048 mm) or larger, a fan shall be installed in both the
  larger and smaller portions of the primary living area. Exception:
  Credit shall not be taken for both ceiling fans and cross ventilation. TABLE
  405.6.6 FAN SIZING TABLE 
                            For SI: 1 inch =
  25.4mm, 1 foot = 304.8 mm. [Renumber section 405.6.6
  to 405.6.7 and renumber section 405.6.7 to 405.6.8.]  | 
  
   Unintended results from the integration of previously adopted Florida-specific amendments with the model code. The included language for ceiling fans has been in the energy code for years; it appears to have been unintentionally left out of the 2010 FBC- Energy Conservation. Submitted by
  the Florida Solar Energy Center.  | 
 ||||||||||||
| 
   | 
  
   | 
  
   |