NEEDED
2010 ENERGY CODE FIXES: Public Comment
18 |
403.1 Controls 403.1.1
Thermostat Provision (Mandatory). At least one
thermostat shall be provided for each separate heating and cooling system. 403.1. 403.1. 403.1. ------------- 401.2 Compliance. Projects shall comply with Sections 401,
402.4, 402.5, and 403.1.1, 403.1.3, 403.1.4,
403.2.2, 403.2.3, and 403.3 through 403.9 (referred to as the mandatory
provisions) and either: 1.
Sections 402.1 through 402.3, 403.1.2, 403.2.1 and 404.1
(prescriptive); or 2.
Section 405 (performance). |
Conflicts within the
updated code. Although Section 403.1,
Controls, is labeled as Mandatory, it is unclear whether all control
requirements are. Table B-1.1.2(1) allows controls other than programmable
thermostats to be used. The proposed language would clarify that programmable
thermostats are Prescriptive for compliance by Section 402.1, Compliance,
rather than to compliance by Section 405 (performance). Changes are also
proposed to Section 401.2 to clarify this conflict of code issue. Conflicts
within the updated code. Submitted by the Florida
Solar Energy Center. |
||||||
19 |
TABLE B-1.1.2(1) [rest of the table
remains the same] SPECIFICATIONS FOR TH ESTANDARD
REFERENCE AND PROPOSED DESIGNS
|
Conflicts within the
updated code. When Florida’s baseline
features were transferred to the FBC-EC,
the design features for programmable thermostats contained in the EG USA
computer program were not included in Table B-1.1.2(1). EG USA uses the
indicated setback schedule to provide consistent credit for use of this
device, which should be specified here to provide for consistency among code
compliance software programs. Submitted by the Florida Solar Energy Center. |
20 |
405.6.6 Installation criteria for homes using the
ceiling fan option. The ceiling fan option shall apply a 2% reduction
in cooling energy use for the proposed design if one or more ceiling fans are
installed in each of the bedrooms and a minimum of one ceiling fan is
installed in all primary living areas (living rooms, family rooms, or great
rooms). This shall not include spaces designed to be dining rooms or dining
areas. Areas separated by permanently fixed archways, walls, or dividers
shall be considered separate rooms. The following criteria shall be met: 1. Ceiling fans shall be installed with minimum
fan blade diameters of no less than those listed in Table 405.6.5 for the
size and shape of the room. 2. Where a primary living area is an
"L-shaped" room and the smaller portion of this area is 8 feet by
10 feet (2438 mm by 3048 mm) or larger, a fan shall be installed in both the
larger and smaller portions of the primary living area. Exception:
Credit shall not be taken for both ceiling fans and cross ventilation. TABLE
405.6.6 FAN SIZING TABLE
For SI: 1 inch =
25.4mm, 1 foot = 304.8 mm. [Renumber section 405.6.6
to 405.6.7 and renumber section 405.6.7 to 405.6.8.] |
Unintended results from the integration of previously adopted Florida-specific amendments with the model code. The included language for ceiling fans has been in the energy code for years; it appears to have been unintentionally left out of the 2010 FBC- Energy Conservation. Submitted by
the Florida Solar Energy Center. |
||||||||||||
|
|
|