CARBON MONOXIDE DETECTORS
CS/CS/SB 1822 ENROLLED
Section 1. Subsection (5) is added to
section 509.211,
22 Florida Statutes, to
read:
23 509.211
Safety regulations.--
24
(5) Every enclosed space or room that contains a
25
boiler regulated under chapter 554 which is fired by the
26
direct application of energy from the combustion of fuels and
27
that is located in any portion of a public lodging
28
establishment that also contains sleeping rooms shall
be
29
equipped with one or more carbon monoxide sensor devices that
30 bear the label of a
nationally recognized testing laboratory
31 and have been tested and
listed as complying with the most
1 recent Underwriters Laboratories, Inc., Standard
2034, or its
2 equivalent, unless it is determined
that carbon monoxide
3 hazards have otherwise been adequately mitigated as
determined
4 by the division. Such devices shall be integrated with
the
5 public lodging establishment's fire detection
system. Any such
6 installation or determination shall be
made in accordance with
7 rules adopted by the division.
8 Section 2. Section 553.885, Florida Statutes, is
9 created to read:
10 553.885
Carbon monoxide alarm required.--
11
(1) Every building for which a building permit is
12
issued for new construction on or after July 1, 2008, and
13
having a fossil-fuel-burning heater or appliance, a fireplace,
14
or an attached garage shall have an approved operational
15
carbon monoxide alarm installed within 10 feet of each
room
16
used for sleeping purposes.
17
(2) The Florida Building Commission shall adopt rules
18
to administer this section and shall incorporate such
19
requirements into its next revision of the
20
Code.
21 (3) As
used in this section, the term:
22 (a) "Carbon monoxide
alarm" means a device that is
23 meant for the purpose of
detecting carbon monoxide, that
24 produces
a distinct audible alarm, and that
CS/CS/SB 1822 Carbon Monoxide Detectors
Action required:
1)
Adopt a rule to require CO
detectors in buildings with fossil fuel burning heater or appliance (including
boiler in public lodging), fireplace, or attached garage and rooms used for
sleeping purposes effective by July 1,2008.
2)
Include requirements in next
revision/(edition) of FBC.
3) Work with DBPR on chapter 4, FBC, Building requirements for public
lodging buildings with both sleeping rooms and
combustion fired boilers in the building.