(E6460 AS)

Chapter 27 – Electrical Systems

Option #1: No change – keep as is

Section 2703 Lightning Protection

2703.1 Lightning Protection. A lightning protection system shall be provided for all new buildings and additions in accordance with NFPA 780, Standard for the Installation of Lightning Protection Systems.

2703.2 Where additions are constructed to existing building, the existing building’s lightning protection system, if connected to the new lightning protection system, shall be inspected and brought into compliance with current standards.

2703.3 Surge protection devices shall be installed for all normal and emergency electrical systems in accordance with NFPA 70, National Electrical Code.

Exceptions:

1. One- and two-family dwellings

2. Lightning protection shall not be required for any building or addition where shown unnecessary by evaluation using the Risk Assessment Guide in NFPA 780, Standard for the Installation of Lightning Protection Systems or an alternative method approved by the authority having jurisdiction.

Option #2: Revise as follows:

Section 2703 Lightning Protection

2703.1 Lightning Protection. A lightning protection system shall be provided for all new buildings and additions in accordance with NFPA 780, Standard for the Installation of Lightning Protection Systems, UL 96A, Installation Requirements for Lightning Requirement, HBP-21 or other alternative equivalent standard for the installation of  lightning protection systems.

2703.2 Where additions are constructed to existing building, the existing building’s lightning protection system, if connected to the new lightning protection system, shall be inspected and brought into compliance with current standards.

2703.3 Surge protection devices shall be installed for all normal and emergency electrical systems in accordance with NFPA 70, National Electrical Code.

Exceptions:

1. One- and two-family dwellings

2. Lightning protection shall not be required for any building or addition where shown unnecessary by evaluation using the Risk Assessment Guide in NFPA 780, Standard for the Installation of Lightning Protection Systems or an alternative method approved by the authority having jurisdiction.

Option #3: Delete Section 2703 as follows:

Section 2703 Lightning Protection. 

Section 2703 Lightning Protection

2703.1 Lightning Protection. A lightning protection system shall be provided for all new buildings and additions in accordance with NFPA 780, Standard for the Installation of Lightning Protection Systems.

2703.2 Where additions are constructed to existing building, the existing building’s lightning protection system, if connected to the new lightning protection system, shall be inspected and brought into compliance with current standards.

2703.3 Surge protection devices shall be installed for all normal and emergency electrical systems in accordance with NFPA 70, National Electrical Code.

Exceptions:

1. One- and two-family dwellings

2. Lightning protection shall not be required for any building or addition where shown unnecessary by evaluation using the Risk Assessment Guide in NFPA 780, Standard for the Installation of Lightning Protection Systems or an alternative method approved by the authority having jurisdiction.