First Hearing- Legal Report:
DCA10-DEC-059 by Paul
T. Myers, Building Official of Putnam County.
TAC action: Recommend dismissal due to the lack of
jurisdiction.
DCA10-DEC-146 by Gary
Harrison, Building Official of Collier County
TACs action:
Question One: Would these type structures be included in the classification as residential in accordance with FBC 2007 Residential?
Answer: Yes. The structure provides two sleeping (bunk) rooms. See section 310.1. (Emphasis added)
Question Two: If they are considered residential, even though they will be used on a part time basis (2 weeks per year), would they still be required to meet all the criteria as set forth in the code?
Answer: Yes. The applicability of the code is not based on how long a structure is occupied. The only buildings or structures exempt from the code are as provided in section 102.2 of the FBC.
Question Three: Would the building be defined as living and habitable space i.e. sleeping, eating, and bathing. Heating and sanitation purposes, as set forth in FBC 2007 Residential
Answer: Yes.
Question Four: If the answer to the above questions is yes, then would it also have to meet all the requirements as set forth in NEC 2008 for residential construction?
Answer: Yes. The FBC, Residential Code, Chapter 33 references the NFPA 70 (National Electric Code)