2012 SUPPLEMENT TO THE FLORIDA BUILDING CODE, ENERGY CONSERVATION

 

Chapter 1 - Administration

Limit scope of Section 101.4.7.1 and 101.4.7.2 to residential buildings as follows: 

101.4.7.1 Replacement HVAC equipment

101.4.7.1.1 Duct sealing upon equipment replacement (Mandatory). At the time of the total replacement of HVAC evaporators and condensing units for residential buildings, all accessible (a minimum of 30 inches clearance) joints and seams in the air distribution system shall be inspected and sealed where needed using reinforced mastic or code approved equivalent and shall include a signed certification by the contractor that is attached to the air handler unit stipulating that this work has been accomplished.

            Exceptions:
            1. Ducts in conditioned space.
            2. Joints or seams that are already sealed with fabric and mastic.
            3. If system is tested and repaired as necessary.

101.4.7.1.2 Replacement equipment sizing (Mandatory). An A/C contractor or licensed Florida PE shall submit a nationally recognized method based sizing calculation to the code official at the time of permit application for total replacement of the condensing and evaporator components of HVAC systems for residential buildings in accordance with Florida law and the provisions of Section 403.6.1 or Section 503.2.1, as applicable.

 

Reorganize exempt building section and add Florida-specific exemptions from previous code as follows:

101.4.8 Exempt buildings. Buildings exempt from the provisions of the Florida Building Code, Energy Conservation, include existing buildings except those considered renovated buildings, changes of occupancy type, or previously unconditioned buildings to which comfort conditioning is added.  Exempt buildings include those specified in Sections 101.4.8.1 through 101.4.8.5.

 101.4.8.1 Federal standards. Any building for which federal mandatory standards preempt state energy codes

101.4.8.2 Hunting or recreational buildings < 1,000 square feet. Any building of less than l,000 square feet (93 m2) whose primary use is not as a principal residence and which is constructed and owned by a natural person for hunting or similar recreational purposes is exempt from this code; however, no such person may build more than one exempt building in any 12-month period. 

101.4.8.3 Historic buildings. Any building meeting the criteria for historic buildings in Section 101.4.2.

101.4.8.4 Low energy buildings as described in Section 101.5.2.   Such buildings shall not contain electrical, plumbing or mechanical systems which have been designed to accommodate the future installation of heating or cooling equipment.

101.4.8.5 Buildings designed for purposes other than general space comfort conditioning.  Any building where heating or cooling systems are provided which are designed for purposes other than general space comfort conditioning. Buildings included in this exemption include:

1.  Commercial service areas where only ceiling radiant heaters or spot coolers are to be installed which will provide heat or cool only to a single work area and do not provide general heating or cooling for the space.

2.  Buildings heated with a system designed to provide sufficient heat only to prevent freezing of products or systems. Such systems shall not provide heating above 50°F (10°C).

3.  Pre-manufactured freezer or refrigerated storage buildings and areas where the temperature is set below 40°F (4°C) and in which no operators work on a regular basis.

4.  Electrical equipment switching buildings which provide space conditioning for equipment only and in which no operators work on a regular basis except that the provisions of Section 505.7 shall apply.

5.  Buildings containing a system(s) designed and sold for dehumidification purposes only and controlled only by a humidistat. No thermostat shall be installed on systems thus exempted from this code.

 

 

 

Chapter 4 – Residential Energy Efficiency

Revise Section 401.2 as follows:

 

401.2 Compliance. Projects shall comply with Sections 401, 402.4, 402.5, and 403.1.1, 403.1.3, 403.1.4, 403.2.2, 403.2.3, and 403.3 through 403.9 (referred to as the mandatory provisions) and either:

1. Sections 402.1 through 402.3, 403.1.2, 403.2.1 and 404.1 (prescriptive); or

2. Section 405 (performance).

Revise Table 402.1.1.3 to correct mass wall U-factors as follows:

TABLE 402.1.1.3

EQUIVALENT U-FACTORSa,f,g

FENESTRATION U-FACTORe

SKYLIGHT U-FACTOR

CEILING

U-FACTORh

FRAME WALL

U-FACTORb

MASS WALL U-FACTOR

FLOOR

U-FACTOR

BASEMENT WALL

U-FACTORd

CRAWL SPACE

     WALL

U-FACTORc

0.65

0.75

0.035

0.082

0.096 0.124

0.064

0.360

   0.477

a. Nonfenestration U-factors shall be obtained from measurement, calculation or an approved source.

b. When more than half the insulation is on the exterior interior, the mass wall U-factors shall be a maximum of  0.105 0.165.

c. Basement wall U-factor of 0.360.

d. Foundation U-factor requirements shown in Table 402.1.1.3 include wall construction and interior air films but exclude soil conductivity and exterior air films. U-factors for determining code compliance in accordance with Section 402.1.1.3  (total UA alternative) shall be modified to include soil conductivity and exterior air films.

e. Window to floor area, including skylights, shall not exceed 20 percent. See Section 402.1.2.3.

f. Limitations to compliance by Section 402 found in Section 402.1.2 shall be met.

g. Ducts and air handlers shall be located inside both the thermal and air barrier of the home. Air leakage shall be no more than Qn=0.03 when tested per Section 403.2.2.1. 

h. Roof reflectance shall be no more than 0.25 in accordance with testing to Section 405.6.2.

Revise Section 403.1 as follows:

403.1 Controls (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.

403.1.1 Thermostat Provision (Mandatory).  At least one thermostat shall be provided for each separate heating and cooling system.

403.1.21 Programmable thermostat (Prescriptive). Where the primary heating system is a forced-air furnace, at least one thermostat per dwelling unit shall be capable of controlling the heating and cooling system on a daily schedule to maintain different temperature set points at different times of the day. This thermostat shall include the capability to set back or temporarily operate the system to maintain zone temperatures down to 55°F (13°C) or up to 85°F (29°C). The thermostat shall initially be programmed with a heating temperature set point no higher than 70°F (21°C) and a cooling temperature set point no lower than 78°F (26°C).

403.1.32 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.

 403.1.43 Humidity control (Mandatory). Where a humidistat is used for comfort dehumidification, it shall be capable of being set to prevent the use of fossil fuel or electricity to reduce humidities below 60 percent.

 

Change Section 403.2 as follows:

 

403.2  Ducts.

403.2.1 Insulation(Prescriptive) Supply and return ducts, including air filter enclosures, air ducts and plenums, located in attics or o roofs shall be insulated to a minimum of R-8. located inside the building thermal envelope and All other ducts shall be insulated to a minimum of R-6.

Exceptions:

1. Ducts or portions thereof located completely inside the building thermal envelope.

12. Exhaust air ducts

23. Factory-installed plenums, casings or ductwork furnished as a part of tested and rated HVAC equipment.

403.2.2 Sealing (Mandatory). All ducts, air handlers, filter boxes and building cavities which form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section 503.2.7.2 of this code and shall be shown to meet duct tightness criteria in Section 403.2.2.1.

403.2.2.1 Duct tightness.  Duct tightness shall be verified by testing to ASHRAE Standard 152 by either a Class 1 BERS rater or a Class A, B or Mechanical air-conditioning contractor. All ducts and air handlers shall be either located in conditioned space or tested by a Class 1 BERS rater to be “substantially leak free” by one of the following methods:

1. Post construction test: Leakage to outdoors shall be less than or equal to 3 cfm (84.9 L/min) per 100 ft2 (9.29 m2) of conditioned floor area and or a total leakage less than or equal to 9 cfm (254 L/min) per 100 ft2 (9.29 m2) of conditioned floor area when tested at a pressure differential of 0.1 inches w.g. (25 Pa) across the entire system, including the manufacturer’s air handler enclosure. All register boots shall be taped or otherwise sealed during the test.

2. Rough-in test:  Total leakage shall be less than or equal to 4 cfm (113.3 L/min) per 100 ft2 (9.29 m2) of conditioned floor area when tested at a pressure differential of 0.1 inches w.g. (25 Pa) across the roughed-in system, including the manufacturer’s air handler enclosure. All register boots shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test, total leakage shall be less than or equal to 2 cfm (56.3 L/min) per 100 ft2 (9.29 m2) of conditioned floor area.

Exception:  Duct testing is not mandatory for buildings complying by Section 405 of this code. 

 

 

Add Section 405.6.6 as follows:

 

405.6.6  Installation criteria for homes using the ceiling fan option. The ceiling fan option shall apply a 2% reduction in cooling energy use for the proposed design if one or more ceiling fans are installed in each of the bedrooms and a minimum of one ceiling fan is installed in all primary living areas (living rooms, family rooms, or great rooms). This shall not include spaces designed to be dining rooms or dining areas. Areas separated by permanently fixed archways, walls, or dividers shall be considered separate rooms. The following criteria shall be met:

1. Ceiling fans shall be installed with minimum fan blade diameters of no less than those listed in Table 405.6.5 for the size and shape of the room.

2. Where a primary living area is an “L-shaped” room and the smaller portion of this area is 8 feet by 10 feet (2438 mm by 3048 mm) or larger, a fan shall be installed in both the larger and smaller portions of the primary living area.

 

Exception: Credit shall not be taken for both ceiling fans and cross ventilation.

 

TABLE 405.6.6

FAN SIZING TABLE

LONGEST WALL LENGTH (feet)

MINIMUM FAN SIZE (inches)

≤ 12

36

> 12 – 16

48

> 16 – 17.5

52

> 17.5 – 25

56

> 25

2 fans (minimum

f 48 inches each)

                           For SI: 1 inch = 25.4mm, 1 foot = 304.8 mm.

 

[Renumber section 405.6.6 to 405.6.7 and renumber section 405.6.7 to 405.6.8.]

 

 

 

Chapter 5 – Commercial Energy Efficiency

Add reference to Section 502.1.1.1 as follows:

502.1.1.1 Shell buildings, renovations and alterations. The building thermal envelope shall meet the requirements of Table 502.1.1.1(1) or Table 502.1.1.1(2). See Section 101.4.3 and Section 101.4.9.

 

Change Tables 502.1.1.1(1) and 502.1.1.1(2) as follows:

TABLE 502.1.1.1 (1)

ENVELOPE PRESCRIPTIVE MEASURES FOR SHELL BUILDINGS1,2

[No change to rest of table]

Building Element

Mandatory Requirement

 

 

 TABLE 502.1.1.1 (2)

ENVELOPE PRESCRIPTIVE MEASURES FOR RENOVATIONS AND ALTERATIONS1

[No change to rest of table]

Building Element

Mandatory

Roof:

Absorptance

R-value (U-value)

 

≤0.22

R-38 (U≤ 0.027 0.033)

 

 

 

Revise Table 503.2.8 as follows:

TABLE 503.2.8

MINIMUM PIPE INSULATION (in.)1

Fluid Design Operating Temperature Range (oF)

Insulation Conductivity

Nominal Pi

pe or Tube Size (in.)

Conductivity

Btu in/(h ft2 .oF)

Mean Temperature

Rating

<1

1 - 1

½

1 ½ - 4

4 -8

>8

Heating Systems (Steam Condensate, and Hot Water)2,3

>350

0.32 - 0.34

250

2.5

3.0

3.0

4.0

4.0

251 – 350

0.29 - 0.32

200

1.5

2.5

3.0

3.0

3.0

201 – 250

0.27 - 0.30

150

1.5

1.5

2.0

2.0

2.0

141 – 200

0.25 - 0.29

125

1.01

1.0

1.0

1.5

1.5

105 – 140

0.22-0.28

100

0.5

0.5

1.0

1.0

1.0

Domestic and Service Hot Water Systems3

>105

0.22-0.28

100

0.5

0.5

1.0

1.0

1.0

Cooling Systems (Chilled Water, Brine, and Refrigerant)4

40 – 60

0.22-0.28

100

0.5

0.5 1.0

1.0

1.0

1.0

 <40

0.22-0.28

100

0.5

1.0 1.5

1.0 1.5

1.0

1.5

1For insulation outside the stated conductivity range, the minimum thickness (T) shall be determined as follows:

T=r{(1+t/r)K/k – 1}

Where T= minimum insulation thickness (in.), r=actual outside radius of pipe (in.), t=insulation thickness listed in this table for applicable fluid temperature and pipe size, K=conductivity of alternate material at mean rating temperature indicated for the applicable fluid temperature (Btu.in.[h.ft2.oF]; and k=upper value of the conductivity range listed in this table for applicable fluid temperature.

2These thicknesses are based on energy efficiency considerations only. Additional insulation is sometimes required relative to safety issues/surface temperatures.

3 Piping insulation is not required between the control valve and coil on run‐outs when the control valve is

located within 4 feet of the coil and the pipe size is 1 inch or less.

4 These thicknesses are based on energy efficiency considerations only. Issues such as water vapor

permeability or surface condensation sometimes require vapor retarders or additional insulation.

 

 

 

Fix Table 504.2 as shown:

 

TABLE 504.2

MINIMUM PERFORMANCE OF WATER-HEATING EQUIPMENT

[No other change to table]

Electric table top water heaters

≤ 12 kW

Resistance = 20 gal

0.93 - 0.00132V EF

DOE 10 CFR Part 430

 

 


NORMATIVE APPENDIX B:  CRITERIA FOR COMPUTER MODELING FOR PERFORMANCE-BASED CODE COMPLIANCE

 

Correct Table B-1.1.2(1) (Residential) as follows:

TABLE B-1.1.2(1)

SPECIFICATIONS FOR TH ESTANDARD REFERENCE AND PROPOSED DESIGNS

[No change to rest of table]

BUILDING COMPONENT

STANDARD REFERENCE DESIGN

PROPOSED DESIGN

Service water heating h,k

Fuel type: same as Proposed Design

Efficiency: in accordance with prevailing federal minimum standards

Use: (gal/day): 30 x Ndu + 10 x Nbr

Where Ndu = number of dwelling units

Tank temperature:  120o F

As proposed

As proposed

 

Same as standard reference design

As proposed

Same as standard reference design As proposed

Thermostat

Type:  Manual

Temperature setpoints

Cooling temperature setpoint = 780F

Heating temperature setpoint = 68oF

 

 

Type:  Same as proposed

Temperature setpoints:  same as the Standard Reference Design, except when programmable thermostats are used.

Programmable thermostat setpoints:

On weekdays cooling is 78oF from 3pm to 8:59am and 80oF from 9am to 2:59pm.  On weekends, cooling is 78oF for 24 hours.

Heating is 68oF from 6am to 10:59pm and 66oF from 11 pm to 5:59 am seven days a week.

 

 

Fix Section B-1.1.3.1 to make consistent with Section B-1.1.1 as follows:

B-1.1.3.1 Following normalization of the heating, cooling and hot water….If the total normalized modified loads of the Proposed Design home (nMEULtot) are equal to or less than 80 percent  of the total reference loads of the Standard Reference Design home (REULtot) the Proposed Design complies with this code.

 

Correct Section B-2.6 (Commercial) as follows:

B-2.6 HVAC systems

 

B-2.6.1 Standard reference design.

[1 – 7, 10 No change]

8.  Fan system efficiency (BHP per cfm of supply air including the effect of belt losses but excluding motor and motor drive losses) shall be the limit allowed in Table 503.2.10.1(1). same as the proposed design or up to the limit prescribed in Section 503.2.10.1,  whichever is smaller. If this limit is reached, each fan shall be proportionally reduced in brake horsepower until the limit is met. Fan electrical power shall then be determined by adjusting the calculated fan HP by the minimum motor efficiency prescribed by Section 505.7.5 for the appropriate motor size for each fan.

9. The equipment capacities for the standard reference design shall be sized proportionally to the capacities in the proposed design based on sizing runs; i.e., the ratio between the capacities used in the annual simulations and the capacities determined by the sizing runs shall be the same for both the proposed design and standard reference design. Unmet load hours for the proposed design shall not differ from unmet load hours for the standard reference design by more than 50 hours

Correct and add to Table B-2.2 (Commercial) as follows:

TABLE B-2.2

SPECIFICATIONS FOR TH ESTANDARD REFERENCE AND PROPOSED DESIGNS

[No change to rest of table]

BUILDING COMPONENT

STANDARD REFERENCE DESIGN

PROPOSED DESIGN

Building envelope

The standard reference design shall have identical conditioned floor area and identical exterior dimensions and orientations as the proposed design, except as noted in (a), (b), and (c) in this clause.

All components of the building envelope in the proposed design shall be modeled as shown on architectural drawings or as installed for existi7ng building envelopes.

Exceptions: The following building elements are permitted to differ from architectural drawings.

(a)   Opaque assemblies such as roof, floors, doors, and walls shall be modeled as having the same heat capacity as the proposed design but with the maximum minimum U-factor required in the Commission approved compliance software1 for new non-residential buildings or additions and alterations as shown below:

                                             CZ1              CZ2

Roof                                        

Insulation above deck     U-0.063    U-0.063 

Metal building                  U-0.065    U-0.065

Attic & other                     U-0.034    U-0.034

Walls, above-grade

Mass                                  U-0.580     U-0.580

Metal building                 U-0.113     U-0.113

Steel framed                    U-0.124     U-0.124

Wood framed & other   U-0.089     U-0.089

Walls, below grade                C-1.140     C-1.140

Floors      

Mass                                 U-0.322        U-0.137

Steel joist                         U-0.350        U-0.052

Wood framed & other   U-0.282        U-0.051

Slab-on-grade floors

Unheated                      F-0.730          F-0.730

Heated                           F-1.020          F-1.020

Opaque doors

Swinging                        U-0.700         U-0.700

Nonswinging                 U-1.450         U-1.450

 

High-rise residential buildings shall be modeled with the maximum U-factors shown below:

                                                  CZ1              CZ2

Roof 

Insulation above deck    U-0.063     U-0.063 

Metal building                 U-0.065     U-0.065

Attic & other                    U-0.027     U-0.034

Walls, above-grade

Mass                                 U-0.151      U-0.151

Metal building                U-0.113      U-0.113

Steel framed                   U-0.124       U-0.124

Wood framed & other   U-0.089      U-0.089

Walls, below grade               C-1.140       C-1.140

Floors                                

Mass                                 U-0.322        U-0.107

Steel joist                         U-0.350        U-0.052

Wood framed & other   U-0.282        U-0.051

Slab-on-grade floors

Heated                            F-0.730          F-0.730

Unheated                       F-1.020          F-1.020

Opaque doors

Swinging                        U-0.700          U-0.700

Nonswinging                 U-1.450          U-1.450

(a) Any envelope assembly that covers less than 5% of the total area of that assembly type (e.g., exterior walls) need not be separately described. If not separately described, the area of an envelope assembly must be added to the area of the adjacent assembly of that same type.

(b) Roof albedo—All roof surfaces shall be modeled with a reflectivity of 0.3.

 

(b)   Exterior surfaces whose azimuth orientation and tilt differ by no more than 45 degrees and are otherwise the same may be described as either a single surface or by using multipliers.

(c) Fenestration—No shading projections are to be modeled; fenestration shall be assumed to be flush with the exterior wall or roof. If the fenestration area for new buildings or additions exceeds 50% of wall area the maximum allowed by the Commission approved compliance software1, the area shall be reduced proportionally along each exposure until the following limits are set in the Commission approved compliance software1 is met.

 

% of wall area   Max.U       SHGC           CZ1    CZ 2

0 – 10%          Ufixed  1.22  SHGCall       0.25   0.39

                        Uoper  1.27  SHGCnorth  0.61   0.61

10.1 – 20%    Ufixed  1.22 SHGCall         0.25   0.25

                        Uoper  1.27  SHGCnorth  0.61   0.61

20.1 – 30%    Ufixed  1.22 SHGCall         0.25   0.25

                        Uoper  1.27  SHGCnorth  0.61   0.61

30.1 – 40%    Ufixed  1.22 SHGCall         0.25   0.25

                        Uoper  1.27  SHGCnorth  0.44   0.61

40.1 – 50%    Ufixed  1.22 SHGCall         0.19   0.17

                        Uoper  1.27  SHGCnorth  0.33   0.42

 

Fenestration U-factor shall be the maximum required for the climate, and the solar heat gain coefficient shall be the maximum allowed for the climate and orientation. The fenestration model for envelope alterations shall reflect the limitations on area, U-factor, and solar heat gain coefficient as allowed by Section 101.4.3.

(c) For exterior roofs other than roofs with ventilated attics, the roof surface may be modeled with a reflectance of 0.45 if the reflectance of the proposed design roof is greater than 0.70 and its emittance is greater than 0.75. The reflectance and emittance shall be determined by a laboratory accredited by a nationally recognized accreditation organization and shall be labeled and certified by the manufacturer. All other roof surfaces shall be modeled with a reflectance of 0.3.

Manually operated fenestration shading devices such as blinds or shades shall not be modeled. Permanent shading devices such as fins, overhangs, and light shelves shall be modeled.

 

Schedules

Same as proposed

Operating schedules shall include hourly profiles for daily operation and shall account for variations between weekdays, weekends, holidays and any seasonal operation. Schedules shall model the time-dependent variations in occupancy, illumination, receptacle loads, thermostat settings, mechanical ventilation, HVAC equipment availability, service hot water usage and any process loads. The schedules shall be typical of the proposed building type as determined by the designer and approved by the jurisdiction. Required schedules shall be identical for the proposed design and standard reference design.

 

 

APPENDIX C:  FORMS

 

Make the following changes to Table 402B of Form 402-2010 as follows: 

 

Table 402B    THERMAL ENVELOPE APPROACH MANDATORY REQUIREMENTS

Components

Section

Requirements

Check

Ceilings/knee walls

405.2.1

R-19 space permitting

 

Air distribution system

403.2

Ducts in attics or on roofs insulated to R-8; other ducts R-6. Shall be located in conditioned space, insulated to a minimum of R-6 and Ducts tested to a Qn=0.03 by a Class 1 BERS rater or a Class A, B or Mechanical air-conditioning contractor.

 

[No other changes made to table]