2009 IECC Based
2010
Chapter 1
Administration
Part
1 – SCOPE AND
APPLICATION
SECTION 101
SCOPE AND GENERAL REQUIREMENTS
101.1
Title. This code shall be known as the International Energy
Conservation Code of [NAME OF JURISDICTION], and shall be cited
as such. It is referred to herein as “this code.”
101.2 Scope. This code applies to residential and
commercial buildings. It is a statewide uniform code and shall not be made more stringent or
lenient by local government (553.901, F.S.).
101.3 Intent. This code shall regulate the design and construction of buildings for the effective use of energy. This code is intended to provide flexibility to permit the use of innovative approaches and techniques to achieve the effective use of energy. This code is not intended to abridge safety, health or environmental requirements contained in other applicable codes or ordinances.
101.4 Applicability. Where, in any specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall govern.
101.4.1 Existing buildings. Existing buildings shall meet the criteria in TABLE 101.4.1 as appropriate to the condition described. Except as specified in this chapter, this code shall not be used to require the removal, alteration or abandonment of, nor prevent the continued use and maintenance of, an existing building or building system lawfully in existence at the time of adoption of this code.
101.4.2 Historic buildings. Any building or
structure as described in Section 267.021, .that is (553.902 F.S.) listed in the State or National
Register of Historic Places; designated as a historic property under local or
state designation law or survey; certified as a contributing resource with a
National Register listed or locally designated historic district; or with an
opinion or certification that the property is eligible to be listed on the
National or State Registers of Historic Places either individually or as a
contributing building to a historic district by the State Historic Preservation
Officer or the Keeper of the National Register of Historic Places, are exempt
from this code.
101.4.3 Additions, alterations, renovations or repairs. Additions, alterations, renovations or repairs to an existing building, building system or portion thereof shall conform to the provisions of Table 101.4.1 of this code as they relate to new construction without requiring the unaltered portion(s) of the existing building or building system to comply with this code. Additions, alterations, renovations or repairs shall not create an unsafe or hazardous condition or overload existing building systems. An addition shall be deemed to comply with this code if the addition alone complies or if the existing building and addition comply with this code as a single building.
Exception: The following need not comply provided the energy use of the building is not increased:
1. Storm windows installed over existing fenestration.
2. Glass only replacements in an existing sash and frame.
3. Existing ceiling, wall or floor cavities exposed during construction provided that these cavities are filled with insulation.
4. Construction where the existing roof, wall or floor cavity is not exposed.
5. Reroofing for roofs where neither the sheathing nor the insulation is exposed. Roofs without insulation in the cavity and where the sheathing or insulation is exposed during reroofing shall be insulated either above or below the sheathing.
6. Reserved. Replacement of existing doors that
separate conditioned space from the exterior shall not require the
installation of a vestibule or revolving door, provided, however, that an
existing vestibule that separates a conditioned space from the exterior
shall not be removed,
7. Alterations that replace less than 50 percent of the luminaires in a space, provided that such alterations do not increase the installed interior lighting power.
8. Alterations that replace only the bulb and ballast within the existing luminaires in a space provided that the alteration does not increase the installed interior lighting power.
101.4.4 Change in occupancy or use. Spaces undergoing a change in occupancy that would result in an increase in demand for either fossil fuel or electrical energy shall comply with this code. Where the use in a space changes from one use in Table 505.5.2 to another use in Table 505.5.2, the installed lighting wattage shall comply with Section 505.5.
101.4.5 Change in space conditioning. Any nonconditioned space that is altered to become conditioned space shall be required to be brought into full compliance with this code.
101.4.6 Mixed occupancy. Where a building includes both residential and commercial occupancies, each occupancy shall be separately considered and meet the applicable provisions of Chapter 4 for residential and Chapter 5 for commercial.
101.4.7 Building
systems. (553.903, F.S.) Thermal efficiency standards are
set for the following building systems where new products are installed or
replaced in existing buildings, and for which a permit must be obtained. New
products shall meet the minimum efficiencies allowed by this code for the
following systems:
Heating,
ventilating or air conditioning systems;
Service water
or pool heating systems;
Electrical
systems and motors;
Lighting systems.
Exceptions:
1. Where part of a
functional unit is repaired or replaced. For example, replacement of an entire
HVAC system is not required because a new compressor or other part does not
meet code when installed with an older system.
2. If the unit being replaced is itself a
functional unit, such as a condenser, it does not constitute a repair. Outdoor and indoor units that are not
designed to be operated together must meet the
a. AHRI data
b. Accredited laboratory
c. Manufacturer’s letter
d. Letter from registered
3. Where existing
components are utilized with a replacement system, such as air distribution
system ducts or electrical wiring for lights, such components or controls need
not meet code if meeting code would require that component’s replacement.
4. Replacement
equipment that would require extensive revisions to other systems, equipment or
elements of a building where such replacement is a like-for-like replacement,
such as through-the-wall condensing units and PTACs, chillers, and cooling
towers in confined spaces.
101.4.8 Exempt
buildings.
101.4.8.1 Federal standards. Any building for which federal
mandatory standards preempt state energy codes. (553.902 F.S.)
101.4.8.2 Hunting or recreational buildings < 1,000
square feet. Any building of less than l,000 square feet (93 m2) whose primary use is not
as a principal residence and which is constructed and owned by a natural person
for hunting or similar recreational purposes is exempt from this code; however,
no such person may build more than one exempt building in any 12-month period. (553.905
F.S.)
TABLE 101.4.1
NONEXEMPT EXISTING BUILDINGS1
|
Permitted
before March 1979 |
Permitted after March 1979 |
Addition |
Meet code for addition2,3 |
|
Not previously conditioned |
Minimum efficiency levels
shall be met for components being changed:
Envelope: Section 402 or 502 Equipment:
Section 403 or 503, 504 Lighting: Section 404 or 505 |
Considered an addition, meet
current code |
New building systems (HVAC,
service hot water or pool heating, lighting, motors) |
New products installed or
replaced in existing buildings shall meet the minimum efficiency allowed for
that system: Equipment:
Section 403 or 503, 504 Lighting: Section 404 or 505 HVAC indoor
and outdoor units ≤ 65,000 Btu/h that are not
designed to operate together shall be matched. HVAC
equipment sizing is required per Sections 403 or 503. |
|
Occupancy type change |
Minimum efficiency levels
shall be met for components being changed:
Envelope: Section 402 or 502 Equipment:
Section 403 or 503, 504 Lighting: Section 404 or 505 |
Meet current code3 |
Renovation4 |
Minimum code envelope,
equipment and lighting efficiency levels shall be met for components being
changed: Envelope:
Section 402 or 502 Equipment: Section 403 or 503,
504 Lighting: Section 404 or 505 |
1 An existing building or portion thereof shall not be altered such that
the building becomes less energy efficient than its existing condition.
2 Minimum
equipment efficiencies shall be met only when equipment is installed to
specifically serve the addition or is being installed in conjunction with the
construction of the addition.
3If an existing building is unable to meet one or more current
prescriptive code minimum requirements, it may be exempt from those minimum
requirements if the entire building is brought into compliance by Section 405
or Section 506, as applicable.
4 See definition of RENOVATION in
Section 202.
101.5 Compliance. Residential buildings less than 4 stories shall meet the provisions of Chapter 4. Commercial buildings and residential buildings greater than 3 stories shall meet the provisions of Chapter 5.
101.5.1 Compliance materials. The Florida Building
Commission code official shall
be permitted to approve specific computer software, worksheets, compliance
manuals and other similar materials that meet the intent of this code.
101.5.2 Low energy buildings. The following buildings, or portions thereof, separated from the remainder of the building by building thermal envelope assemblies complying with this code shall be exempt from the building thermal envelope provisions of this code:
1. Those with a peak design rate of energy usage less than 3.4 Btu/h·ft2 (10.7 W/m2) or 1.0 watt/ft2 (10.7 W/m2) of floor area for space conditioning purposes.
2. Those that do not contain conditioned
space.
SECTION 102
ALTERNATE MATERIALS—METHOD OF CONSTRUCTION, DESIGN
OR INSULATING SYSTEMS
102.1 General. This code is not intended to prevent
the use of any material, method of construction, design or insulating system
not specifically prescribed herein, provided that such construction, design or
insulating system has been approved by the code official as
meeting the intent of this code.
102.1.1 Above
code programs. The Florida Building Commission code official or other
authority having jurisdiction shall be permitted to deem a national, state
or local energy efficiency program to exceed the energy efficiency required by
this code. Buildings approved in writing by such an energy efficiency
program shall be considered in compliance with this code. The requirements
identified as “mandatory” in Chapters 4 and 5 of this code, as applicable,
shall be met.
SECTION 103
CONSTRUCTION DOCUMENTS
103.1
General. Construction documents and other supporting data shall be
submitted in one or more sets with each application for a permit. The
construction documents shall be prepared by a registered design professional where
required by the Florida Statutes
of the jurisdiction in which the project is to be constructed. Where
special conditions exist, the code official is authorized to require
necessary construction documents to be prepared by a registered design
professional.
Exception:
The code official is authorized to waive the requirements for construction documents or other supporting data if the code official determines they are not necessary to confirm compliance with this code.
103.2
Information on construction documents.
103.2.1 Code demonstration forms.
103.2.1.1 Residential ≤ 3 stories
103.2.1.1 Building thermal envelope
alternative. An accurately completed
103.2.1.2 Simulated performance
alternative. An accurately
completed
103.2.1.2Commercial
and residential >3 stories.
103.2.2.1 Building thermal envelope
alternative. An accurately completed
103.2.2.2 Simulated performance
alternative, commercial and high-rise residential. An accurately completed
103.2.2 Details required. Construction documents shall be drawn to scale upon suitable material. Electronic media documents are permitted to be submitted when approved by the code official. Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed, and show in sufficient detail pertinent data and features of the building, systems and equipment as herein governed. Details shall include, but are not limited to, as applicable, insulation materials and their R-values; fenestration U-factors and SHGCs; area-weighted U-factor and SHGC calculations; mechanical system design criteria; mechanical and service water heating system and equipment types, sizes and efficiencies; economizer description; equipment and systems controls; fan motor horsepower (hp) and controls; duct sealing, duct and pipe insulation and location; lighting fixture schedule with wattage and control narrative; and air sealing details.
103.2.3 Compliance certification.
103.2.3.1 Code
compliance demonstration.
103.2.3.1.1
Residential.
No license or registration is required to prepare the code compliance form for
single-family residential dwellings, duplexes and townhouses.
103.2.3.1.2
Commercial and multiple-family residential. Completion of procedures
demonstrating compliance with this code for commercial buildings and
multiple-family residential shall be signed and sealed by an architect or
engineer licensed to practice in the state of
Exception.
Buildings excluded by Section
481.229, Florida Statutes, or Section 471.003,
Design
professionals responsible under Florida law for the design of lighting,
electrical, mechanical, and plumbing systems and the building shell, shall
certify compliance of those building systems with the code by signing and
providing their professional registration number on the energy code form
provided as part of the plans and specifications to the building department.
103.2.3.2 Code compliance certification. The building’s owner, the
owner’s architect, or other authorized agent legally designated by the owner
shall certify that the building is in compliance with the code, as per Section
553.907, Florida Statutes, prior to receiving the permit to begin
construction or renovation.
103.3 Examination of documents. The code official shall examine or cause to be examined the accompanying construction documents and shall ascertain whether the construction indicated and described is in accordance with the requirements of this code and other pertinent laws or ordinances.
103.3.1 Approval of construction documents. When the code official issues a permit where construction documents are required, the construction documents shall be endorsed in writing and stamped “Reviewed for Code Compliance.” Such approved construction documents shall not be changed, modified or altered without authorization from the code official. Work shall be done in accordance with the approved construction documents.
One set of construction documents so reviewed shall be retained by the code official. The other set shall be returned to the applicant, kept at the site of work and shall be open to inspection by the code official or a duly authorized representative.
103.3.2 Previous approvals. This code shall not require changes in the construction documents, construction or designated occupancy of a structure for which a lawful permit has been heretofore issued or otherwise lawfully authorized, and the construction of which has been pursued in good faith within 180 days after the effective date of this code and has not been abandoned.
103.3.3 Phased approval. The code official shall have the authority to issue a permit for the construction of part of an energy conservation system before the construction documents for the entire system have been submitted or approved, provided adequate information and detailed statements have been filed complying with all pertinent requirements of this code. The holders of such permit shall proceed at their own risk without assurance that the permit for the entire energy conservation system will be granted
103.4 Amended construction documents. Changes made
during construction that are not in compliance with the approved construction
documents shall be resubmitted for approval as an amended set of construction
documents.
103.5 Retention of construction documents. One set of approved construction documents shall be retained by the code official for a period of not less than 180 days from date of completion of the permitted work, or as required by state or local laws.
SECTION 104
INSPECTIONS
104.1 General. Construction or work for which a permit is required shall be subject to inspection by the code official.
104.2 Required approvals. Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the code official. The code official, upon notification, shall make the requested inspections and shall either indicate the portion of the construction that is satisfactory as completed, or notify the permit holder or his or her agent wherein the same fails to comply with this code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the code official.
104.3 Final inspection. The building shall have a final inspection and not be occupied until approved.
104.4 Reinspection. A
building shall be reinspected when determined
necessary by the code official
104.5 Approved inspection agencies. The code official is authorized to accept reports of approved inspection agencies, provided such agencies satisfy the requirements as to qualifications and reliability.
104.6 Inspection requests. It shall be the duty of the holder of the permit or their duly authorized agent to notify the code official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this code.
104.7 Reinspection and testing. Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made so as to achieve compliance with this code. The work or installation shall then be resubmitted to the code official for inspection and testing.
104.8 Approval. After the prescribed tests and inspections indicate that the work complies in all respects with this code, a notice of approval shall be issued by the code official.
104.8.1 Revocation. The code official is authorized to, in writing, suspend or revoke a notice of approval issued under the provisions of this code wherever the certificate is issued in error, or on the basis of incorrect information supplied, or where it is determined that the building or structure, premise, or portion thereof is in violation of any ordinance or regulation or any of the provisions of this code.
SECTION 105
VALIDITY
105.1 General. If a portion of this code is held to be illegal or void, such a decision shall not affect the validity of the remainder of this code.
SECTION 106
REFERENCED STANDARDS
106.1 General. The codes and standards referenced in this code shall be those listed in Chapter 6, and such codes and standards shall be considered as part of the requirements of this code to the prescribed extent of each such reference.
106.2 Conflicting requirements. Where the provisions of this code and the referenced standards conflict, the provisions of this code shall take precedence.
106.3Application of references. References to chapter or section numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code.
106.4 Other laws. The provisions of this code shall
not be deemed to nullify any provisions of local, state or federal law.
SECTION 107
FEES
RESERVED
107.1
Fees. A permit shall not be issued until the fees prescribed in
Section 107.2 have been paid, nor shall an amendment to a permit be released
until the additional fee, if any, has been paid.
107.2
Schedule of permit fees. A fee for each permit shall be paid as
required, in accordance with the schedule as established by the applicable
governing authority.
107.3
Work commencing before permit issuance. Any person who commences any
work before obtaining the necessary permits shall be subject to an additional
fee established by the code official, which shall be in addition to the
required permit fees.
107.4
Related fees. The payment of the fee for the construction, alteration,
removal or demolition of work done in connection to or concurrently with the
work or activity authorized by a permit shall not relieve the applicant or
holder of the permit from the payment of other fees that are prescribed by law.
107.5 Refunds. The code official is
authorized to establish a refund policy.
SECTION 108
STOP WORK ORDER
108.1 Authority. Whenever the code official finds any work regulated by this code being performed in a manner either contrary to the provisions of this code or dangerous or unsafe, the code official is authorized to issue a stop work order.
108.2 Issuance. The stop work order shall be in writing and shall be given to the owner of the property involved, or to the owner’s agent, or to the person doing the work. Upon issuance of a stop work order, the cited work shall immediately cease. The stop work order shall state the reason for the order, and the conditions under which the cited work will be permitted to resume.
108.3 Emergencies. Reserved. Where an emergency
exists, the code official shall not be required to give a written notice
prior to stopping the work.
108.4
Failure to comply. Any person who shall continue any work after
having been served with a stop work order, except such work as that person is
directed to perform to remove a violation or unsafe condition, shall be
liable to a fine of not less than [AMOUNT] dollars or more than [AMOUNT] dollars
subject
to penalties as prescribed by law.
SECTION 109
BOARD OF APPEALS
RESERVED
109.1
General. In order to hear and decide appeals of orders, decisions or
determinations made by the code official relative to the application and
interpretation of this code, there shall be and is hereby created a board of
appeals. The code official shall be an ex officio member of said board
but shall have no vote on any matter before the board. The board of appeals
shall be appointed by the governing body and shall hold office at its pleasure.
The board shall adopt rules of procedure for conducting its business, and shall
render all decisions and findings in writing to the appellant with a duplicate
copy to the code official.
109.2
Limitations on authority. An application for appeal shall be based
on a claim that the true intent of this code or the rules legally adopted there
under have been incorrectly interpreted, the provisions of this code do not
fully apply or an equally good or better form of construction is proposed. The
board shall have no authority to waive requirements of this code.
109.3 Qualifications. The board of appeals
shall consist of members who are qualified by experience and training and are
not employees of the jurisdiction
SECTION 110
REPORTING (553.907
F.S.)
110.0
Reporting to the Department of Community Affairs. A reporting form shall be
submitted to the local building department by the owner or owner’s agent with
the submittal certifying compliance with this code. Reporting forms shall be a
copy of the front page of the form applicable for the code chapter under which
compliance is demonstrated.
110.1 Reporting schedule. It shall be the responsibility
of the local building official to forward the reporting section of the proper
form to the Department of Community Affairs on a quarterly basis as per the
reporting schedule in Appendix A.
TABLE 110.1
REPORTING SCHEDULE
Group
I* Group II* Group III*
Quarter 1 12/31 1/31 2/28
Quarter 2 3/31 4/30 5/31
Quarter 3 6/30 7/31 8/31
Quarter 4 9/30 10/31 11/30
*See Appendix 13-A of this
chapter for group designations.
CHAPTER 2
DEFINITIONS
SECTION 201
GENERAL
201.1 Scope. Unless stated otherwise, the following words and terms in this code shall have the meanings indicated in this chapter.
201.2 Interchangeability. Words used in the present tense include the future; words in the masculine gender include the feminine and neuter; the singular number includes the plural and the plural includes the singular.
201.3 Terms
defined in other codes. Terms that are not defined in this code but
are defined in the Florida Building Code, International Building Code, the International
Fire Code, International Florida Building Code, Fuel Gas Code, the Florida
Building Code, International
Mechanical Code, the Florida
Building Code, International Plumbing Code or the Florida
Building Code, International
Residential Code shall have the
meanings ascribed to them in those codes.
201.4 Terms not defined. Terms not defined by this chapter shall have the meanings stated in ANSI/ASHRAE/IESNA Standard 90.1, in codes referenced
from Section 201.3, in Webster's Ninth New Collegiate
Dictionary, as revised, or in
ordinarily
accepted meanings such as the context implies.
SECTION 202
GENERAL DEFINITIONS
[Definitions will be added later once the extent of code
requirements is determined.]
CHAPTER 3
CLIMATE ZONES
SECTION 301
CLIMATE ZONES
301.1 General. Climate zones from Figure 301.1
or Table 301.1 shall be used in determining the applicable requirements from
Chapters 4 and 5. Locations not in Table 301.1 (outside the
301.2Warm humid counties. All Wwarm
humid counties are identified in Table 301.1 by an asterisk.
TABLE 301.1
FLORIDA CLIMATE ZONES, MOISTURE
REGIMES, AND WARM-HUMID DESIGNATIONS
BY STATE, COUNTY AND TERRITORY
Key: A – Moist,
Asterisk (*) indicates a warm-humid location.
COUNTY |
CLIMATE ZONE |
COUNTY |
CLIMATE ZONE |
COUNTY |
CLIMATE ZONE |
Alachua |
2A* |
Hardee |
2A* |
Okeechobee |
2A* |
Baker |
2A* |
Hendry |
2A* |
|
2A* |
Bay |
2A* |
Hernando |
2A* |
Osceola |
2A* |
|
2A* |
|
2A* |
|
2A* |
Brevard |
2A* |
Hillsborough |
2A* |
|
2A* |
Broward |
1A* |
Holmes |
2A* |
Pinellas |
2A* |
Calhoun |
2A* |
|
2A* |
Polk |
2A* |
|
2A* |
|
2A* |
Putnam |
2A* |
Citrus |
2A* |
|
2A* |
|
2A* |
Clay |
2A* |
|
2A* |
|
2A* |
Collier |
2A* |
|
2A* |
Seminole |
2A* |
|
2A* |
Lee |
2A* |
|
2A* |
DeSoto |
2A* |
|
2A* |
St. Lucie |
2A* |
|
2A* |
Levy |
2A* |
|
2A* |
Duval |
2A* |
|
2A* |
|
2A* |
|
2A* |
|
2A* |
|
2A* |
Flagler |
2A* |
Manatee |
2A* |
|
2A* |
|
2A* |
|
2A* |
Volusia |
2A* |
|
2A* |
Martin |
2A* |
Wakulla |
2A* |
Gilchrist |
2A* |
Miami-Dade |
1A* |
Walton |
2A* |
Glades |
2A* |
|
1A* |
|
2A* |
Gulf |
2A* |
|
2A* |
|
|
|
2A* |
Okaloosa |
2A* |
|
|
TABLE 301.3(1)
INTERNATIONAL CLIMATE
ZONE DEFINITIONS
MAJOR CLIMATE TYPE DEFINITIONS |
Warm-humid Definition—Moist (A) locations where
either of the following wet-bulb temperature conditions shall occur during
the warmest six consecutive months of the year:
|
Dry (B) Definition – Locations meeting the following
criteria: Not marine and Pm< 0.44 x (TF – 19.5) [Pcm
< 2.0 x (TC + 7) in SI units] Where: Pin = Annual precipitation in inches (cm) T = Annual mean temperature in oF
(oC) |
Moist (A) Definition – Locations that are not marine
and not dry. |
For SI: oC = [(oF) – 32]/1.8; 1 inch = 2.54 cm.
TABLE 301.3(2)
INTERNATIONAL CLIMATE
ZONE DEFINITIONS
ZONE NUMBER |
THERMAL CRITERIA |
|
|
IP Units |
SI Units |
1 |
9000 < CDD50oF |
5000 < CDD 10
oC. |
2 |
6300 < CDD 50oF
≤ 9000 |
3500 < CDD 10
oC
≤ 5000 |
For SI: oC = [(oF) – 32]/1.8
301.3 International
cClimate zones. The
climate zone for any location outside the shall be
determined by applying Table 301.3(1) and then Table 301.3(2). Code compliance shall be
specific to the building location and Table 301.1.
SECTION 302
DESIGN CONDITIONS
302.1 Interior design conditions. The interior
design temperatures used for heating and cooling load calculations shall be a
maximum of 72şF (22şC) for heating and minimum of 75şF (24şC) for cooling.
SECTION 303
MATERIALS, SYSTEMS AND EQUIPMENT
303.1 Identification. Materials, systems and equipment shall be
identified in a manner that will allow a determination of compliance with the
applicable provisions of this code.
303.1.1 Building thermal envelope insulation. An R-value
identification mark shall be applied by the manufacturer to each piece of building
thermal envelope insulation 12 inches (305 mm) or greater in width. Alternately,
the insulation installers shall provide a certification listing the type,
manufacturer and R-value of insulation installed in each element of the building
thermal envelope. For blown or sprayed insulation (fiberglass and cellulose), the
initial installed thickness, settled thickness, settled R-value,
installed density, coverage area and number of bags installed shall be listed on the
certification. For sprayed polyurethane foam (SPF) insulation, the installed
thickness of the areas covered and R-value of installed thickness shall be listed on the
certification. The insulation installer shall sign, date and post the
certification in a conspicuous location on the job site.
303.1.1.1 Blown or sprayed roof/ceiling
insulation. The thickness of blown-in or sprayed roof/ceiling insulation (fiberglass
or cellulose) shall be written in inches (mm) on markers that are installed at
least one for every 300 square feet (28 m2) throughout the attic space. The
markers shall be affixed to the trusses or joists and marked with the minimum
initial installed thickness with numbers a minimum of 1 inch (25 mm) in height.
Each marker shall face the attic access opening. Spray polyurethane foam
thickness and installed R-value shall be listed on
certification provided by the insulation installer
303.1.2 Insulation mark installation. Insulating
materials shall be installed such that the manufacturer’s R-value mark is
readily observable upon inspection.
303.1.3 Fenestration product rating. U-factors of
fenestration products (windows, doors and skylights) shall be determined in
accordance with NFRC 100 by an accredited, independent laboratory, and labeled
and certified by the manufacturer. Products lacking such a labeled U-factor shall
be assigned a default U-factor from Table 303.1.3(1) or 303.1.3(2).
The solar heat gain coefficient (SHGC) of glazed fenestration products
(windows, glazed doors and skylights) shall be determined in accordance with
NFRC 200 by an accredited, independent laboratory, and labeled and certified by
the manufacturer. Products lacking such a labeled SHGC shall be assigned a
default SHGC from Table 303.1.3(3).
TABLE 303.1.3(1)
DEFAULT
GLAZED FENESTRATION U-FACTOR
Frame
Type |
Single
Pane |
Double
pane |
Skylight |
|
Single |
Double |
|||
Metal |
1.20 |
0.80 |
2.00 |
1.30 |
Metal with
thermal break |
1.10 |
0.65 |
1.90 |
1.10 |
Nonmetal or
metal clad |
0.95 |
0.55 |
1.75 |
1.05 |
Glazed block |
0.60 |
TABLE 303.1.3(2)
DEFAULT
DOOR U-FACTORS
Door
Type |
U-Factor |
Uninsulated
metal |
1.20 |
Insulated
metal |
0.60 |
Wood |
0.50 |
Insulated,
nonmetal edge, max. 45% glazing, any glazing
double pane |
0.35 |
TABLE 303.1.3(3)
DEFAULT
GLAZED FENESTRATION SHGC
Single
Glazed |
Double
Glazed |
Glazed
Block |
||
Clear |
Tinted |
Clear |
Tinted |
|
0.8 |
0.7 |
0.7 |
0.6 |
0.6 |
303.1.4 Insulation product rating. The thermal
resistance (R-value) of insulation shall be determined in accordance with the
U.S. Federal Trade Commission R-value rule (CFR Title 16, Part 460, May 31,
2005) in units of h _ ft2 _ °F/Btu at a mean temperature of 75°F (24°C).
303.2 Installation. All materials, systems and equipment shall be
installed in accordance with the manufacturer’s installation instructions and
the Florida International Building
Code.
303.2.1 Protection of exposed foundation
insulation. Insulation applied to the exterior of basement walls, crawlspace
walls and the perimeter of slab-on-grade floors shall have a rigid, opaque and
weather-resistant protective covering to prevent the degradation of the
insulation’s thermal performance. The protective covering shall cover the
exposed exterior insulation and extend a minimum of 6 inches (153 mm) below
grade.
303.3 Maintenance information. Maintenance instructions shall be
furnished for equipment and systems that require preventive maintenance.
Required regular maintenance actions shall be clearly stated and incorporated
on a readily accessible label. The label shall include the title or publication
number for the operation and maintenance manual for that particular model and
type of product.
303.3.1 Commercial buildings. The code official shall ensure that the construction documents require an operating and maintenance manual be transmitted to the building owner for all commercial buildings. The manual shall include basic data relating to the design, operation and maintenance of HVAC and lighting systems and equipment. Required routine maintenance actions shall be clearly identified. Where applicable, control information such as diagrams, schematics, control sequence descriptions, and maintenance and calibration information shall be included. [from ASHRAE 90.1]
Chapter 4
Residential Energy Efficiency
SECTION 401
GENERAL
401.1 Scope. This chapter applies to residential buildings
401.2
Compliance. Projects shall comply with Sections 401, 402.4, 402.5, and 403.1,
403.2.2, 403.2.3, and 403.3 through 403.9 (referred to as the mandatory
provisions) and either:
1. Sections
402.1 through 402.3, 403.2.1 and 404.1 (prescriptive); or
2. Section 405 (performance).
401.3 Certificate. Energy
performance level (EPL) display card. The building official shall
require that an energy performance level (EPL) display card be completed and
certified by the builder to be accurate and correct before final approval of
the building for occupancy. A permanent certificate shall also be posted on or in the
electrical distribution panel and .
The certificate shall not cover or obstruct the visibility of the circuit
directory label, service disconnect label or other required labels. The
certificate shall be completed by the builder or registered design
professional. The certificate shall list the predominant R-values of
insulation installed in or on ceiling/roof, walls, foundation (slab, basement
wall, crawlspace wall and/or floor) and ducts outside conditioned
spaces; U-factors for fenestration and the solar heat
gain coefficient (SHGC) of fenestration. Where there is more than one value for
each component, the certificate shall list the value covering the largest area.
The certificate shall list the types and efficiencies of heating, cooling and
service water heating equipment. Where a gas-fired unvented room heater,
electric furnace, or baseboard electric heater is installed in the residence,
the certificate shall list “gas-fired unvented room heater,” “electric furnace”
or “baseboard electric heater,” as appropriate. An efficiency
shall not be listed for gas-fired unvented room heaters, electric
furnaces or electric baseboard heaters.
SECTION 402
BUILDING THERMAL ENVELOPE
402.1 General
(Prescriptive).
402.1.1 Insulation and fenestration criteria. The building
thermal envelope shall meet the requirements of Table 402.1.1 based on the climate zone specified in
Chapter 3.
402.1.1.1.2 R-value
computation. Insulation material used in layers, such as framing cavity
insulation and insulating sheathing, shall be summed to compute the component R-value. The
manufacturer’s settled R-value shall be used for blown insulation.
Computed R-values shall not include an R-value for
other building materials or air films.
TABLE 402.1.1
INSULATION
AND FENESTRATION REQUIREMENTS BY COMPONENTa
COMPONENT EFFICIENCIES REQUIREDa,l
OPTION
Percent
Glazingc |
Fenestration U-Factorb |
Sky-lightb U-Factor |
Glazed Fenes-
tration SHGCb |
Ceiling R-value/ Attic Radiant Barriere |
Roof Reflectance Tested per S. 405.5.5.2 |
Wood Frame
Wall R-value |
Mass
Wall R-valuei |
Floor
R-value/ Slab
R-valued |
Door U-Factor |
Ducts: R-value/ Locationk |
Air Handler Locationk, |
Air Leakage Tested per S. 403.2.2.1 |
1 13% |
0.65 j |
0.75 |
0.30 |
38/No |
0.25 |
13 |
6 / 7.8 |
13/0 |
0.65 |
R-8/ Unconditioned |
Unconditioned |
Qn=0.03 |
2 16% |
0.65j |
0.75 |
0.30 |
30/Yes |
0.25 |
13 |
6 / 7.8 |
13/0 |
0.65 |
R-8/ Unconditioned |
Unconditioned |
Qn=0.03 |
3 20% |
0.65 j |
0.75 |
0.30 |
30/No |
0.25 |
13 |
6 / 7.8 |
13/0 |
0.65 |
R-6/ Conditioned |
Conditioned |
Qn=0.03 |
For
SI: 1 foot = 304.8 mm.
a. R-values
are minimums. U-factors and SHGC are
maximums. R-19 batts compressed into a nominal 2 × 6
framing cavity such that the R-value
is reduced by R-1 or more shall be marked with the compressed batt R-value
in addition to the full thickness R-value.
b. The fenestration U-factor
column excludes skylights. The SHGC column applies to all glazed fenestration.
c. Percent glazing shown in the Option column shall be the
maximum glazing allowed for that option. Percent glazing area shall be measured
in window to floor area and shall include skylight area. PERCENT
TO BE DETERMINED BY SELECTION OF OPTION
“15/19” means R-15 continuous insulated
sheathing on the interior or exterior of the home or R-19 cavity insulation at
the interior of the basement wall. “15/19” shall be permitted to be met with
R-13 cavity insulation on the interior of the basement wall plus R-5 continuous
insulated sheathing on the interior or exterior of the home. “10/13” means R-10
continuous insulated sheathing on the interior or exterior of the home or R-13
cavity insulation at the interior of the basement wall.
d. R-5 shall be added to the required
slab edge R-values for heated
slabs only;. Iinsulation depth shall be
the depth of the footing or 2 feet, whichever is less in Zones 1through 3
for heated slabs. No insulation is required for unheated slabs, basement
walls or crawl space walls.
e. A sheet radiant barrier shall be installed in the attic in
accordance with Section 405.5.5.1. There are no SHGC requirements
in the Marine Zone.
f. Basement wall insulation is not required
in warm-humid locations as defined by Figure 301.1 and Table 301.1.
g. Or insulation sufficient to fill the
framing cavity, R-19 minimum.
h. “13+5” means R-13 cavity insulation plus
R-5 insulated sheathing. If structural sheathing covers 25 percent or less of
the exterior, insulating sheathing is not required where structural sheathing
is used. If structural sheathing covers more than 25 percent of exterior,
structural sheathing shall be supplemented with insulated sheathing of at least
R-2.
i.
The second R-value applies when
more than half the insulation is on the interior of the mass wall.
j. For impact rated fenestration complying
with Section R301.2.1.2 of
the InternationalResidential Code,
Residential or Section 1609.1.2 of the International Florida Building Code, Building the maximum U-factor
shall be 0.75 in Zone 2 and 0.65 in Zone 3.
k.
Conditioned= entire distribution system located inside both the thermal and air
barrier of the home. Unconditioned = any
portion located in unconditioned space.
l. Limitations to compliance by Section
402 found in Section 402.2 shall be met.
TABLE 402.1.3
EQUIVALENT
U-FACTORSa,f
Climate
Zone |
Fenestration
U-Factore |
Skylight U-Factor |
Ceiling U-Factor |
Frame
Wall U-Factor |
Mass
Wall U-Factorb |
Floor U-Factor |
Basement
Wall U-Factord |
Crawl
Space Wall U-Factorc |
1 |
0.65 |
0.75 |
0.035 |
0.082 |
0.124 |
0.064 |
0.360 |
0.477 |
2 |
0.65 |
0.75 |
0.035 |
0.082 |
0.124 |
0.064 |
0.360 |
0.477 |
a.
Nonfenestration U-factors
shall be obtained from measurement, calculation or an approved source.
b.
When more than half the insulation is on the interior, the mass wall U-factors
shall be a maximum of 0.102 in Zone 1 and, 0..102 in Zone 2, 0.12 in
Zone 3, 0.10 in Zone 4 except Marine, and the same as the frame wall U-factor
in Marine Zone 4 and Zones 5 through 8.
c.
Basement wall U-factor of 0.360 in
warm-humid locations as defined by Figure 301.1 and Table 301.2.
d.
Foundation U-factor requirements
shown in Table 402.1.3 include wall construction and interior air films but
exclude soil conductivity and exterior air films. U-factors
for determining code compliance in accordance with Section 402.1.4 (total UA
alternative) of Section 405 (Simulated Performance Alternative) shall be
modified to include soil conductivity and exterior air films.
e. Window to floor area shall not
exceed X percent. See Section 402.1.2.3. PERCENT TO BE DETERMINED BY SELECTION OF
OPTION FOR TABLE 402.1.1
f. Limitations to compliance by Section
402 found in Section 402.2 shall be met.
[Additional caveats may be required based on
options chosen for Table 402.1.1]
402.1.1.2.
3 U-factor alternative. An assembly
with a U-factor equal to or less than that specified in Table 402.1.3
shall be permitted as an alternative to the corresponding component R-value in
Table 402.1.1. All
other prescriptive criteria of Table 402.1, the prescriptive criteria in Section
402.1.5 and footnotes to Table 402.1.3 shall be met.
402.1.1.3 4 Total UA alternative. If the total building
thermal envelope UA (sum of U-factor times assembly area) is less than or
equal to the total UA resulting from using the U-factors in
Table 402.1.3 (multiplied by the same assembly area as in the proposed
building), the building shall be considered in compliance with Table 402.1.1. All other prescriptive criteria of
Table 402.1, the prescriptive criteria in Section 402.1.5 and footnotes to
Table 402.1.3 shall be met. The UA calculation shall be done using a
method consistent with the ASHRAE Handbook of Fundamentals and shall
include the thermal bridging effects of framing materials. The SHGC
requirements shall be met in addition to UA compliance.
402.1.2 Limitations to compliance by Section 402.
402.1.2.1 Electric
space heating. Electric resistance space heating systems shall not be used when
complying with this code by Section 402.
402.1.2.2 Air handlers in attics. Air handlers may not be installed in attics when
complying with Section 402.
402.1.2.3 Maximum percent window area. The window area as a percentage of the
conditioned floor area (CFA) shall not exceed the percent glazing listed for
the code compliance Option chosen in Table 402.1.1.
Exceptions: The follow exceptions
apply to additions.
1. When a fenestration(s) in an existing exterior wall is
being removed or enclosed by an addition, an amount equal to the total area of
this fenestration may be subtracted from the total glass area prior to
determining the installed glass percentage.
2. Additions of 600 square feet (56 m2) or
less may have up to 50 percent glass to conditioned floor area.
3. Glass windows
and doors that were previously located in an existing exterior wall that is
being removed or enclosed by an addition do not have to comply with the
U-factor and solar heat gain coefficient requirements in Table 402.1.1 when
reinstalled as part of the addition.
402.1.2.4 Air
handlers in attics. Air
handlers may not be installed in attics when complying with Section 402.
402.1.2.5 Equipment efficiencies. Minimum equipment efficiencies for cooling,
heating and water heating shall be code minimums as per Sections 403.4 and
403.6.
402.2 Specific
insulation requirements (Prescriptive).
402.2.1Ceilings with attic spaces. When Section
402.1.1 would require R-38 in the ceiling, R-30 shall be deemed to satisfy the
requirement for R-38 wherever the full height of uncompressed R-30 insulation
extends over the wall top plate at the eaves. Similarly, R-38 shall be deemed
to satisfy the requirement for R-49 wherever the full height of uncompressed
R-38 insulation extends over the wall top plate at the eaves. This reduction
shall not apply to the U-factor alternative approach in Section
402.1.3 and the total UA alternative in Section 402.1.4.
402.2.2 Ceilings without attic spaces. Where Section 402.1.1 would require
insulation levels above R-30 and the design of the roof/ceiling assembly does
not allow sufficient space for the required insulation, the minimum required
insulation for such roof/ceiling assemblies shall be R-30. This reduction of insulation
from the requirements of Section 402.1.1 shall be limited to 500 square feet
(46m2) or 20 percent of the total insulated ceiling area, whichever is less.
This reduction shall not apply to the U-factor alternative approach in Section
402.1.3 and the total UA alternative in Section 402.1.4
402.2.3 Access hatches and doors. Access doors
from conditioned spaces to unconditioned spaces (e.g., attics and crawl spaces)
shall be weatherstripped and insulated to a level
equivalent to the insulation on the surrounding surfaces. Access shall be
provided to all equipment that prevents damaging or compressing the insulation.
A wood framed or equivalent baffle or retainer is required to be provided when
loose fill insulation is installed, the purpose of which is to prevent the
loose fill insulation from spilling into the living space when the attic access
is opened, and to provide a permanent means of maintaining the installed -value
of the loose fill insulation.
402.2.4 Mass walls. Mass walls for
the purposes of this chapter shall be considered above-grade walls of concrete
block, concrete, insulated concrete form (ICF), masonry cavity, brick (other
than brick veneer), earth (adobe, compressed earth block, rammed earth) and
solid timber/logs.
402.2.5 Steel-frame ceilings, walls, and
floors. Steel frame ceilings, walls and floors shall meet the insulation
requirements of Table 402.2.5 or shall meet the U-factor
requirements in Table 402.1.3. The calculation of the U-factor for a
steel-frame envelope assembly shall use a series-parallel path calculation
method.
Exception: In Climate Zones 1 and 2, the continuous
insulation requirements in Table 402.2.54 shall be permitted to
be reduced to R-3 for steel frame wall assemblies with studs spaced at 24
inches (610 mm) on center.
402.2.6 Floors. Floor
insulation shall be installed to maintain permanent contact with the underside
of the subfloor decking.
402.2.7 Basement walls. Walls associated with conditioned basements
shall be insulated from the top of the basement wall down to 10
feet (3048 mm) below grade or to the basement floor, whichever is less. Walls
associated with unconditioned basements shall meet this requirement unless the
floor overhead is insulated in accordance with Sections 402.1.1 and 402.2.6.
TABLE 402.2.5
STEEL-FRAME CEILING, WALL AND FLOOR
INSULATION
(R-VALUE)
Wood Frame R-Value Requirement |
Cold-Formed Steel Equivalent R-valuea |
Steel Truss Ceilingsb |
|
R-30 |
R-38 or R-30 + 3 or R-26 +
5 |
R-38 |
R-49 or R-38 + 3 |
R-49 |
R-38 + 5 |
Steel Joist Ceilingsb |
|
R-30 |
R-38 in 2x4 or 2x6 or 2x8 R-49 in any framing |
R-38 |
R-49 in 2x4 or 2x6 or 2x8
or 2x10 |
Steel-Framed Wall |
|
R-13 |
R-13 + 5 or R-15 + 4
or R-21 + 3 or R-0 + 10 |
R-19 |
R-13 + 9 or R-19 + 8
or R-25 + 7 |
R-21 |
R-13 + 10 or R-19 + 9
or R-25 + 8 |
Steel Joist Floor |
|
R-13 |
R-19 in 2x6 R-19 + 6 in 2x8 or 2x10 |
R-19 |
R-19 + 6 in 2x6
R-19 + 12 in 2x8 or 2x10 |
a. Cavity insulation R-
value is listed first, followed by continuous insulation R-
value.
b. Insulation exceeding the height of the
framing shall cover the framing.
402.2.8 Slab-on-grade floors. Reserved. Slab-on-grade
floors with a floor surface less than 12 inches (305 mm) below grade shall be
insulated in accordance with Table 402.1.1. The insulation shall extend
downward from the top of the slab on the outside or inside of the foundation
wall. Insulation located below grade shall be extended the distance provided in
Table 402.1.1 by any combination of vertical insulation, insulation extending
under the slab or insulation extending out from the building. Insulation
extending away from the building shall be protected by pavement or by a minimum
of 10 inches (254 mm) of soil. The top edge of the insulation installed between
the exterior wall and the edge of the interior slab shall be
permitted to be cut at a 45-degree (0.79 rad) angle
away from the exterior wall. Slab-edge
insulation is not required in jurisdictions designated by the code
official as having a very heavy termite infestation.
402.2.9 Crawl space walls. As an alternative to insulating
floors over crawl spaces, crawl space walls shall be permitted to be insulated
when the crawl space is not vented to the outside. Crawl space wall insulation
shall be permanently fastened to the wall and extend downward from the floor to
the finished grade level and then vertically and/or horizontally for at least
an additional 24 inches (610 mm). Exposed earth in unvented crawl space
foundations shall be covered with a continuous Class I vapor retarder. All
joints of the vapor retarder shall overlap by 6 inches (153 mm) and be sealed
or taped. The edges of the vapor retarder shall extend at least 6 inches (153
mm) up the stem wall and shall be attached to the stem wall.
402.2.10 Masonry
veneer. Insulation shall not be required on the horizontal portion of the
foundation that supports a masonry veneer.
402.2.11 Thermally isolated sunroom
insulation. The minimum ceiling insulation R-values shall
be R-19 in Zones 1 through 4 and R-24 in Zones 5 through 8. The minimum
wall R-value shall
be R-13 in all zones. New wall(s) separating a sunroom from conditioned
space shall meet the building thermal envelope requirements
402.2.12 Common
walls/ceilings/floors. Walls, ceilings or floors common to separate conditioned
tenancies shall be insulated to a minimum R-11, space permitting.
Exception: Mass common walls
shall be insulated to a minimum of R-6.
402.2.13 Walls considered ceiling area. Wall areas that separate
conditioned living space from unconditioned attic space (such as attic knee
walls, walls on cathedral ceilings, skylight chimney shafts, gambrel roofs,
etc.) shall be considered ceiling area. Such areas shall be included in
calculations of ceiling area and shall have a minimum insulation value of R-19.
402.3
Fenestration. (Prescriptive).
402.3.1 U-factor. An area-weighted
average of fenestration products shall be permitted to satisfy the U-factor
requirements.
402.3.2 Glazed fenestration SHGC. An
area-weighted average of fenestration products more than 50 percent glazed
shall be permitted to satisfy the SHGC requirements
402.3.3 Glazed fenestration exemption. Up to 15
square feet (1.4m2) of glazed fenestration per dwelling unit shall be permitted
to be exempt from U-factor and SHGC requirements in Section 402.1.1. This exemption
shall not apply to the U-factor alternative approach in Section
402.1.3 and the Total UA alternative in Section 402.1.4.
402.3.4 Opaque door exemption. One
side-hinged opaque door assembly up to 24 square feet (2.22 m2) in area is
exempted from the U-factor requirement in Section 402.1.1. This exemption shall not
apply to the U-factor alternative approach in Section 402.1.3 and the total UA
alternative in Section 402.1.4
402.3.5 Thermally isolated sunroom U-factor. For Zones 4
through 8, the maximum fenestration U-factor shall
be 0.50 and the maximum skylight U-factor shall
be 0.75. New windows and doors separating the sunroom from conditioned
space shall meet the building thermal envelope requirements.
402.3.6 Replacement fenestration. Where some or
all of an existing fenestration unit is replaced with a new fenestration
product, including sash and glazing, the replacement fenestration unit shall
meet the applicable requirements for U-factor and SHGC in Table 402.1.1.
402.4 Air
leakage (Mandatory).
402.4.1 Building thermal envelope. The building thermal
envelope shall be durably sealed to limit infiltration. The sealing methods
between dissimilar materials shall allow for differential expansion and
contraction. The following shall be caulked, gasketed,
weatherstripped or otherwise sealed with an air
barrier material, suitable film or solid material:
1. All joints, seams and penetrations.
2. Site-built windows, doors and skylights.
3. Openings between window and door assemblies and their
respective jambs and framing.
4. Utility penetrations.
5. Dropped ceilings or chases adjacent to the thermal envelope.
6. Knee walls.
7. Walls and ceilings separating a garage from conditioned spaces.
8. Behind tubs and showers on exterior
walls.
9. Common walls between dwelling units.
10. Attic access openings.
11. Rim joist junction.
12. Other sources of infiltration.
402.4.2 Air sealing and insulation. Building
envelope air tightness and insulation installation shall be demonstrated to
comply with one of the following options given by Section 402.4.2.1 or
402.4.2.2
402.4.2.1 Testing option. Building envelope tightness and insulation
installation shall be considered acceptable when tested air leakage is less
than seven air changes per hour (ACH) when tested with a blower door at a
pressure of 33.5 psf (50 Pa). Testing shall occur
after rough in and after installation of penetrations of the building envelope,
including penetrations for utilities, plumbing, electrical, ventilation and
combustion appliances.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be
closed, but not sealed;
2. Dampers shall be closed, but not sealed, including exhaust,
intake, makeup air, backdraft
and flue dampers;
3. Interior doors shall be open;
4. Exterior openings for continuous ventilation systems and heat
recovery ventilators shall be closed and sealed;
5. Heating and cooling system(s) shall be turned off;
6. HVAC ducts shall not be sealed; and
7. Supply and return registers shall not be
sealed.
402.4.2.2 Visual inspection option. Building
envelope tightness and insulation installation shall be considered acceptable
when the items listed in Table 402.4.2, applicable to the method of
construction, are field verified. Where required by the code
official, an approved party independent from the installer of the
insulation shall inspect the air barrier and insulation. [No change to Table 402.4.2]
402.4.3 Fireplaces. New
wood-burning fireplaces shall have gasketed doors and
outdoor combustion air.
402.4.4 Fenestration air leakage. Windows,
skylights and sliding glass doors shall have an air infiltration rate of no
more than 0.3 cfm per square foot (1.5 L/s/m2), and
swinging doors no more than 0.5 cfm per square foot
(2.6 L/s/m2), when tested according to NFRC 400 or AAMA/WDMA /CSA
101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the
manufacturer.
Exceptions: Site-built windows, skylights and
doors.
402.4.5 Recessed lighting. Recessed luminaires
installed in the building thermal envelope shall be sealed to limit air
leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC-rated and labeled as meeting
ASTM E 283 when tested at 1.57 psf (75 Pa) pressure
differential with no more than 2.0 cfm (0.944 L/s) of
air movement from the conditioned space to the ceiling
cavity.
All recessed luminaires
shall be sealed with a gasket or caulk between the housing and the interior
wall or ceiling covering.
402.5 Maximum
fenestration U-factor and SHGC
(Mandatory). The area-weighted average maximum fenestration U-factor
permitted using trade-offs from Section 402.1.4 or 404 shall be 0.48 in
Zones 4 and 5 and 0.40 in Zones 6 through 8 for vertical fenestration, and 0.75
in Zones 4 through 8 for skylights. The area-weighted average maximum
fenestration SHGC permitted using trade-offs from Section 405 in Zones 1 and
2 through 3 shall be 0.50.
SECTION 403
SYSTEMS
403.1 Controls (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
403.1.1 Programmable thermostat. Where the primary heating system is a forced-air furnace, at least one thermostat per dwelling unit capable of controlling the heating and cooling system on a daily schedule to maintain different temperature set points at different times of the day. This thermostat shall include the capability to set back or temporarily operate the system to maintain zone temperatures down to 55°F (13°C) or up to 85°F (29°C). The thermostat shall initially be programmed with a heating temperature set point no higher than 70°F (21°C) and a cooling temperature set point no lower than 78°F (26°C).
403.1.2 Heat pump supplementary
heat (Mandatory). Heat pumps having supplementary electric-resistance heat
shall have controls that, except during defrost, prevent supplemental heat
operation when the heat pump compressor can meet the heating load.
403.1.3 Humidity control. Where a humidistat is used for comfort dehumidification,
it shall be capable of being set to prevent the use of fossil fuel or
electricity to reduce humidities below 60 percent.
403.2 Ducts.
403.2.1 Insulation
(Prescriptive). Supply ducts, including air filter enclosures, air ducts and plenums, located
in attics or on roofs shall be insulated to a minimum of R-8. All other
ducts shall be insulated to a minimum of R-6.
Exceptions:
1. Ducts or portions thereof located completely inside the building thermal envelope.
2. Exhaust air ducts
3. Factory-installed plenums,
casings or ductwork furnished as a part of tested and rated HVAC equipment.
403.2.2 Sealing (Mandatory). All
ducts, air handlers, filter boxes and building cavities which form the primary air
containment passageways for air distribution systems shall be considered ducts
or plenum chambers, shall be constructed and sealed in accordance with used
as ducts shall be sealed. Joints and seams shall comply with Section
M1601.4.1 of the Florida
Building Code, International
Residential, Code. or
Section 603 of the
403.2.2.1 Duct tightness. Duct tightness shall be verified by testing
to either of the following
1. Post construction test:
Leakage to outdoors shall be less than or equal to 8 cfm
(226.5 L/min) per 100 ft2 (9.29 m2) of conditioned
floor area or a total leakage less than or equal to 12 cfm
(12 L/min) per 100 ft2 (9.29 m2) of conditioned floor
area when tested at a pressure differential of 0.1 inches w.g. (25 Pa) across the entire system, including the
manufacturer’s air handler enclosure. All register boots shall be taped or
otherwise sealed during the test.
2. Rough-in test: Total leakage shall be less than or equal to 6
cfm (169.9 L/min) per 100 ft2 (9.29 m2)
of conditioned floor area when tested at a pressure differential of 0.1
inches w.g. (25 Pa) across the roughed-in system,
including the manufacturer’s air handler enclosure. All register boots shall be
taped or otherwise sealed during the test. If the air handler is not installed
at the time of the test, total leakage shall be less than or equal to 4 cfm (113.3 L/min) per 100 ft2 (9.29 m2)
of conditioned floor area.
Exceptions:
Duct tightness test is not required if the air handler and all ducts
are located within conditioned space.
ASHRAE Standard 152. All ducts and air handlers shall be either located in conditioned space or tested by a Class 1 BERS rater to be “substantially leak free”. “Substantially leak free” shall mean distribution system air leakage to outdoors no greater than 3 cfm per 100 square feet of conditioned floor area at a pressure differential of 25 Pascal (0.10 in. w.c.) across the entire air distribution system, including the manufacturer’s air handler enclosure.
403.2.3 Building cavities. Building framing cavities shall not be used as supply ducts.
403.2.4 Air-handling units. Air handling units shall
not be installed in the attic when a home is brought into code compliance by
Section 402. Air-handling
units shall be allowed in attics for compliance by Section 405 only if
the following conditions are met:
1. The service panel
of the equipment is located within 6 feet (1829 mm) of an attic access.
2. A device is
installed to alert the owner or shut the unit down when the condensation drain
is not working properly.
3. The attic
access opening is of sufficient size to replace the air handler.
4. A notice is
posted on the electric service panel indicating to the homeowner that the air
handler is located in the attic. Said notice shall be in all capitals, in 16
point type, with the title and first paragraph in bold:
NOTICE TO HOMEOWNER
A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR HANDLER,
IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT, AND ECONOMIC OPERATION OF THE
AIR-CONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED. YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH
ONE OR BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU WHEN THE
CONDENSATION DRAIN IS NOT WORKING PROPERLY OR (2) A DEVICE THAT WILL SHUT THE
SYSTEM DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF SERVICE, IT IS RECOMMENDED THAT
YOU ENSURE PROPER WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF PEAK
OPERATION.
403.3 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below55°F (13°C) shall be insulated to a minimum of R-3.
403.4
Hot water systems (Mandatory. 553.909, F.S.)
403.4.1 Circulating hot water systems, insulation (Mandatory). All circulating service hot water piping shall be insulated to at least R-2. Circulating hot water systems shall include an automatic or readily accessible manual switch that can turn off the hot water circulating pump when the system is not in use. Pipe insulation buried underground shall be as specified by the manufacturer for underground use.
403.4.2
Heat traps. Storage water heaters not
equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall
consist of either a commercially available heat trap or a downward and upward
bend of at least 3˝ inches (89 mm) in the hot water distribution line and cold
water line located as close as possible to the storage tank.
403.4.3 Water heater efficiencies.
403.4.3.1 Storage water heater temperature controls.
403.4.3.1.1 Automatic controls. Service water heating systems
shall be equipped with automatic temperature controls capable of adjustment
from the lowest to the highest acceptable temperature settings for the intended
use. The minimum temperature setting range shall be from 100°F to 140°F (38°C
to 60°C).
403.4.3.1.2 Shut down. A separate switch or a clearly
marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided
to permit the energy supplied to the main burner(s) of combustion types of
service water heating systems to be turned off.
403.4.3.2 Water heater efficiencies. Residential sized water
heaters shall meet the minimum efficiencies of this section. Water heating
systems not covered in this section shall meet the minimum efficiencies listed
for that system in Section 504 of this code.
403.4.3.2.1 Electric water heaters. All automatic electric storage water heaters
having a storage capacity of 120 gallons (454 L) or less and an input rating of
12 kw or less shall, when tested in accordance with
the DOE Uniform Test Method for Measuring the Energy Consumption of Water
Heaters, Appendix E to Subpart B, 10 CFR Part 430, meet the performance
minimums listed in Table 403.4.2.2.
403.4.3.2.2
Gas- and oil-fired water heater
efficiencies. All gas- and oil-fired automatic storage water heaters with capacities
of 100 gallons or less and an input rating of 75,000 Btu/h or less (gas) or
105,000 Btu/h or less (oil) shall, when tested in accordance with the DOE
Uniform Test Method for Measuring the Energy Consumption of Water Heaters,
Appendix E to Subpart B, 10 CFR Part 430, meet the performance minimums listed
in Table 403.4.2.2.
403.4.3.2.2.1 Gas Instantaneous
or Tankless Water Heaters. All gas-fired instantaneous (tankless) water
heaters that a) initiate heating based on sensing water flow, b) are designed
to deliver water at a controlled temperature of less than 180 °F (82 °C), c) have
an input less than 200,000 Btu/h (210 MJ/h), d) have a manufacturer's specified
storage capacity of less than 2 gallons (7.6 liters) and, e) have either a
fixed or variable burner input shall, when tested in accordance with the DOE
Uniform Test Method for Measuring the Energy Consumption of Water Heaters,
Appendix E to Subpart B, Title 10 CFR 430, meet the performance minimums
established in Title 10 CFR 430.32, Energy and Water Conservation Standards and
Effective Dates.
403.4.3.2.2.2 Combination service water heating and
space heating equipment. Service water heating equipment used to
provide additional functions (e.g. space heating) as part of a combination
(integrated) system shall comply with minimum performance requirements for
water heating equipment. For combined
gas storage tank water heating and space heating systems tested to ANSI/ASHRAE
124, the EF used shall be the effective water heating efficiency (CA ef) listed for the appliance by the Gas
Appliance Manufacturer’s Association (GAMA).
For combined gas instantaneous (tankless) water heating and space
heating systems, the EF used shall be determined in accordance with the DOE
Uniform Test Method for Measuring the Energy Consumption of Water Heaters,
Appendix E to Subpart B, Title 10 CFR 430.
Combination systems utilizing a
storage tank water heater as the heat source for space heating purposes with
input ratings of 105,000 Btu/h (360m3/kW) or less shall utilize a
water heater listed by the Gas Appliance Manufacturer’s Association (GAMA). Changeouts of burners or heating elements to increase
capacity shall not be made unless the unit has been listed at that capacity by
GAMA.
403.4.3.2.3 Solar water heating systems. Solar systems for domestic hot
water production are rated by the annual solar energy factor of the system. The
solar energy factor of a system shall be determined from the
1. Be installed
with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at
an orientation within 45 degrees of true south.
TABLE 403.4.3.2
MINIMUM PERFORMANCE STANDARDS
WATER HEATING EQUIPMENT:
FIRED STORAGE WATER HEATER
MINIMUM ENERGY FACTORS (EF)
TYPE / VOLUME |
TANK VOLUME (GALLONS) |
||||||||
|
20 |
30 |
40 |
50 |
60 |
70 |
80 |
100 |
120 |
ELECTRIC: Up to 120 gallon or
12kW input |
.94 |
.93 |
.92 |
.90 |
.88 |
— |
.86 |
.84 |
.81 |
GAS: Up to 100 gallon or
75,000 Btu/h input |
.63 |
.61 |
.59 |
.58 |
.55 |
.53 |
— |
.48 |
— |
OIL: Up to 50 gallon or 75,000
Btu/h input |
— |
.53 |
.51 |
.50 |
— |
— |
— |
— |
— |
403.5
Mechanical ventilation (Mandatory). Outdoor air intakes and exhausts shall
have automatic or gravity dampers that close when the ventilation system is not
operating.
403.5.1 Ventilation air. Residential buildings designed to be operated at a
positive indoor pressure or for mechanical ventilation shall meet the following
criteria:
1. The design air change per hour
minimums for residential buildings in ASHRAE 62, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential
applications.
2. No ventilation
or air-conditioning system make-up air shall be provided to conditioned space
from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent
to swimming pools or spas.
3. If ventilation
air is drawn from enclosed space(s), then the walls of the space(s) from which
air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be
insulated to a minimum of R-19, space permitting, or R-10 otherwise.
403.6 Heating and Cooling Equipment sizing (Mandatory. 553.912, F.S.).
403.6.1 Equipment sizing. Heating and
cooling equipment shall be sized based on building loads calculated in
accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies. in accordance with Section
M1401.3 of the International Residential Code. The manufacturer and model
number of the outdoor and indoor units (if split system) shall be submitted
along with the sensible and total cooling capacities at the design conditions
described in Section 302.1.
403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be
selected so that its total capacity is not less than the calculated total load
but not more than 1.15 times greater than the total load calculated according
to the procedure selected in Section 403.6, or the closest available size
provided by the manufacturer's product lines. The corresponding latent capacity
of the equipment shall not be less than the calculated latent load.
Exceptions:
1. Attached
single- and multiple-family residential equipment sizing may be selected so
that its cooling capacity is less than the calculated total sensible load but
not less than 80 percent of that load.
2. When signed and
sealed by a Florida-registered engineer, in attached single- and multiple-family
units, the capacity of equipment may be sized in accordance with good design
practice.
403.6.1.2 Heating equipment capacity.
403.6.1.2.1 Heat Pumps. Heat pump sizing shall be based on the cooling
requirements as calculated according to Section 403.6.1.1 and the heat pump
total cooling capacity shall not be more than 1.15 times greater than the
design cooling load even if the design heating load is 1.15 times greater than
the design cooling load.
403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within
4 kW of the design requirements calculated according to the procedure selected
in Section 403.6.1.
403.6.1.2.3 Fossil fuel heating
equipment. The capacity of fossil fuel
heating equipment with natural draft atmospheric burners shall not be less than
the design load calculated in accordance with Section 403.6.1.
403.6.1.3 Extra capacity required for special occasions. Residences requiring excess
cooling or heating equipment capacity on an intermittent basis, such as
anticipated additional loads caused by major entertainment events, shall have
equipment sized or controlled to prevent continuous space cooling or heating
within that space by one or more of the following options:
1. A separate
cooling or heating system is utilized to provide cooling or heating to the
major entertainment areas.
2. A variable
capacity system sized for optimum performance during base load periods is
utilized.
403.6.2 Equipment performance standards.
403.6.2.1 Equipment ratings. Equipment
efficiency ratings shall be obtained from a nationally recognized certification
program directory, or from a manufacturer’s rating certified to be in
compliance with an approved Department of Energy (DOE) or Air-conditioning,
Heating and Refrigeration Institute (AHRI) rating procedure. Equipment efficiencies shall be
based on the standard rating conditions contained in the test standard
referenced in Chapter 6 that is appropriate for that equipment. Minimum ratings
for products covered under the National Appliance Energy Conservation Act of
1987 shall be those determined for Region IV and used for the Federal Trade
Commission’s required appliance labeling.
403.6.2.1.1 Equipment efficiency verification. Equipment covered under the Federal Energy Policy
Act of 1992 (EPACT) shall comply with
403.6.2.2 Minimum efficiencies for
cooling equipment.
Residential
sized cooling and heating equipment shall meet the minimum efficiencies of
Table 403.6.2.2(1) through 403.6.2.2 (3) of this section. Cooling systems not
covered in this section shall meet the minimum efficiencies listed for that
type of system in Section 503 of this code. Equipment used to provide water heating functions as part of a
combination system shall satisfy all stated requirements for the appropriate
space heating or cooling category.
Exception: Existing mechanical systems
undergoing alteration need not meet the minimum equipment efficiencies of this
section except to preserve the original approval or listing of the equipment.
TABLE 403.6.2.2(1)
ELECTRICALLY OPERATED UNITARY
AIR CONDITIONERS AND CONDENSING UNITS
Equipment
Type |
Size Category |
Heating
Section Type |
Sub-Category
or Rating
Condition |
Minimum
Efficiency2 |
Test Procedure1 |
Air
Conditioners, Air Cooled |
<65,000
Btu/h3 |
All |
|
13.0 SEER |
ARI 210/240 |
Single Package |
13.0 SEER |
||||
≥65,000
Btu/h and <135,000 Btu/h |
Electric Resistance (or None) |
|
10.3 EER |
ARI 340/360 |
|
All other |
|
10.1 EER |
|||
Through-the
Wall, Air-cooled |
<30,000
Btu/h3 |
All |
|
10.9 SEER |
ARI 210/240 |
Single Package |
10.6 SEER |
||||
Small-Duct
High-Velocity, Air cooled |
<65,000
Btu/h3 |
All |
Split system or Single Package |
11.0 SEER |
ARI 210/240 |
Space
constrained products, air conditioners |
<65,000
Btu/h3 |
All |
Split system or Single Package |
12.0 SEER4 |
ARI 210/240 |
Air
Conditioners, Water and Evaporatively Cooled |
<65,000
Btu/h |
All |
|
12.1 EER |
ARI 210/240 |
≥65,000
Btu/h and <135,000 Btu/h |
Electric Resistance (or None) |
|
11.5 EER |
ARI 340/360 |
|
All other |
|
11.3 EER |
1 Chapter 6
contains a complete specification of the reference test procedure, including
the referenced year version of the test procedure.
2 IPLVs and part
load rating conditions are only applicable to equipment with capacity
modulation.
3 Single-phase,
air-cooled air-conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.
4As granted by
U.S. Department of Energy letter of exception, specific to individual
companies, SDHV products without a letter of exception
shall have the same efficiency as air-cooled
air-conditioners.
TABLE 403.6.2.2(2)
ELECTRICALLY OPERATED UNITARY
AND APPLIED HEAT PUMPS
– MINIMUM EFFICIENCY
REQUIREMENTS
Equipment
Type |
Size Category |
Heating
Section Type |
Sub-Category
or Rating Condition |
Minimum Efficiency2 |
Test
Procedure1 |
Air Cooled
(Cooling Mode) |
<65,000
Btu/h3 |
All |
|
13.0 SEER |
ARI 210/240 |
Single Package |
13.0 SEER |
||||
≥65,000
Btu/h and <135,000 Btu/h |
Electric
Resistance (or None) |
|
10.1 EER |
||
All other |
|
9.9 EER |
|||
Through-the
Wall, Air-cooled |
≤30,000
Btu/h3 |
All |
|
10.9 SEER |
ARI 210/240 |
Single Package |
10.6 SEER |
||||
Small-Duct
High-Velocity, Air cooled |
<65,000
Btu/h3 |
All |
|
11.0 SEER |
ARI 210/240 |
Water Source
(Cooling Mode) |
<17,000
Btu/h |
All |
86oF Entering Water |
11.2 EER |
ISO-13256-1 |
≥17,000
Btu/h and <135,000 Btu/h |
All |
86oF Entering Water |
12.0 EER |
||
Groundwater
Source (Cooling Mode) |
<135,000
Btu/h |
All |
59oF Entering Water |
16.2 EER |
|
Ground Source (Cooling
Mode) |
<135,000
Btu/h |
All |
77oF Entering Water |
13.4 EER |
|
Air Cooled (Heating
Mode) |
<65,000
Btu/h3 (Cooling
Capacity) |
|
|
7.7 HSPF |
ARI 210/240 |
Single Package |
7.7 HSPF |
||||
≥65,000
Btu/h and <135,000 Btu/h (Cooling Capacity) |
|
47oF db/43oF wb Outdoor Air |
3.2 COP |
ARI 340/360 |
|
17oF db/15oF wb Outdoor Air |
2.2 COP |
||||
Through-the
Wall, Air-cooled, heating mode) |
≤30,000
Btu/h3 (Cooling
Capacity) |
|
|
7.1 HSPF |
ARI 210/240 |
Single Package |
7.0 HSPF |
||||
Small-Duct
High-Velocity, Air cooled, heating mode |
<65,000
Btu/h3 (Cooling
Capacity) |
|
|
6.8 HSPF4 |
ARI 210/240 |
Space
constrained products, heap pumps |
<65,000
Btu/h3 |
|
|
7.4 HSPF |
ARI 210/240 |
Water-Source (Heating
Mode) |
<135,000
Btu/h (Cooling Capacity) |
|
68oF Entering Water |
4.2 COP |
I ISO-13256-1 |
Groundwater
Source (Heating
Mode) |
<135,000
Btu/h (Cooling Capacity) |
|
50oF Entering Water |
3.6 COP |
|
Ground Source (Heating
Mode) |
<135,000
Btu/h (Cooling Capacity) |
|
32oF Entering Water |
3.1 COP |
1 Chapter 6
contains a complete specification of the reference test procedure, including
the referenced year version of the test procedure.
2 IPLVs and Part
Load rating conditions are only applicable to equipment with capacity
modulation.
3 Single-phase,
air-cooled heat pumps <65,000 Btu/h are regulated by NAECA. SEER and HSPF values are those set by NAECA.
4As granted by
U.S. Department of Energy letter of exception, specific to individual
companies, SDHV products without a letter of exception
shall have the same efficiency as air-cooled
air-conditioners.
TABLE 403.6.2.2(3)
ELECTRICALLY OPERATED PACKAGED
TERMINAL AIR CONDITIONERS, PACKAGED TERMINAL HEAT PUMPS, SINGLE-PACKAGE
VERTICAL AIR CONDITIONERS, SINGLE-PACKAGE VERTICAL HEAT PUMPS, ROOM AIR CONDITIONERS, AND
ROOM AIR CONDITIONERS HEAT PUMPS — MINIMUM EFFICIENCY REQUIREMENTS
Equipment Type |
Size Category |
Subcategory or Rating
Condition |
Minimum Efficiency1 |
Test Procedure2 |
|
>15,000
Btu/h |
|
2.51 COP |
|
Room Air
Conditioners with Louvered Sides |
<8,000 |
|
9.7 EER |
ANSI/ AHAM RAC-1 |
>8,000<14,000Btu/h |
|
9.8 EER |
||
>14,000<20,000Btu/h |
|
9.7 EER |
||
>20,000
Btu/h |
|
8.5 EER |
||
Room Air
Conditioners, without Louvered Sides |
<8,000
Btu/h |
|
9.0 EER |
|
>8,000
Btu/h |
|
8.5 EER |
||
Room Air
Conditioner Heat Pumps with Louvered Sides |
<20,000
Btu/h ≥20,000
Btu/h |
|
9.0 EER 8.5 EER |
|
Room Air
Conditioner Heat Pumps without Louvered Sides |
<14,000
Btu/h |
|
8.5 EER |
|
≥14,000
Btu/h |
|
8.0 EER |
||
Room Air
Conditioner, Casement only |
All
Capacities |
|
8.7 EER |
|
Room Air
Conditioner, Casement-Slider |
All
Capacities |
|
9.5 EER |
1 Chapter 6
contains a complete specification of the referenced test procedure, including
the referenced year version of the test procedure.
2 Replacement
units must be factory labeled as follows: “MANUFACTURED FOR REPLACEMENT
APPLICATIONS ONLY; NOT TO BE
INSTALLED IN NEW CONSTRUCTION PROJECTS.” Replacement
efficiencies apply only to units with existing sleeves less than 16 in. high
and less than 42 in. wide.
3 Cap means the
rated cooling capacity of the product in Btu/h. If the unit’s capacity is less
than 7,000 Btu/h, use 7,000 Btu/h in the calculation.
If the unit’s capacity is greater than 15,000
Btu/h, use 15,000 Btu/h in the calculation.
403.6.2.3 Minimum efficiencies for heating equipment. Residential
sized heating equipment shall meet the minimum efficiencies of Table
403.6.2.3(1) through 403.6.2.3(2) of this section. Heating systems not covered
in this section shall meet the minimum efficiencies listed for that type of
system in Section 503 of this code.
Exception: Existing mechanical systems
undergoing alteration need not meet the minimum equipment Efficiencies of this
section except to preserve the original approval or listing of the equipment
403.6.2.3.1 Gas and oil-fired furnaces. Gas-fired and oil-fired forced
air furnaces with input ratings >225,000 Btu/h shall also have an
intermittent ignition or interrupted device (IID) and have either power venting
or a flue damper. A vent damper is an acceptable alternative to a flue damper
for furnaces where combustion air is drawn from the conditioned space. All
furnaces with input ratings >225,000 Btu/h, including electric furnaces,
that are not located within the conditioned space shall have jacket losses not
exceeding 0.75 percent of the input.
403.6.2.3.2 Central electric furnaces. Central electric furnaces
greater than 10 kW shall be divided into at least two stages and controlled by
an outdoor thermostat, multistage indoor thermostat, or combinations thereof.
TABLE 403.6.2.3(1)
WARM AIR FURNACES AND
COMBINATION WARM AIR FURNACES/AIR-CONDITIONING UNITS, WARM AIR DUCT FURNACES
AND UNIT HEATERS MINIMUM
EFFICIENCY REQUIREMENTS
Equipment
Type |
Size Category |
Subcategory
or Rating Condition |
Minimum
Efficiency1 |
Test
Procedure2 |
Warm Air
Furnace, Gas-Fired |
<225,000
Btu/h |
Maximum
Capacity4 |
78% AFUE or
80% Et4 |
DOE 10 CFR,
Part 430 or ANSI Z 21.47 |
≥225,000
Btu/h |
80% Ec3 |
ANSI Z21.47 |
||
Warm Air
Furnace, Oil-Fired |
<225,000
Btu/h |
Maximum
Capacity4 |
78% AFUE or |
DOE 10 CFR,
Part 430 or UL 727 |
≥225,000
Btu/h |
81% Et6 |
UL 727 |
||
Warm Air Duct
Furnaces, Gas-Fired |
All
Capacities |
Maximum
Capacity5 |
80% Ec7 |
ANSI Z83.8 |
Warm Air Unit
Heaters, Gas-Fired |
All Capacities |
Maximum
Capacity5 |
80% Ec7 |
ANSI Z83.8 |
Warm Air Unit
Heaters, Oil-Fired |
All Capacities |
Maximum
Capacity5 |
80% Ec7 |
UL 731 |
1 Et = thermal efficiency. See test
procedure for detailed discussion.
2 Chapter 6
contains a complete specification of the referenced test procedure, including
the referenced year version of the test procedure.
3 Ec = combustion efficiency. Units must
also include an IID, have jacket losses not exceeding 0.75% of the input rating,
and have either power venting or a flue damper. A vent damper is an acceptable
alternative to a flue damper for those furnaces where combustion air is drawn
from the conditioned space.
4 Combination
units not covered by NAECA (3 phase power or cooling capacity greater than or
equal to 65,000 Btu/h) may comply with either rating.
5 Minimum and maximum ratings as provided for and allowed
by the unit’s controls.
6 Et = thermal
efficiency. Units must also include an IID, have jacket losses not exceeding 0.75%
of the input rating, and have either power venting or a flue damper. A vent
damper is an acceptable alternative to a flue damper for those furnaces where
combustion air is drawn from the conditioned space.
7 Ec = combustion efficiency (100% less flue losses).
See test procedure for detailed discussion.
TABLE 403.6.2.3(2)
Gas- and Oil-Fired Boilers
Minimum Efficiency Requirements
Equipment
Type4 |
Size Category
(Input) |
Subcategory
or Rating Condition |
Minimum
Efficiency1 |
Test
Procedure2 |
Boilers,
Gas-Fired |
<300,000
Btu/h |
Hot water |
80% AFUE |
DOE 10 CFR
Part 430 |
Steam |
75% AFUE |
|||
Boilers,
Oil-Fired |
<300,000
Btu/h |
|
80% AFUE |
DOE 10 CFR
Part 430 |
1 Et = thermal efficiency. See reference documents for
detailed information.
2 Chapter 6
contains a complete specification of the referenced test procedure, including
the referenced year version of the test procedure.
3 Minimum
and maximum ratings as provided for and allowed by the unit’s controls.
4 These requirements apply to boilers with rated input of
8,000,000 Btu/h or less that are not packaged boilers, and to all package
boilers. Minimum efficiency requirements for boilers cover all
capacities of packaged boilers.
403.7 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units and equipment not covered by Section 403.6.2 shall comply with Sections 503 and 504 in lieu of Section 403.
403.8 Snow melt system controls
(Mandatory). Reserved. Snow- and ice-melting systems,
supplied through energy service to the building, shall include automatic
controls capable of shutting off the system when the pavement temperature is
above 50°F, and no precipitation is falling and an automatic or manual control
that will allow shutoff when the outdoor temperature is above 40°F.
403.9 Pools (Mandatory). Pools shall be provided with
energy-conserving measures in accordance with Sections 403.9.1 through 403.9.3.
403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-off switch to allow shutting off the heater without adjusting the thermostat setting.
403.9.1.1 Gas and oil-fired pool
and spa heaters. All gas-
and oil-fired pool and spa heaters shall have a minimum thermal efficiency of
78 percent when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural gas shall not
have continuously burning pilot lights.
403.9.1.2 Heat
pump pool heaters. Heat pump pool heaters shall
have a minimum COP of 4.0 when tested in accordance with ARI 1160, Table 2, Standard Rating Conditions-Low Air Temperature. A test
report from an independent laboratories is required to
verify procedure compliance.
403.9.2 Time switches. Time switches shall be
installed on swimming pool heaters and pumps that can automatically turn off
and on the heaters and pumps off and on according to a preset
schedule shall be installed on swimming pool heaters and pumps.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Where pumps are required to operate solar- and waste-heat-recovery pool heating systems.
403.9.3 Pool covers. Heated swimming pools and spas shall be equipped with a vapor-retardant pool cover on or at the water surface. Pools heated to more than 90°F (32°C) shall have a pool cover with a minimum insulation value of R-12.
Exception: Outdoor
pPools
deriving over 70
60 percent of the energy for heating from site-recovered energy or
solar energy source computed
over an operating season.
SECTION 404
ELECTRICAL POWER AND LIGHTING SYSTEMS
404.1 Lighting
equipment (Prescriptive). A minimum of 50 percent of the lamps in
permanently installed lighting fixtures shall be high-efficacy lamps.
SECTION 405
SIMULATED PERFORMANCE ALTERNATIVE
(Performance)
405.1 Scope. This section
establishes criteria for compliance using simulated energy performance analysis.
Such analysis shall include heating, cooling, and service water heating energy
only.
405.2 Mandatory
requirements. Compliance with this section requires that the mandatory
provisions identified in Section 401.2 be met. All supply and return ducts not
completely inside the building thermal envelope shall be
insulated to a minimum of R-6.
405.3
Performance-based compliance. Compliance based on simulated energy
performance requires that a proposed residence (proposed
design) be shown to have an annual normalized, modified energy load that
is less than or equal to the annual energy load of the standard
reference design. code official, such as the
Department of Energy, Energy Information Administration’s State Energy
Price and Expenditure Report. Code officials shall be
permitted to require time-of-use pricing in energy cost calculations.
405.4
Documentation.
405.4.1 Compliance software tools. Documentation
verifying that the methods and accuracy of tThe Energy
Gauge USA Fla/Res compliance software tools
shall be utilized to conform to the provisions of this section.
shall be provided to the code
official.
405.4.2 Compliance report. The cCompliance software tools
shall generate a Form 405 report that documents that the proposed
design complies with Section 405.3. The compliance documentation shall be submitted to the building
official before a building permit is issued and shall include the
following information:
1. Address or other identification of the residence;
2. An inspection checklist documenting the building component
characteristics of the proposed design as listed in
Table 405.5.2(1). The inspection checklist shall show results for both the standard
reference design and the proposed design, and shall
document all inputs entered by the user necessary to reproduce the results;
3. Name of individual completing the compliance report; and
4. Name and version of the compliance software tool.
Exception: Worst case calculations for mMultiple orientations. When an otherwise identical
building model is offered in multiple orientations or with improved component or equipment
alternatives, compliance for any orientation shall be permitted by
documenting that the building meets the performance requirements for the worst case component or
equipment alternative(s) and in each of the four cardinal (north, east, south
and west) orientations.
405.4.3 Additional documentation. The code
official shall be permitted to require the following documents:
1.
Documentation of the building component characteristics of the standard
reference design.
2. An EPL
Display Card certification signed by the builder providing
the building component characteristics of the proposed design (as given in
Table 405.5.2(1)) to
be provided to the
purchaser of the home at time of title transfer.
3. Documentation of the component efficiencies actual
values used in the software calculations for the proposed
design.
405.5
Calculation procedure.
405.5.1 General. Except as
specified by this section, the Standard Reference Design and Proposed Design
shall
be configured and analyzed using identical methods and techniques. The Standard Reference Design totals for the Simulated Performance
Alternative compliance method developed in accordance with the criteria in Sections
405.5.2 and 405.3 shall be adjusted by a factor of 0.80 to make the code 20
percent more stringent than the “2007” Florida energy code’s Standard Reference Design (Baseline) features.
405.5.2 Residence specifications. The Standard Reference Design and Proposed Design shall be configured and analyzed as specified by Table 405.5.2(1). Table 405.5.2(1) shall include by reference all notes contained in Table 402.1.1.
405.5.3 Envelope calculation
requirements.
405.5.3.1 Glass areas. All glazing areas of a
residence, including windows, sliding glass doors, glass in doors, skylights,
etc. shall include the manufacturer’s frame area in the total window area.
Window measurements shall be as specified on the plans and specifications for
the residence.
Exception: When a window in existing exterior walls is enclosed by
an addition, an amount equal to the area of this window may be subtracted from
the glazing area for the addition for that overhang and orientation.
405.5.3.2 Overhangs. Overhang effect is measured by
Overhang Separation, which is the vertical measure of the distance from the top
of a window to the bottom of the overhang.
The overhang for adjustable exterior shading devices shall be determined
at its most extended position. Nonpermanent shading devices such as canvas awnings shall
not be considered overhangs. Permanently attached wood and metal awnings may be
considered overhangs.
405.5.3.3 Doors
with glazing. For doors that are opaque or where the glass is
less than one-third of the area of the door, the total door area shall be included
in the door calculation. For unlabeled sliding glass doors
or when glass areas in doors is greater than or equal to one-third of the area
of the door, the glazing portion shall be included in the glazing calculation
and the opaque portion of the door shall be included in the door calculation.
When glass area in doors is greater than or equal to one-third of the area of
the door, the door shall be included in
the glazing calculation as a total fenestration using the tested
U-factor and solar heat gain coefficient.
405.5.4.
Equipment calculation of End Use Energy Loads for Code Compliance
Determination.
405.5.4.1
The energy loads for heating, cooling and hot water in the Proposed Design home shall be normalized to account for the
differences in improvement potential that exist across equipment types using
the following formula in accordance with the paper "The HERS Rating Method
and the Derivation of the Normalized Modified Loads Method," Research
Report No. FSEC-RR-54-00,
nMEUL =
REUL * (nEC_x /EC_r)
where:
nMEUL = normalized Modified End Use Loads (for heating,
cooling or hot water) as computed using EnergyGauge
EC_r = estimated
Energy Consumption for the Standard
Reference Design Home’s end uses (for heating, including auxiliary electric
consumption, cooling or hot water) as computed using EnergyGauge USA Fla/Res.
and
where: nEC_x
= (a* EEC_x – b)*(EC_x * EC_r * DSE_r) / ( EEC_x * REUL)
where:
nEC_x = normalized Energy Consumption for Proposed Design’s end uses (for heating,
including auxiliary electric consumption, cooling or hot water) as computed
using EnergyGauge
EC_r = estimated Energy Consumption for Standard Reference Design home’s end uses (for heating, including
auxiliary electric consumption, cooling or hot water) as computed using
EnergyGauge USA Fla/Res.
EC_x = estimated Energy Consumption for the Proposed Design home’s end uses (for
heating, including auxiliary electric consumption, cooling or hot water) as
computed using EnergyGauge USA Fla/Res.
EEC_x = Equipment Efficiency Coefficient for the Standard Reference Design home’s
equipment, such that
EEC_x equals the energy consumption per unit load in like
units as the load, and as derived from the Manufacturer’s Equipment Performance
Rating (MEPR) such that
EEC_x equals 1.0 / MEPR for AFUE, COP or EF
ratings, or such that EEC_x equals 3.413 / MEPR for
HSPF, EER or SEER ratings.
DSE_r =
REUL/EC_r * EEC_r
For simplified system performance
methods, DSE_r equals 0.80 for heating and cooling
systems. However, for detailed modeling of heating and cooling systems, DSE_r may be less than 0.80 as a result of part load
performance degradation, coil air flow degradation, improper system charge and
auxiliary resistance heating for heat pumps. Except as otherwise provided by
these Standards, where detailed systems modeling is employed, it must be
applied equally to both the Standard Reference
Design and the Proposed Design homes.
EEC_r = Equipment Efficiency Coefficient for the Standard Reference Design home’s
equipment, such that EEC_r equals the energy
consumption per unit load in like units as the load, and as derived from the
Manufacturer’s Equipment Performance Rating (MEPR) such that EEC_r equals 1.0 / MEPR for AFUE, COP or EF ratings, or
such that EEC_r equals 3.413 / MEPR for HSPF, EER or
SEER ratings.
REUL
= Standard Reference Design home End
Use Loads (for heating or cooling) as
computed using EnergyGauge USA Fla/Res.
and where the coefficients ‘a’ and ‘b’ are
as defined by Table 405.5.2(3).
405.5.4.2 Following normalization of the heating, cooling and hot
water energy consumptions for the Proposed
Design home as specified in Section
405.5.3 above, the Standard Reference
Design home’s total reference end use loads for heating, cooling and hot
water (REULtot) shall be compared with the Proposed Design home’s total normalized
modified end use loads for heating, cooling and hot water (nMEULtot). If the total normalized modified loads of the
Proposed Design home (nMEULtot) are equal to or less than the total reference
loads of the Standard Reference Design
home (REULtot), the Proposed Design complies with this code.
405.5.5 Requirements specific to credit options. Credit may be claimed in
the software compliance calculation for technologies that meet prescriptive criteria specified below for various options.
405.5.5.1 Installation criteria for homes claiming the
radiant barrier option. The sheet radiant barrier or IRCC options may be claimed
where the radiant barrier system is to be installed in one of the
configurations depicted in Figure 405.5.4.1 and the following conditions are
met:
1. It shall be
fabricated over a ceiling insulated to a minimum of R-19 with conventional
insulation and shall not be used as a means to achieve partial or whole
compliance with a minimum attic insulation level of R-19. Either a sheet type
or spray applied interior radiation control coating (IRCC) may be used.
2. If the radiant
barrier material has only one surface with high reflectivity or low emissivity
it shall be facing downward toward the ceiling insulation.
3. The attic airspace shall be
vented in accordance with Section R806 of the Florida Building Code, Residential.
4. The radiant
barrier system shall conform to ASTM C 1313, Standard Specification for Sheet
Radiant Barriers for Building Construction Applications, or ASTM C 1321,
Standard Practice for Installation and Use of Interior Radiation Control
Coating Systems (IRCCS) in Building Construction as appropriate for the type of
radiant barrier to be installed. The operative surface shall have an emissivity
not greater than 0.06 for sheet radiant barriers or 0.25 for interior radiation
control coatings as demonstrated by independent laboratory testing according to
ASTM C 1371.
5. The radiant
barrier system (RBS) shall conform with ASTM C 1158, Use and Installation of
Radiant Barrier Systems (RBS) in Building Constructions for Sheet Radiant
Barriers, or ASTM C 1321, Standard Practice for Installation and Use of
Interior Radiation Control Coating Systems (IRCCS) in Building Construction for
IRCC systems.
6. The radiant barrier shall be
installed so as to cover gable ends without closing off any soffit, gable or
roof ventilation.
FIGURE 405.5.5.1
ACCEPTABLE ATTIC RADIANT BARRIER
CONFIGURATIONS
[No change to figure]
405.5.5.2
Installation criteria for homes claiming the cool roof option. The cool roof option may be claimed
where the roof to be installed has a tested solar reflectance of greater than 4
percent when evaluated in accordance with ASTM methods E-903, C-1549, E-1918 or
CRRC Method #1. Emittance values provided by the
roofing manufacturer in accordance with ASTM C 1371 shall be used when
available. In cases where the
appropriate data are not known, emittance shall be
the same as the Standard Reference Design. Testing of a qualifying sample of
the roofing material shall be performed by an approved independent laboratory
with these results provided by the manufacturer.
405.5.5.3 Installation criteria for homes using the
unvented attic assembly option. The unvented attic assembly option may be used if the
criteria in Section R806.4 of the
405.5.5.4 Installation criteria for homes using the cross
ventilation option. The cross ventilation option may
be used if the following criteria have been met.
1. Operable aperture areas totaling a minimum of 12
percent of the floor area of the room shall be provided for all primary living
areas and main bedrooms.
2. Insect screens shall be provided for all windows and
doors to be considered operable aperture area. All screened entry doors and
interior doors in the ventilated areas shall be provided with either (1)
mechanically attached door stops (or similar devices) to hold the door in an
open position or (2) operable louvers.
3. The total aperture area shall be provided by a minimum
of two distinct windows. Each window shall provide not more than 70 percent of
the total aperture area. The windows (or sliding glass doors) shall be placed
in adjacent or opposite walls. The windows may be placed on a single outside
wall if wing walls are used.
4. Where wing walls are included
in the building design for ventilation purposes, they shall be placed between
windows to create a high-pressure and a low-pressure zone on each window. Wing
walls shall extend from the ground to eve height, be located on the windward
side of the building, and extend outward from the building a distance at least
equal to one-half the width of the window. NOTE: This technique is effective
only for areas which experience significant and continuous winds during the
cooling months.
405.5.5.5 Installation criteria
for homes using the whole house fan option.
The
whole house fan option may be used if the following criteria have been met.
1. The whole house fan has been sized to provide a
minimum of 20 air changes per hour for the entire house.
2. The fan installed shall have a free air cfm rating of at least three times the square footage of
the conditioned area of the house.
3. To ensure adequate air
exhaust, the house attic shall have gable, ridge or wind turbine vents whose
total opening area is equal to four times the ceiling cutout area for the whole
house fan. Soffit vents shall not be included in the exhaust vent area.
405.6
Calculation software tools.
405.6.1 Minimum capabilities. Calculation procedures used to
comply with this section shall be software tools capable of calculating the
annual energy consumption of all building elements that differ between the standard
reference design and the proposed design and shall
include the following capabilities:
1. Computer generation of the standard reference design using only the
input for the proposed design. The calculation procedure shall not allow
the user to directly modify the building component characteristics of the standard
reference design.
2. Calculation of whole-building (as a single zone) sizing for
the heating and cooling equipment in the standard reference design residence in
accordance with Section 403.6 M1401.3 of the International
Residential Code.
3. Calculations that account for the effects of indoor and outdoor
temperatures and part-load ratios on the performance of heating, ventilating and
air-conditioning equipment based on climate and equipment sizing.
4. Printed code official inspection
checklist listing each of the proposed design component
characteristics from Table 405.5.2(1) determined by the analysis to provide
compliance, along with their respective performance ratings (e.g., R-value, U-factor, SHGC,
HSPF, AFUE, SEER, EF, etc.)
405.6.2 Specific approval. The pPerformance analysis tools
shall be approved by the meeting
the applicable sections of Section 405 shall be permitted to be approved. Tools are
permitted to be approved based on
meeting a specified threshold for a jurisdiction. The code
official shall be permitted to approve tools for a specified application or
limited scope.
405.6.3 Input values. When calculations require input values not
specified by Sections 402, 403, 404 and 405, those input values shall be taken
from an approved source.
TABLE 405.5.2(1)
SPECIFICATIONS FOR
THE STANDARD REFERENCE AND PROPOSED DESIGNS
Building
Component |
Standard
Reference Design |
Proposed
Design |
Above-grade
walls: |
Type:
Gross
area: same as proposed U-Factor:
0.082 Solar
absorptance = 0.75 Emittance = 0.90 |
As
proposed As
proposed As
proposed As
proposed As
proposed |
Conditioned basement |
Type:
same as proposed Gross
area: same as proposed U-Factor:
0.36 with the insulation layer on the interior side of walls |
As
proposed As
proposed As
proposed |
|
Type:
wood frame Gross
area: same as proposed U-Factor:
0.064 |
As
proposed As
proposed As
proposed |
Ceilings:
|
Type:
Wood frame Gross
area: same as proposed U-Factor:
0.035 |
As
proposed As
proposed As
proposed |
Roofs:
|
Type:
composition shingle on wood sheathing Gross
area: same as proposed Solar
absorptance = 0.75 Emittance = 0.90 |
As
proposed As
proposed As proposed, except
that proposed solar absorptances less than 0.96
require test report in accordance with section ???? As
proposed |
Attics:
|
Type:
vented with aperture = 1 ft2 per 300 ft2 ceiling area |
As
proposed |
Foundations:
|
Type:
same as proposed Foundation
wall area above and below grade and soil characteristics: same as proposed Gross Area: same as proposed R-value: 0 |
As
proposed As
proposed As
proposed |
Crawlspaces: |
Type: vented with net free vent
aperture = 1 ft2 per 150 ft2 of crawlspace foor area. |
Same as proposed, but not less net free ventilation area
than the Standard Reference Design unless
an approved ground cover in accordance with Section 408.1 of the Florida
Building Code, Residential, is used, in which case, the same net free
ventilation area as the Proposed Design
home down to a minimum net free vent area of 1 ft2 per 1,500 ft2
of crawlspace floor area. |
Doors:
|
Area:
40 ft2 Orientation:
North U-factor: 0.75 |
As
proposed As
proposed As
proposed |
Glazing:
(a) |
Total
area (b)
Orientation:
equally distributed to four (4) cardinal compass orientations
(N,E,S&W) U-factor:
0.75 SHGC:0.40
Interior shade coefficient
Summer Winter External
shading: none |
As
proposed As
proposed As
proposed As proposed
As
proposed (c) As
proposed As
proposed |
Skylights |
None |
As
proposed |
Thermally
isolated sunrooms |
None
|
As
proposed |
Air
exchange rate |
Specific
Leakage Area (SLA) (d) = 0.00036 (assuming no energy recovery) |
For
residences that are not tested, the same as the Baseline Home. For
residences with mechanical ventilation systems and with envelope leakage
tested in accordance with ASHRAE Standard 119, Section 5.1, the measured air
exchange rate (e) combined with the proposed mechanical ventilation rate (f) Where: CFA
= conditioned floor area Nbr = number of bedrooms |
Mechanical
ventilation: |
None,
except where a mechanical ventilation system is specified by the proposed
design, in which case: Annual
vent fan energy use: kWh/yr
= 0.03942*CFA + 29.565 * (Nbr+1) (per dwelling unit) where:
CFA = conditioned floor area Nbr =
number of bedrooms |
As
proposed As
proposed |
Internal
gains: |
IGain = 17,900 + 23.8*CFA + 4104*Nbr (Btu/day per dwelling unit) |
Same
as reference design |
Internal
mass: |
An
internal mass for furniture and contents of 8 pounds per square foot of floor
area |
Same
as reference design plus any additional mass specifically designed as a
Thermal Storage Element (g,f) but not integral to
the building envelope or structure |
Structural
mass: |
For
masonry floor slabs, 80% of floor area covered by R-2 carpet and pad, and 20%
of floor directly exposed to room air. For
masonry basement walls, as proposed, but with insulation For
other walls, for ceilings, floors, and interior walls, wood frame
construction. |
As
proposed As
proposed . |
Heating
systems (g,h) |
Fuel type: same as Proposed Design efficiencies:
Electric: air source heat pump with
prevailing federal minimum efficiency Non-electric
furnaces: natural gas furnace with prevailing federal minimum efficiency Non-electric
boilers: natural gas boiler with prevailing federal minimum efficiency Capacity: sized in accordance with |
As
proposed(i) As
proposed As
proposed As
proposed As
proposed |
Cooling
systems (h,k) |
Fuel type: Electric Efficiency: in accordance with
prevailing federal minimum standards Capacity: sized in accordance with Section 403.6.1
|
As
proposed (k) As
proposed As
proposed |
Service
water heating systems |
Fuel type:same
as Proposed Design Efficiency: in accordance with
prevailing federal minimum standards Use: where Ndu
= number of dwelling units Tank temperature: 120 F |
As
proposed(m) As
proposed As
proposed As
proposed |
Thermal
distribution systems: |
A thermal distribution system efficiency
(DSE) of 0.80 |
Using Proposed Design duct locations and a DSE of 0.88, except
when tested in accordance with ASHRAE Standard 152(n),
in which case measured duct air leakage values shall be used. |
Thermostat
|
Type: manual Temperature setpoints:
cooling temperature set point = heating temperature set point = |
Type: Same As proposed
Temperature setpoints:
same as the Standard Reference Design,
except when programmable thermostats are used. |
Notes:
(a) Glazing shall be defined as
sunlight-transmitting fenestration, including the area of sash, curbing or
other framing elements, that enclose conditioned space. Glazing includes the
area of sunlight-transmitting fenestration assemblies in walls bounding
conditioned basements. For doors where
the sunlight-transmitting opening is less than one-third of the door area, the
glazing area of the sunlight transmitting opening shall be used. For all other doors, the glazing area shall
be the rough frame opening area for the door, including the door and the frame.
(b) For residences with conditioned basements and for multiple family attached
homes the following formula shall be used to determine total window area:
AF = 0.18 x AFL x FA x F
where:
AF = Total fenestration area
AFL = Total floor area of directly conditioned space
FA = (Above-grade thermal boundary gross wall area) / (above-grade boundary gross wall area + 0.5 x
below-grade boundary gross wall area)
F = (Above-grade thermal boundary gross wall
area) / (above-grade thermal boundary gross wall area + common gross wall area) or 0.56 whichever is
greater
and where:
Thermal boundary wall is any wall that
separates conditioned space from unconditioned space or ambient conditions
Above-grade thermal
boundary wall
is any portion of a thermal boundary wall not in contact with soil
Below-grade boundary
wall is
any portion of a thermal boundary wall in soil contact
Common wall is the total wall area
of walls adjacent to another conditioned living unit, not including common
foundation and attic walls.
(c) For fenestrations facing within 15
degrees of due south that are directly coupled to thermal storage mass, the
winter interior shade coefficient shall be permitted to increase to 0.95 in the
proposed design.
(d) Where Leakage Area (L) is defined in
accordance with Section 5.1 of ASHRAE Standard 119 and where:
Hourly calculations
using the procedures given in the ASHRAE Handbook of Fundamentals,
Chapter 27, page 27.21, equation 40
(Sherman-Grimsrud model) using Shelter Class 4 shall
be used to determine the air exchange rate resulting from infiltration.
(e) Tested
envelope leakage shall be determined in accordance with Section 5.1 of ASHRAE
Standard 119 and documented by a Certified Class 1
(f) The combined air exchange rate for
infiltration and mechanical ventilation shall be determined in accordance with
Equation 43 of ASHRAE Handbook
of Fundamentals page 27.23.
(g) Thermal storage element shall mean a
component not normally part of the floors, walls, or ceilings that is part of a
passive solar system, and that provides thermal storage such as enclosed water
columns, rock beds, or phase change containers. A thermal storage element must
be in the same room as fenestration that faces within 15 degrees of due south,
or must be connected to such a room with pipes or ducts that allow the element
to be actively charged.
(h) For a Proposed Design with multiple heating,
cooling, or water heating systems using different fuel types, the applicable
system capacities and fuel types shall be weighted in accordance with the loads distribution (as
calculated by accepted engineering practice for that equipment and fuel type) of the subject multiple
systems. For the Standard Reference
Design, the prevailing federal minimum efficiency shall be assumed except
that the efficiencies given in Table 405.5.2(2) below will be assumed when:
1)
A type of device not covered by NAECA
is found in the As-Built Home;
2)
The Proposed Design is heated by
electricity using a device other than an air source heat pump; or
3)
The Proposed Design does not contain
one or more of the required HVAC equipment systems.
TABLE 405.5.2(2)
DEFAULT STANDARD REFERENCE DESIGN HOME
Heating and Cooling Equipment Efficiencies (i)
(k) (m) (n)
As-Built Home Fuel |
Function |
Baseline Home Device |
Electric |
Heating |
7.7 HSPF air source heat pump |
Non-electric warm air furnace or
space heater |
Heating |
78% AFUE gas furnace |
Non-electric boiler |
Heating |
80% AFUE gas boiler |
Any type |
Cooling |
13 SEER electric air conditioner |
(i) For a Proposed Design
without a proposed heating system, a heating system with the prevailing federal
minimum efficiency shall be assumed for both the Standard Reference Design home and Proposed Design home. For electric heating systems, the prevailing
federal minimum efficiency air-source heat pump shall be selected.
(k) For an Proposed Design home without a proposed
cooling system, an electric air conditioner with the prevailing federal minimum
efficiency shall be assumed for both the Standard
Reference Design and the Proposed
Design home.
(m) For a Proposed Design home with a non-storage
type water heater, a 40-gallon storage-type water heater with the prevailing
federal minimum efficiency and with the same fuel as the proposed water heater
shall be assumed for the Standard
Reference Design home. For the case of a Proposed Design home without a proposed water heater, a 40-gallon
storage-type water heater with the prevailing federal minimum efficiency with
the same fuel as the predominant heating fuel type shall be assumed for both
the Proposed Design and Standard Reference Design.
(n)
Tested duct leakage shall be
determined and documented by a Certified Class 1
TABLE
405.5.2(3)
COEFFICIENTS ‘a’ AND ‘b’
Fuel type and End Use |
a |
b |
Electric space heating Fossil fuel* space heating Biomass space heating Electric air conditioning Electric water heating Fossil fuel* water heating |
2.2561 1.0943 0.8850 3.8090 0.9200 1.1877 |
0 0.4043 0.4047 0 0 1.0130 |
*Such as natural gas, LP, fuel oil