32994.1 |
32994.01 PAC-150 x 90° Seam (S1) |
.032" (min.) x 12" thru 20" Wide Aluminum Panel over Wood Deck |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-99.3 Other: Uplift Load for 20" wide panel w/two screws per clip: 6" o/c -99.3 PSF, 12" o/c -89.3 PSF, 18" o/c -79.3 PSF, 24" o/c -69.3 PSF. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_LOAD TABLES 0.032 n0374.03-450-18-r0.pdf FL32994_R5_II_PAC-150 typ install details.pdf Verified By: Architectural Testing, Inc. (an Intertek company) - West Palm Beach, FL Test Reports FL32994_R5_TR_BCIS 0.032 n0374.03-450-18-r0.pdf |
|
32994.2 |
32994.02 PAC-150 x 180° Seam (S2) |
.032" (min.) x 12" thru 20" Wide Aluminum Panel over Wood Deck |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-166.8 Other: Uplift Load for 20" wide panel w/two screws per clip: 12" o/c -166.8 PSF, 18" o/c -142.8 PSF, 24" o/c -118.9 PSF, 30" o/c -94.9 PSF, 36" o/c -71.0 PSF. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_LOAD TABLES 0.032 n0374.03-450-18-r0.pdf FL32994_R5_II_PAC-150 typ install details.pdf Verified By: Architectural Testing, Inc. (an Intertek company) - West Palm Beach, FL Test Reports FL32994_R5_TR_BCIS 0.032 n0374.03-450-18-r0.pdf |
|
32994.3 |
32994.03 PAC-150 x 90° Seam (S1) |
24 ga. (min.) x 12" thru 20" Wide Steel Panel over Wood Deck |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-114.3 Other: Uplift Load for 20" wide panel w/two screws per clip: 6" o/c -114.3 PSF, 12" o/c -99.3 PSF, 18" o/c -84.3 PSF, 24" o/c -69.3 PSF. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_LOAD TABLES 24 ga. n0374.04-450-18-r0.pdf FL32994_R5_II_PAC-150 typ install details.pdf Verified By: Architectural Testing, Inc. (an Intertek company) - West Palm Beach, FL Test Reports FL32994_R5_TR_BCIS 24 ga. n0374.04-450-18-r0.pdf |
|
32994.4 |
32994.04 PAC-150 x 180° Seam (S2) |
24 ga. (min.) x 12" thru 20" Wide Steel Panel over Wood Deck |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-136.8 Other: Uplift Load for 20" wide panel w/two screws per clip: 12" o/c -136.8 PSF, 18" o/c -122.2 PSF, 24" o/c -107.6 PSF, 30" o/c -93.1 PSF, 36" o/c -78.5 PSF. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_LOAD TABLES 24 ga. n0374.04-450-18-r0.pdf FL32994_R5_II_PAC-150 typ install details.pdf Verified By: Architectural Testing, Inc. (an Intertek company) - West Palm Beach, FL Test Reports FL32994_R5_TR_BCIS 24 ga. n0374.04-450-18-r0.pdf |
|
32994.5 |
32994.05 SNAP-CLAD (S1) |
.032" (min.) x 12" thru 18" Wide Aluminum Panel over Wood Deck |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-153.5 Other: Uplift Load for 18" wide panel w/two screws per clip: 6" o/c -153.5 PSF, 12" o/c -135.5 PSF, 18" o/c -117.5 PSF, 24" o/c -99.5 PSF, 30" o/c -81.5 PSF, 36" o/c -63.5 PSF. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_LOAD TABLE M5239.04-450-18 SNCLD 0.032 ALUM OVER WOOD.pdf FL32994_R5_II_Snap-Clad typ install details.pdf Verified By: Architectural Testing, Inc. (an Intertek company) - West Palm Beach, FL Test Reports FL32994_R5_TR_m5239.04-450-18-r0 SNCLD 0.032 ALUM OVER WOOD.pdf |
|
32994.6 |
32994.06 SNAP-CLAD (S2) |
.040" (min.) x 12" thru 18" Wide Aluminum Panel over Wood Deck |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-174.2 Other: Uplift Load for 18" wide panel w/two screws per clip: 6" o/c -174.2 PSF, 12" o/c -158.1 PSF, 18" o/c -141.9 PSF, 24" o/c -128.8 PSF, 30" o/c -109.6 PSF, 36" o/c -93.5 PSF. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_LOAD TABLE M5239.03-450-18 SNCLD 0.040 ALUM OVER WOOD.pdf FL32994_R5_II_Snap-Clad typ install details.pdf Verified By: Architectural Testing, Inc. (an Intertek company) - West Palm Beach, FL Test Reports FL32994_R5_TR_m5239.03-450-18-r0 SNCLD 0.040 ALUM OVER WOOD.pdf |
|
32994.7 |
32994.07 SNAP-CLAD (S3) |
24 ga. (min.) x 12" thru 18" Wide Steel Panel over Wood Deck |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-144.5 Other: Uplift Load for 18" wide panel w/two screws per clip: 6" o/c -144.5 PSF, 12" o/c -128.1 PSF, 18" o/c -111.9 PSF, 24" o/c -95.8 PSF, 30" o/c -79.6 PSF, 36" o/c -63.5 PSF. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_LOAD TABLE M5239.05-450-18 SNCLD 24 GA. STEEL OVER WOOD.pdf FL32994_R5_II_Snap-Clad typ install details.pdf Verified By: Architectural Testing, Inc. (an Intertek company) - West Palm Beach, FL Test Reports FL32994_R5_TR_m5239.05-450-18-r0 SNCLD 24 GA. STEEL OVER WOOD.pdf |
|
32994.8 |
32994.08 Tite-Loc Plus (S1) |
.032" (min.) x 12" thru 18" Wide Aluminum Panel over Wood Deck |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-174.2 Other: Uplift Load for 18" wide panel w/two screws per clip: 6" o/c -174.2 PSF, 12" o/c -159.2 PSF, 18" o/c -144.2 PSF, 24" o/c -129.2 PSF, 30" o/c -96.4 PSF, 36" o/c -63.5 PSF. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_LOAD TABLE M5239.02-450-18 TLP 0.032 ALUM OVER WOOD.pdf FL32994_R5_II_Tite-Loc Plus typ install details.pdf Verified By: Architectural Testing, Inc. (an Intertek company) - West Palm Beach, FL Test Reports FL32994_R5_TR_m5239.02-450-18-r0 TLP 0.032 ALUM OVER WOOD.pdf |
|
32994.9 |
32994.09 Tite-Loc Plus (S2) |
24 ga. (min.) x 12" thru 18" Wide Steel Panel over Wood Deck |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-204.5 Other: Uplift Load for 18" wide panel w/two screws per clip: 6" o/c -204.5 PSF, 12" o/c -176.3 PSF, 18" o/c -148.1 PSF, 24" o/c -119.9 PSF, 30" o/c -91.7 PSF, 36" o/c -63.5 PSF. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_LOAD TABLE M5239.01-450-18 TLP 24 GA. STEEL OVER WOOD.pdf FL32994_R5_II_Tite-Loc Plus typ install details.pdf Verified By: Architectural Testing, Inc. (an Intertek company) - West Palm Beach, FL Test Reports FL32994_R5_TR_m5239.01-450-18-r0 TLP 24 GA. STEEL OVER WOOD.pdf |
|
32994.10 |
32994.10 PAC T-250 (S1) |
16" Wide x .032" (min) Aluminum Panel w/Continuous Clips |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-140.40 Other: Uplift load for 16" wide panel is -78.00 PSF w/screw spacing of 60" o.c. and -140.40 PSF w/screw spacing of 24" o.c. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_T-250 Installation Details.pdf Verified By: Farabaugh Engineering and Testing, Inc. Test Reports FL32994_R5_TR_T-250 E1592 .032 aluminum.pdf |
|
32994.11 |
32994.11 PAC T-250 (S2) |
16" Wide x .032" (min) Aluminum Panel w/Individual Clips |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-65.00 Other: Uplift load for 16" wide panel is -28.60 PSF w/clip spacing of 60" o.c. and -65.00 PSF w/clip spacing of 24" o.c. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_T-250 Installation Details.pdf Verified By: Farabaugh Engineering and Testing, Inc. Test Reports FL32994_R5_TR_T-250 E1592 .032 aluminum.pdf |
|
32994.12 |
32994.12 PAC T-250 (S3) |
16" Wide x .040" (min) Aluminum Panel w/Continuous Clips |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-127.15 Other: Uplift load for 16" wide panel is -91.00 PSF w/screw spacing of 60" o.c. and -127.15 PSF w/screw spacing of 24" o.c. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_T-250 Installation Details.pdf Verified By: Farabaugh Engineering and Testing, Inc. Test Reports FL32994_R5_TR_T-250 E1592 .040 aluminum.pdf |
|
32994.13 |
32994.13 PAC T-250 (S4) |
16" Wide x .040" (min) Aluminum Panel w/Individual Clips |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-78.00 Other: Uplift load for 16" wide panel is -38.75 PSF w/clip spacing of 60" o.c. and -78.00 PSF w/clip spacing of 24" o.c. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_T-250 Installation Details.pdf Verified By: Farabaugh Engineering and Testing, Inc. Test Reports FL32994_R5_TR_T-250 E1592 .040 aluminum.pdf |
|
32994.14 |
32994.14 PAC T-250 (S5) |
16" Wide x 24 Ga. (min) Steel Panel w/Continuous Clips |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-119.85 Other: Uplift load for 16" wide panel is -98.80 PSF w/screw spacing of 60" o.c. and -119.85 PSF w/screw spacing of 24" o.c. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_T-250 Installation Details.pdf Verified By: Farabaugh Engineering and Testing, Inc. Test Reports FL32994_R5_TR_T-250 E1592 24 ga. steel.pdf |
|
32994.15 |
32994.15 PAC T-250 (S6) |
16" Wide x 24 Ga. (min) Steel Panel w/Individual Clips |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-65.00 Other: Uplift load for 16" wide panel is -33.80 PSF w/clip spacing of 60" o.c. and -65.00 PSF w/clip spacing of 24" o.c. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_T-250 Installation Details.pdf Verified By: Farabaugh Engineering and Testing, Inc. Test Reports FL32994_R5_TR_T-250 E1592 24 ga. steel.pdf |
|
32994.16 |
32994.16 PAC T-250 (S7) |
16" Wide x 22 Ga. (min) Steel Panel w/Continuous Clips |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-147.95 Other: Uplift load for 16" wide panel is -91.00 PSF w/screw spacing of 60" o.c. and -147.95 PSF w/screw spacing of 24" o.c. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_T-250 Installation Details.pdf Verified By: Farabaugh Engineering and Testing, Inc. Test Reports FL32994_R5_TR_T-250 E1592 22 ga. steel.pdf |
|
32994.17 |
32994.17 PAC T-250 (S8) |
16" Wide x 22 Ga. (min) Steel Panel w/Individual Clips |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-72.80 Other: Uplift load for 16" wide panel is -46.85 PSF w/clip spacing of 60" o.c. and -72.80 PSF w/clip spacing of 24" o.c. Install per manufacturer's details. Not for use in HVHZ. |
Installation Instructions FL32994_R5_II_T-250 Installation Details.pdf Verified By: Farabaugh Engineering and Testing, Inc. Test Reports FL32994_R5_TR_T-250 E1592 22 ga. steel.pdf |
|
32994.18 |
7.2 Panel (S1) 2' - 5' Spans |
36" Wide x 24 Ga. (min.) Steel |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-159.70 Other: Allowable Wind Uplift Pressure, psf. Panel Span,
ft: -159.70 @ 2', -132.70 @ 3', -105.80 @ 4', -78.85 @
5'. Not for use in HVHZ. Safety Factor of 2.0 is included. |
Installation Instructions FL32994_R5_II_Installation Details ALL.pdf FL32994_R5_II_Negative Load Table 2 to 5 FT spans.pdf Verified By: Farabaugh Engineering and Testing, Inc. Test Reports FL32994_R5_TR_T277-08_e1592_24_GA.pdf |
|
32994.19 |
7.2 Panel (S2) 2' - 5' Spans |
36" Wide x .032" (min.) Aluminum |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-104.05 Other: Allowable Wind Uplift Pressure, psf. Panel Span,
ft: -104.05 @ 2', -89.70 @ 3', -75.40 @ 4', -61.15 @ 5',
Not for use in HVHZ. Safety Factor of 2.0 is included. |
Installation Instructions FL32994_R5_II_Installation Details ALL.pdf FL32994_R5_II_Negative Load Table 2 to 5 FT spans.pdf Verified By: Farabaugh Engineering and Testing, Inc. Test Reports FL32994_R5_TR_T281-08_e1592_032.pdf |
|
32994.20 |
7.2 Panel (S3) 1' - 5' Spans |
36" Wide x .050" (min.) Aluminum |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-192.10 Other: Allowable Wind Uplift Pressure, psf. Panel Span,
ft: -192.10 @ 1', -162.20 @ 2', -132.40 @ 3', -102.50 @
4', -72.75 @ 5'. Not for use in HVHZ. Safety Factor of 2.0
is included. |
Installation Instructions FL32994_R5_II_Installation Details ALL.pdf FL32994_R5_II_Negative Load Table 1 to 5 FT spans.pdf Verified By: Farabaugh Engineering and Testing, Inc. Test Reports FL32994_R5_TR_ALL test reports 1 FT to 5 FT spans.pdf |