19588.1 |
1 - American Standard Condenser (Ground Mounted) |
Steel Tie-Down Clip System (For Use with Mechanical Units at Ground) |
Limits of Use Approved for use in HVHZ: Yes Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +60/-60 Other: Maximum Rated Wind Pressures (ASD): ± 60 psf Lateral, 0 psf Uplift. (Per the codes and standards referenced, no uplift is required at grade). See the "Installation Instructions" PDF for limitations, conditions, and more information.
|
Installation Instructions FL19588_R6_II___DWG1.pdf Verified By: Frank Bennardo, P.E. 0046549 Created by Independent Third Party: Yes Evaluation Reports FL19588_R6_AE___EVAL1.pdf Created by Independent Third Party: Yes |
|
19588.2 |
2 - American Standard Condenser (Roof Mounted) |
Steel Tie-Down Clip System (For Use with Mechanical Units at Roof) |
Limits of Use Approved for use in HVHZ: Yes Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +200/-200 Other: Maximum Rated Wind Pressures (ASD): ± 200 psf Lateral, 100 psf Uplift. See the "Installation Instructions" PDF for limitations, conditions, and more information.
|
Installation Instructions FL19588_R6_II___DWG2.pdf Verified By: Frank Bennardo, P.E. 0046549 Created by Independent Third Party: Yes Evaluation Reports FL19588_R6_AE___EVAL2.pdf Created by Independent Third Party: Yes |
|
19588.3 |
3 - Trane Condenser (Ground Mounted) |
Steel Tie-Down Clip System (For Use with Mechanical Units at Ground) |
Limits of Use Approved for use in HVHZ: Yes Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +60/-60 Other: Maximum Rated Wind Pressures (ASD): ± 60 psf Lateral, 0 psf Uplift. (Per the codes and standards referenced, no uplift is required at grade). See the "Installation Instructions" PDF for limitations, conditions, and more information. |
Installation Instructions FL19588_R6_II__DWG3.pdf Verified By: Frank Bennardo, P.E. 0046549 Created by Independent Third Party: Yes Evaluation Reports FL19588_R6_AE___EVAL3.pdf Created by Independent Third Party: Yes |
|
19588.4 |
4 - Trane Condenser (Roof Mounted) |
Steel Tie-Down Clip System (For Use with Mechanical Units at Roof) |
Limits of Use Approved for use in HVHZ: Yes Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +200/-200 Other: Maximum Rated Wind Pressures (ASD): ± 200 psf Lateral, 100 psf Uplift. See the "Installation Instructions" PDF for limitations, conditions, and more information. |
Installation Instructions FL19588_R6_II___DWG4.pdf Verified By: Frank Bennardo, P.E. 0046549 Created by Independent Third Party: Yes Evaluation Reports FL19588_R6_AE___EVAL4.pdf Created by Independent Third Party: Yes |
|
19588.5 |
5 - American Standard Units |
Applicable for Ground & Roof Mounted installations. |
Limits of Use Approved for use in HVHZ: Yes Approved for use outside HVHZ: Yes Impact Resistant: No Design Pressure: +200/-200 Other: Maximum Rated Wind Pressures (ASD): ± 200 psf Lateral, 100 psf Uplift. See the "Installation Instructions" PDF for limitations, conditions, and more information. |
Installation Instructions FL19588_R6_II__DWG5.pdf Verified By: Frank Bennardo, P.E. 0046549 Created by Independent Third Party: Yes Evaluation Reports FL19588_R6_AE__EVAL5.pdf Created by Independent Third Party: Yes |
|
19588.6 |
6 - Trane Units |
Applicable for Ground & Roof Mounted installations. |
Limits of Use Approved for use in HVHZ: Yes Approved for use outside HVHZ: Yes Impact Resistant: No Design Pressure: +200/-200 Other: Maximum Rated Wind Pressures (ASD): ± 200 psf Lateral, 100 psf Uplift. See the "Installation Instructions" PDF for limitations, conditions, and more information. |
Installation Instructions FL19588_R6_II__DWG6.pdf Verified By: Frank Bennardo, P.E. 0046549 Created by Independent Third Party: Yes Evaluation Reports FL19588_R6_AE__EVAL6.pdf Created by Independent Third Party: Yes |